STAIR AND BALUSTRADES: ALL BALUSTRADES AND HANDRAILS TO BE
1000 MIN ABOVE FINISHED FLOOR LEVEL, 865MM MIN ABOVE STAIR
NOSINGS AND HAVE NO OPENINGS GREATER THAN 125MM, IN
ACCORDANCE WITH NCC VOL 2 2019 PART 3.9.2. FLOORS OVER 4M
MUST NOT FACILITATE CLIMBING BETWEEN 150MM AND 760MM FOR
WET AREAS: ALL WET AREAS ARE TO BE WATERPROOFED
THROUGHOUT WITH A PROPRIETARY WATERPROOFING SYSTEM
INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS
RECOMMENDATIONS AND NCC REQUIREMENTS, WITH JUNCTIONS
BETWEEN WALL AND FLOOR FLASHED TO PREVENT MOISTURE
ARTICULATION JOINTS: PROVIDE ARTICULATION JOINTS TO COMPLY
WITH ENGINEERS DESIGN AND "CEMENT AND CONCRETE
ASSOCIATION CONSTRUCTION NOTE TN9".
POOL: CONTRACTOR TO CONFIRM HEIGHTS/DEPTHS/STEPS AND
PLUMBING/ELECTRICAL REQUIREMENTS AND LOCATIONS PRIOR TO
010.02
BALUSTRADES TO STAIRS. MINIMUM STAIR CLEARANCE 2.0M MEASURE PENETRATION INTO WALLS. BUILDER TO PROVIDE CERTIFICATE OF CONSTRUCTION.
FROM TOE OF NOSING. STAIRS MUST COMPLY WITH THE NCC FOR SLIP INSTALLATION AND COMPLIANCE. PROVIDE MECHANICAL NOTES & LEGENDS
RESISTANCE. BUILDER/STAIR MANUFACTURER TO CHECK STAIR VENTILATION TO COMPLY WITH AS1668 TO ALL WET AREAS AND FIRE SAFETY: SMOKE ALARM DETECTORS TO BE INSTALLED IN
COMPLIANCE PRIOR TO STAIR INSTALLATION. IF THERE ARE ISSUES ROOMS NOT NATURALLY VENTILATED. ALL TIMBER OR STEEL FRAMED ACCORDANCE WITH AS 3786-2014, NCC PART 3.7.2 & LOCAL QFES GENERAL NOTES
WITH HEIGHT, CONTACT ARCHITECT AS SOON AS POSSIBLE. STEPS TO WALLS TO WET AREAS TO BE LINED WITH FC OR APPROVED WET AREA LEGISLATION. SMOKE ALARMS IN THE DWELLING MUST: BE
BE PROVIDED WHERE FALL FROM DWELLING EXCEEDS 190MM. CLADDING, FIXED IN ACCORDANCE WITH MANUFACTURER'S PHOTOELECTRIC (AS3786-2014) ; AND NOT ALSO CONTAIN AN
SPECIFICATIONS. SUPSPENDED TIMBER OR STEEL FRAMED FLOORS TO IONISATION SENSOR; AND BE HARD-WIRED TO THE MAINS POWER
GLAZING: ALL ALUMINIUM AND GLAZING TO COMPLY WITH AS 2047 HAVE WET AREA FLOORING TO ALL WET AREAS, FIXED IN SUPPLY WITH A SECONDARY POWER SOURCE (I.E. BATTERY); AND BE
AND NCC VOL 2 2019 PART 3.6 AND ANY OTHER INDUSTRY STANDARDS ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. INTERCONNECTED WITH EVERY OTHER SMOKE ALARM IN THE
/ LEGISLATION, AND MUST BE DESIGNED FOR THE WIND LOADS DWELLING SO ALL ACTIVATE TOGETHER. SMOKE DETECTORS TO BE
SPECIFIC TO THE SITE AND BUILDING. FOR WINDOWS WHERE THE FALL SANITARYWARE: TYPICAL HEIGHTS OF ACCESSORIES: TOILET ROLL LOCATED: IN EACH BEDROOM; AND HALLWAYS (OR ROOMS) THAT
HEIGHT FROM FLOOR TO GROUND IS 2M OR GREATER, ALL OPENINGS HOLDER: 700MM ABOVE FFL; TOWEL RAIL 1100MM ABOVE FFL; HOSE CONNECT BEDROOMS; AND ON THE MOST LIKELY PATH OF TRAVEL TO
WITHIN 1700MM OF THE FLOOR MUST BE PROTECTED WITH A FALL COCK TO FRIDGE RECESS FFL 1900MM ABOVE FFL; SHOWER RAIL AN EXIT ON ANY LEVELS THAT DO NOT CONTAIN BEDROOMS. SMOKE
PREVENTION DEVICE OR RESTRICTED TO A MAXIMUM OPENING OF 1900MM ABOVE FFL; SHOWER RAIL INLET: 1800MM ABOVE FFL, DETECTORS MUST BE PLACED MIN. 300MM AWAY FROM WALLS AND
125MM AS PER NCC REQUIREMENTS. ALL GLAZING IS TO BE IN SHOWER MIXER 1200MM ABOVE FFL. LIGHT FITTINGS, AND MIN. 400MM FROM AIR-CONDITIONING VENTS OR
ACCORDANCE WITH AS1288 AND AS 2047. WINDOW SIZES NOMINATED BUSHFIRE HAZARD AREAS: BUSHFIRE HAZARD AREAS ARE TO COMPLY BLADES OF A CEILING FAN.
ARE NOMINAL ONLY. ACTUAL SIZE MAY VARY ACCORDING TO WITH AS3959 & NCC VOL 2 2019 - PART 2.3, 3.7 & 3.10.5 AND AN
MANUFACTURER. WINDOWS TO BE FLASHED ALL AROUND. APPROVED BUSHFIRE RISK ASSESSMENT REPORT AND / OR BUSHFIRE SUSTAINABLE BUILDINGS: ALL WORKS TO BE IN ACCORDANCE WITH
MANAGEMENT PLAN (AS PREPARED BY A QUALIFIED BUSH FIRE RISK NCC REQUIREMENTS AND APPROVED ENERGY EFFICIENCY REPORT
LININGS: EXTERNAL CLADDINGS AND INTERNAL LININGS TO BE FIXED ASSESSOR). AND ESD CONSULTANT CERTIFICATES IF APPLICABLE. MP 4.1 -
AND FINISHED IN ACCORDANCE WITH MANUFACTURER'S ACCEPTABLE SOLUTIONS: HOME ADDITIONS TO HAVE ENERGY
SPECIFICATION. ALL UNTREATED SOFTWOOD TIMBERS USED IN ROOF GAS: GAS METER TO BE INSTALLED AS PER AS/NZS 5601 OR GAS EFFICIENT LIGHTING FOR A MINIMUM OF 80% OF TOTAL FIXED
FRAMING, ARE TO BE FULLY CLAD. THE BUILDER SHALL TAKE ALL STEPS CYLINDERS TO BE INSTALLED AS PER AS/NZS 1596:2014 & AS/NZS INTERNAL LIGHTING; HOME ADDITIONS TO HAVE NEW
NECESSARY TO ENSURE THE STABILITY AND GENERAL WATER 5601.1:2013 FOR AN EXCHANGE CYLINDER APPLICATION. AIRCONDITIONERS WITH AN E.E.R OF 2.9 MIN; HOME ADDITIONS TO
TIGHTNESS OF ALL NEW AND/OR EXISTING STRUCTURES DURING ALL HAVE ALL SHOWER ROSES AND TAPS SERVING LAUNDRY TUBS,
WORKS. ELECTRICAL FITTINGS: TYPICAL HEIGHTS OF LIGHT SWITCHES: 1300MM KITCHEN SINKS AND BASINS WITH A MIN 3 STAR WATER EFFICIENCY
ABOVE FFL. TYPICAL HEIGHTS OF POWER OUTLETS: GENERAL: 300MM LABELLING AND STANDARDS RATING; ALL TOILET CISTERNS TO HAVE A
EXPANSION JOINTS, WALLS: 5MM. FLOORS: 8MM. FILL BOTH WITH ABOVE FFL; KITCHEN FRIDGE: 1900MM ABOVE FFL; BATH / ENSUITE / DUAL FLUSH SYSTEM AND A MIN 4 STAR WATER EFFICIENCY
SILICONE RUBBER. GROUT FOR WALL: EPOXY BASED MILDEW LAUNDRY: 1100MM ABOVE FFL. LOCATION OF FIXTURES AND FITTINGS LABELLING AND STANDARDS RATING. THE SUB-FLOOR SPACE OF A
RESISTANT. GROUT FOR FLOORS: PREPARED GROUT TO BE ACID SHOWN ON DRAWINGS ARE INDICATIVE ONLY. FINAL LOCATIONS TO DWELLING MUST BE VENTILATED IN ACCORDANCE WITH NCC VOL 2
RESISTANT. ALL WALL TILES TO HAVE FC SUBSTRATE. TILING LAYOUTS BE CONFIRMED WITH ARCHITECT OR CLIENT ON SITE. ELECTRICAL 2019 PART 3.4.1. INSULATION MUST COMPLY WITH AS/NZS 4859.1 AND
SHOWN ARE INDICATIVE ONLY, FINAL SETOUT TO BE DETERMINED ON CONTRACTOR TO ALLOW FOR CONNECTION OF POWER TO A/C, APPROVED ENERGY EFFICIENCY REPORT AND ESD CONSULTANT
SITE BY THE TILING CONTRACTOR. POOL AND HWS PLANT, TO BE CO-ORINATED WITH SPECIALIST CERTIFICATES IF APPLICABLE.
CONTRACTORS / SUPPLIERS / MANUFACTURERS.
SANITARY COMPARTMENTS: WATER CLOSETS (WC'S) TO HAVE A DOCUMENTATION: THE CONTRACTOR SHALL CARRY OUT WORKS IN
MINIMUM CLEAR WIDTH OF 900MM. PROVIDE REMOVABLE HINGES TO JOINERY ITEMS: SHALL INCLUDE MANUFACTURED CASEWORK ITEMS, ACCORDANCE WITH THE SIGNED DRAWINGS AND SCHEDULES AND
DOORS OF SANITARY COMPARTMENTS TO COMPLY WITH NCC AND BE INCLUDING: KITCHEN CABINETS AND CUPBOARDS; BATHROOM ANYTHING REASONABLE INFERRED, AND WITH THE CONDITIONS OF
READILY REMOVABLE FROM OUTSIDE UNLESS THERE IS A CLEAR CABINETS; ROBES. UNLESS NOTED OTHERWISE: NO EXPOSED GABLES CONTRACT, AND IN ACCORDANCE WITH THE DIRECTIONS AND TO THE
SPACE OF AT LEAST 1200MM B/W CLOSET PAN WITHIN THE SANITARY TO JOINERY; ALL EDGES TO BE SQUARE; ALL JOINERY UNITS TO HAVE SATISFACTION OF THE CLIENT & ARCHITECT, WHOSE INTERPRETATION
COMPARTMENT AND THE NEAREST PART OF THE DOORWAY. PROVIDE CARCASS CONSTRUCTED OF 16MM OR 25MM THICK PRE-FINISHED OF THE CONTRACT DOCUMENTS SHALL BE FINAL. THE DRAWINGS AND
ADEQUATE CLEARANCE AT TOP OF DOOR TO SUIT HINGES. BOARD; ALL LAMINATED JOINERY TO HAVE MATCHING ABS EDGING; SPECIFICATIONS/SCHEDULES SHALL BE CONSIDERED
ALL TIMBER VENEER JOINERY TO HAVE MATCHING SOLID TIMBER COMPLEMENTARY, AND ANY WORK AND/OR MATERIALS ABSENT
APPLIANCES & EQUIPMENT: BUILDER TO CO-ORDINATE ALL EDGING; ALL DRAWERS TO HAVE HIGH SIDES; ALL ADJUSTABLE FROM ONE BUT PRESENT OR IMPLIED IN THE OTHER SHALL BE
APPLIANCE AND EQUIPMENT LOCATIONS ON SITE AND WITH JOINER. SHELVES SHALL BE SUPPORTED ON BRASS FERRULES AND BUSHES - FURNISHED AS IF THEY WERE PRESENT IN BOTH.
INSTALLATION AND FINAL CONNECTION BY THE CONTRACTOR. SUPPORTS TO BE AT 50MM CENTRES; ALL HINGED DOORS TO BE HUNG
JOINER TO CONFIRM ALL APPLIANCE AND EQUIPMENT TOLERANCES ON FULLY CONCEALED ALL METAL TYPE WIDE ANGLE HINGES; FINAL CERTIFICATE: AT COMPLETION OF WORK, BUILDER TO OBTAIN
AND REQUIREMENTS IN JOINERY PRIOR TO FABRICATION. BUILDER TO PROVIDE ADEQUATE NOGGINGS TO SUPPORT ALL AND SUPPLY A CERTIFICATE OF CLASSIFICATION FROM A BUILDING
BATHROOM ACCESSORIES AND SUSPENDED JOINERY; FINISH TO CERTIFIER.
INTERNAL PAINTING: UNLESS NOTED OTHERWISE PAINT SYSTEM TO BE UNDERSIDE OF OVERHEAD CUPBOARDS TO MATCH JOINERY FRONTS.
DULUX APPROVED 3 COAT SYSTEM - LOW SHEEN FINISH. COLOURS TO ALL JOINERY TO BE SITE MEASURED ONCE LININGS ARE IN PLACE.
BE SUPPLIED BY CLIENT & ARCHITECT DURING CONTRACT AND CONFIRM ANY DISCREPANCIES PRIOR TO FABRICATION.
APPLIED AS PER DULUX'S RECOMMENDATIONS AND GUIDELINES.
NOTES & LEGENDS APARTMENT FOR BRIGITTE AND KRIS CD - 010.02
B
H
RT
NO
GENERAL NOTES UNIT 8 / PACIFIC OUTLOOK 47 ELANDA STREET, SUNSHINE BEACH QLD 4567 14.12.22 DEVELOPMENT APPROVAL ISSUE REV
Do not scale from drawings. Dimensions are to be checked on site prior to commencement of work. Discrepancies are to be brought to the attention of Minnow Studio. Any dimensions not nominated must be referred to Minnow Studio for confirmation. The concepts and information contained in this document are the copyright of Minnow Studio.
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Proposal Plans-compressed (1).pdfRelated documentApplication case desk ↗
About this file
- File size
- 12.7 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.