ShedSafe Site Specific Design Criteria TSSC214004

of 3

Page text shows just the words. Original shows the document exactly as it was published.

Execut ive Summary - Sit e Specific Analysis

The design analysis of the building has not been considered for each of the 4 orthogonal directions.
Hence the maximum wind speed in any of the 8 cardinal directions has been used as the design wind
speed. This is a conservative approach.

Each cardinal direction has been considered and the results are summarised below



                      F ac t o r                     N    NE      E     SE     S     SW    W      NW
                    Wind Region                                              B
              Importance level (IL)                                          2
            Regional Wind Speed (Vr)                                        57.0
              Terrain Category (TC)                2.86   2.88   2.83   2.98 2.99    2.87 2.7 2.94
         Terrain Category Multiplier (Mz)          0.84   0.84   0.85   0.83 0.83    0.84 0.86 0.84
             Shielding Multiplier (Ms)               1      1      1      1      1     1    1    1
            Topographic Multiplier (Mt)              1      1      1      1      1     1    1    1
         Wind Direction Multiplier 1 (Md1)         0.95   0.95   0.95   0.95 0.95    0.95 0.95 0.95
     Site specific design wind speed (Vsite1)      45.7   45.6   45.8    45     45   45.6 46.5 45.3

         Wind Direction Multiplier 2 (Md2)          1       1     1    1    1         1    1    1
     Site specific design wind speed (Vsite2)      48.1    48    48.2 47.4 47.4      48   48.9 47.6



Design Wind Speed          for the resultant forces and overturning moments on the complete
                  46.5 m/s
(Vsite1)                   building and wind actions on major structural elements.

Design Wind Speed          for all other cases, including cladding and immediate supporting
                  48.9 m/s
(Vsite2)                   members (Purlins and Girts)

Snow Load           Nil

Seismic Factor      Nil

Durability Alert    No




                                                                                               Page 3 of 3
Log in to download the original file

ShedSafe Site Specific Design Criteria TSSC214004.pdf · 380 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.