ShedSafe Site Specific Design Criteria TSSC214004
2 Boston Ct
Varsity Lakes QLD 4227
Phone: 0756578843
Fax: 07 5657 8899
SITE SPECIFIC
DESIGN CRITERIA
ANALYSIS
P re p are d f o r: I s s ue d :
22/08/2021
Sup p lie r: B uild ing D e t ails :
THE Shed Company Sunshine Span: 8
Coast Length: 9
Avg. Height: 5.736
A s s e s s m e nt R e f :
STX21080691XJ
C e rt if ie d b y :
J. Ronaldson
for and on behalf of
Apex Engineering Group PTY LTD
(ACN 632 588 562)
Member Ins titution of Engineers (Aus t.), CPEng (NER Structural) Regn. No. 5276680
Regis tered Profes s ional Engineer (Structural) - Queens land: Regn. No. 24223
Regis tered Profes s ional Engineer (Structural) - Victoria: Regn. No. EC67493
Regis tered Building D es igner & Profes s ional Engineer (Structural) - Tas mania: Regn. No. 185770492
Page 1 of 3
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalSearchable page text hides email addresses. Original files are unchanged and may show email addresses.
Full text of the other 2 pages
Page 2
Sit e L o c at io n:
Geographic coordinates of
-26.37313,152.85327
Generally described as:
9 Rules Rd Pomona QLD 4568
Page 2 of 3
Page 3
Execut ive Summary - Sit e Specific Analysis
The design analysis of the building has not been considered for each of the 4 orthogonal directions.
Hence the maximum wind speed in any of the 8 cardinal directions has been used as the design wind
speed. This is a conservative approach.
Each cardinal direction has been considered and the results are summarised below
F ac t o r N NE E SE S SW W NW
Wind Region B
Importance level (IL) 2
Regional Wind Speed (Vr) 57.0
Terrain Category (TC) 2.86 2.88 2.83 2.98 2.99 2.87 2.7 2.94
Terrain Category Multiplier (Mz) 0.84 0.84 0.85 0.83 0.83 0.84 0.86 0.84
Shielding Multiplier (Ms) 1 1 1 1 1 1 1 1
Topographic Multiplier (Mt) 1 1 1 1 1 1 1 1
Wind Direction Multiplier 1 (Md1) 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95
Site specific design wind speed (Vsite1) 45.7 45.6 45.8 45 45 45.6 46.5 45.3
Wind Direction Multiplier 2 (Md2) 1 1 1 1 1 1 1 1
Site specific design wind speed (Vsite2) 48.1 48 48.2 47.4 47.4 48 48.9 47.6
Design Wind Speed for the resultant forces and overturning moments on the complete
46.5 m/s
(Vsite1) building and wind actions on major structural elements.
Design Wind Speed for all other cases, including cladding and immediate supporting
48.9 m/s
(Vsite2) members (Purlins and Girts)
Snow Load Nil
Seismic Factor Nil
Durability Alert No