Skip to the record
For the highest quality transcripts.

Council archive · source document

7550J 191022 Construction Issue · OPW19/0245

Attached to the e-mail Jetty application OPW19/0245 - 10 The Peninsula, Noosaville.

of 7

Text shows just the words. Original shows the document exactly as it was published.

                                                                                                                                   GENERAL                                                                                                            DIMENSIONS/LEVELS                                                                                                 CONSTRUCTABILITY CONSTRAINTS:
                                                                                                                                   G1    STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE                         L1. CONSTRUCTION SHALL BE SET OUT USING SURVEY BENCHMARKS PROVIDED BY COUNCIL.                                                               CC1. CONSTRUCTABILITY CONSTRAINTS:
                                                                                                                                         SPECIFICATION, ARCHITECTURAL, AND OTHER CONSULTANTS' DOCUMENTS.
                                                                                                                                                                                                                           L2. ALL LEVELS AND SETOUT POINTS ARE SHALL BE CONFIRMED ON SITE BY REGISTERED                                                                     A)   PROTECT ALL EXISTING INFRASTRUCTURE (EG CULVERT CROSSING, PAVEMENTS,
                                                                                                                                   G2    REFER TO THE ARCHITECTURAL DRAWINGS FOR SETOUT. NO DIMENSIONS SHALL BE            SURVEYOR PRIOR TO CONSTRUCTION. ADVISE ANY DISCREPANCY BEFORE PROCEEDING.                                                                              FENCING & ELECTRICAL POLES/WIRES) FROM ANY DAMAGE.
                                                                                                                                         OBTAINED BY SCALING FROM DRAWINGS.
                                                                                                                                                                                                                           L3. DIMENSION STANDARDS:                                                                                                                       B)      ALLOW OF LIKELIHOOD OF FLOW WITHIN THE WATERWAY: EXISTING WATERWAY ARE
                                                                                                                                   G3    UNLESS OTHERWISE NOTED (UNO), ALL LEVELS ARE IN METRES AND ALL DIMENSIONS ARE IN      - REDUCED LEVELS, CHAINAGES AND COORDINATES ARE ALL IN METRES.                                                                                     FLOODED MULTIPLE TIMES PER YEAR. PROTECT CONSTRUCTION EQUIPMENT AND
                                                                                                                                         MILLIMETRES.                                                                          - CIVIL DRAWINGS (SKC SERIES): ALL OTHER DIMENSIONS ARE IN METRES (m).                                                                             WORKS.
                                                                                                                                                                                                                               - STRUCTURAL DRAWINGS (SKS SERIES): ALL OTHER DIMENSIONS ARE IN MILLIMETRES (mm).
                                                                                                                                   G4    THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE STABILITY OF THE                                                                                                                                                       CC2. NO WORK TO COMMENCE ON SITE UNTIL:
                                                                                                                                         STRUCTURE UNTIL ITS COMPLETION AND SHALL ENSURE THAT NO PART OF THE STRUCTURE     L4. ALL LEVELS ARE TO AUSTRALIAN HEIGHT DATUM.                                                                                                    - OFFICIAL PRE-START MEETING HELD AND PRE-START MEETING MINUTES ISSUED
                                                                                                                                         IS OVER-STRESSED BY EXCESSIVE LOADING.                                                                                                                                                                                              - CONTRACTOR'S MANAGEMENT PLANS SUBMITTED (SITE, TRAFFIC, ENVIRONMENT,
                                                                                                                                                                                                                           L5. DIMENSIONS SHALL NOT BE SCALED FROM DRAWINGS.                                                                                                 SAFETY) FOR SUPERINTENDENT'S REVIEW.
                                                                                                                                   G5    ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE CURRENT VERSION
                                                                                                                                         OF THE APPLICABLE STANDARD EXCEPT WHERE VARIED BY THE SPECIFICATION AND/OR        L6. DESIGN USES DIGITAL TERRAIN MODEL GENERATED FROM THE SITE SURVEY. SOME                                                                   DRIVEN PILES:
                                                                                                                                         DRAWINGS. APPLICABLE CODES OF PRACTICE INCLUDE BUT ARE NOT LIMITED TO THE             ELEMENTS ARE INTERPOLATED AND MAY VARY FROM THE ACTUAL SITE CONDITIONS
                                                                                                                                         FOLLOWING:                                                                                                                                                                                                                     P1.       PILES SHALL BE CONSTRUCTED IN ACCORDANCE WITH AS2159.
                                                                                                                                         AS 1163         STRUCTURAL STEEL HOLLOW SECTIONS
                                                                                                                                         AS 1170         SAA LOADING CODE                                                  DESIGN CRITERIA
                                                                                                                                                                                                                                                                                                                                                                        P2.       CONSTRUCTION CONSTRAINTS: AVOID LOADING EXISTING REVETMENT WALLS.
                                                                                                                                         AS 1289         METHODS OF TESTING SOILS FOR ENGINEERING PURPOSES
                                                                                                                                         AS 1554         WELDING OF STEEL STRUCTURES                                       DC1 THE STRUCTURAL ELEMENTS HAVE BEEN DESIGNED FOR THE FOLLOWING LIVE LOADS
                                                                                                                                                                                                                                                                                                                                                                        P3.       DESIGN LOADS: PILES TO ACHIEVE GEOTECHNICAL CAPACITIES (VERTICAL &
                                                                                                                                         AS 1664         ALUMINIUM STRUCTURES                                                  IN ACCORDANCE WITH AS 1170.1: LIVE LOAD REDUCTIONS ARE NOT APPLICABLE.
                                                                                                                                                                                                                                                                                                                                                                                  HORIZONTAL) SHOWN ON THE DRAWINGS
                                                                                                                                         AS 1684         RESIDENTIAL TIMBER-FRAMED CONSTRUCTION                                ELEMENT              UDL        CONCENTRATED
                                                                                                                                         AS 1720         TIMBER STRUCTURES                                                     ROOF                 0.25 kPa   1.1KN
                                                                                                                                                                                                                                                                                                                                                                        P4.       REQUIRED PILE POSITION TOLERANCES:
                                                                                                                                         AS 2159         PILING CODE                                                           INTERNAL FLOORS      1.5kPa
                                                                                                                                         AS 4100         STEEL STRUCTURES                                                      DECK                 2.0kPa
                                                                                                                                                                                                                                                                                                                                                                                  PLAN POSITION: +/- 50mm AT UNDERSIDE OF EACH GROUND BEAM.
                                                                                                                                         AS 5100         BRIDGE DESIGN                                                         THOROUGHFARES        4.0 kPa
                                                                                                                                                                                                                                                                                                                                                                                  PILE VERTICALITY:
                                                                                                                                         BCA             BUILDING CODE OF AUSTRALIA (NATIONAL CONSTRUCTION CODE)                                                                                                                                                                  - WITHIN 4% FOR ALL PILES
                                                                                                                                                                                                                           DC2 WIND LOADS HAVE BEEN DETERMINED IN ACCORDANCE WITH AS 1170.2 BASED ON:
                                                                                                                                   G6    ANY DISCREPANCY SHALL BE REFERRED TO THE SUPERINTENDENT FOR A DECISION BEFORE         IMPORTANCE LEVEL                2
                                                                                                                                                                                                                                                                                                                                                                        P5.       PILE TOE LEVELS ON THE DRAWINGS ARE ESTIMATED LEVELS. ACTUAL TOE LEVELS
                                                                                                                                         PROCEEDING WITH THE WORK.                                                             REGION                          N4
                                                                                                                                                                                                                                                                                                                                                                                  SHALL BE DETERMINED DURING CONSTRUCTION BY AN RPEQ-CERTIFIED
                                                                                                                                                                                                                               ULTIMATE WIND SPEED             61 m/s
                                                                                                                                                                                                                                                                                                                                                                                  GEOTECHNICAL ENGINEER.
                                                                                                                                   G7    ALL PROPRIETARY PRODUCTS NOT DEEMED TO COMPLY WITH THE BCA SHALL HAVE                 SERVICEABILITY WIND SPEED       39.0 m/s
                                                                                                                                         THIRD-PARTY CERTIFICATION WITH RELEVANT TESTING AND SIGN-OFF BY AN RPEQ ENGINEER.     TERRAIN CATEGORY                2
                                                                                                                                                                                                                                                                                                                                                                        P6.       DO NOT FOUND PILES HIGHER THAN TOE LEVELS ON DRAWINGS, UNLESS APPROVED BY
                                                                                                                                         PROPRIETARY PRODUCTS INCLUDES PREFABRICATED TRUSSES, LIGHT-GAUGE STEEL                                                                                                                                                                   BOTH THE SUPERINTENDENT AND THE GEOTECHNICAL ENGINEER. THE
                                                                                                                                         FRAMING, FLOORING PRODUCTS, RECYCLED TIMBER AND PLASTICS, BALUSTRADES, SCREENS, DC3 EARTHQUAKE LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH AS 1170.4 BASED                                                                            SUPERINTENDENT SHALL SEEK ADVICE FROM THE DESIGN ENGINEER AS REQUIRED.
                                                                                                                                         SHADE FABRICS, JOINERY, PARTITIONS AND OPERABLE WALLS.                                ON:
                                                                                                                                                                                                                               ACCELERATION COEFFICIENT        0.06
                                                                                                                                   G8    REFER TO ARCHITECTS DRAWINGS FOR DETAILS OF ALL GROOVES, FILLETS, HOBS, DRIP          SITE FACTOR                     1
                                                                                                                                         GROOVES AND THE LIKE.                                                                 IMPORTANCE LEVEL                1
                                                                                                                                                                                                                               STRUCTURE TYPE
                                                                                                                                   G9    GIVE AT LEAST 24 HOURS NOTICE OF AN INSPECTION BEING REQUIRED FOR :                   DESIGN CATEGORY                 EDC1
File: C:\- Projects\00 - Black & More\7550 - Noosa Jetty Builders\7550H - 10 THE PENINSULA\ 7550J - Notes Sheet.dwg




                                                                                                                                         - PILING
                                                                                                                                         - JETTY FRAMING (TIMBER)                                                                                     DC4 FIRE RESISTANCE LEVELS OF STRUCTURAL ELEMENTS HAVE BEEN TAKEN AS FOLLOWS:
                                                                                                                                         - BRACING AND TIE DOWN                                                                                           ELEMENT       FRL (mins)
                                                                                                                                                                                                                                                          COLUMNS        -/-/-
                                                                                                                                   G10   ALL FABRICATION SHOP DRAWINGS SHALL BE PROVIDED TO THE ENGINEER FOR REVIEW AND                                   BEAMS          -/-/-
                                                                                                                                         COMMENT IN A3 HARDCOPY OR PDF FORMAT.                                                                            WALLS          -/-/-
                                                                                                                                   G11 ABBREVIATIONS (GENERAL):                                                                                       DC5 DETERMINATION OF DESIGN LOADING FOR NON-STRUCTURAL ELEMENTS SUCH AS
                                                                                                                                       NTS      NOT TO SCALE                                                                                              CEILING AND CLADDING SYSTEMS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
                                                                                                                                       UNO      UNLESS NOTED OTHERWISE
                                                                                                                                       NSOE     NOT SHOWN ON ELEVATION                                                                                DC6 FLOOD LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH AS 5100 WITH NOMINAL
                                                                                                                                       NSOP     NOT SHOWN ON PLAN                                                                                         FLOOD VELOCITY TO BE CONFIRMED BY HYDRAULIC REQUIREMENTS AS FOLLOWS:
                                                                                                                                       TYP      TYPICAL                                                                                                   -V100 = 1m/s.
                                                                                                                                       (O)      OVER
                                                                                                                                       (U)      UNDER                                                                                                  TEMPORARY WORKS:
                                                                                                                                       CRS      CENTRES
                                                                                                                                       NOM      NOMINAL
                                                                                                                                                                                                                                                      T1.       MAINTAIN THE WORKS IN A SAFE CONDITION. ENSURE STRUCTURES ARE NOT
                                                                                                                                       CFW      CONTINUOUS FILLET WELD
                                                                                                                                                                                                                                                                OVER-STRESSED AT ANY TIME. TEMPORARY ROAD SURFACES SHALL BE TRAFFICABLE
                                                                                                                                                                                                                                                                AT ALL TIMES. POTHOLES ETC SHALL BE MONITORED AND REPAIRED.
                                                                                                                                                                                                                                                      T2.       CONTRACTOR'S RPEQ TO CERTIFY DESIGN AND CONSTRUCTION FOR TEMPORARY
                                                                                                                                                                                                                                                                WORKS: STRUTS, PROPPING, FORMWORK STRIPPING AND PROPPING PROCEDURES, TIE
                                                                                                                                                                                                                                                                BACKS, EXCAVATION SHORING, PROTECTION WORKS, DE-WATERING SYSTEMS,
                                                                                                                                                                                                                                                                FORMWORK, EARLY LOADING OF STRUCTURES AND THE LIKE.
Printed: 22 October 2019, 12:03 PM




                                                                                                                                                                                                                                                                                                                                                                                                                                                         CONSTRUCTION ISSUE
                                                                                                                                                                                                             NOOSA JETTY BUILDERS           © Black & More                                                                         Client                                     Project                                           Drawing Title
                                                                                                                                                                                                             JoB No: 1206                   This document is and shall remain
                                                                                                                                                                                                                                                                                               Black & More
                                                                                                                                                                                                                                                                                               ABN 19 609 960 232
                                                                                                                                                                                                                                                                                                                                           NOOSA JETTY BUILDERS    PROPOSED NEW JETTY
                                                                                                                                                                                                             Address:                       the property of Black & More.                                                          Address
                                                                                                                                                                                                                                                                                                                                           10 THE PENINSULA, NOOSAVILLE                                                          GENERAL NOTES - SHEET 1 OF 2
                                                                                                                      Revisions




                                                                                                                                                                                                                                            This document may only be used                     7 / 28 Sunshine Beach Road,
                                                                                                                                                                                                             10 THE PENINSULA, NOOSAVILLE                                                      Noosa Heads QLD. 4567
                                                                                                                                                                                                                                            for the purposes for which it was
                                                                                                                                                                                                             LOT 448    ON RP863243         commissioned and in accordance                     PO Box 611, Noosa Heads QLD. 4567   Drawn           Drawing        Approved                               Date    22/10/19
                                                                                                                                                                                                             Client:                        with the Terms of Engagement for
                                                                                                                                                                                                                                                                                               Telephone (07) 5447 4444
                                                                                                                                                                                                                                                                                                                                              ST   Check     FM
                                                                                                                                                                                                                                            the commission. Unauthorised use                                                                                                                                                    Drawing Size Scale (A3 size)     Drg No                 Revision
                                                                                                                                  C1 CONSTRUCTION ISSUE                           FM      FM        22/10/19 JANE AND GRAHAM ROSS                                                                                                                                                                          RPEQ 19951
                                                                                                                                  No.                         Description       Reviewed Approved    Date
                                                                                                                                                                                                                                            of this document in any form
                                                                                                                                                                                                                                            whatsoever is prohibited.
                                                                                                                                                                                                                                                                                               Email
                                                                                                                                                                                                                                                                                               Internet
                                                                                                                                                                                                                                                                                                         [email protected]
                                                                                                                                                                                                                                                                                                         www.blackm.com
                                                                                                                                                                                                                                                                                                                                   Designed
                                                                                                                                                                                                                                                                                                                                              FM
                                                                                                                                                                                                                                                                                                                                                   Design
                                                                                                                                                                                                                                                                                                                                                   Check     DS    Drawing is not to be used for construction unless approved      A3             NOT TO SCALE            7550J- S002    C1
                                                                                                                      External References:    B&M-JETTY-TITLE-A3_e.dwg

Used in these records

About this file

File size
955 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

7550J 191022 Construction Issue.pdf · 955 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.