Existing 1% AEP flood level
Area of shallow cut to offset
loss of floodplain storage.
Fill – earthworks to augment the
capacity of the existing basin
Fill at lot 8 building platform
Figure 2-3: Proposed cut / fill areas and extent of 1% AEP (CC) flood level
2.2.7. Flood Immunity
The NSC Planning Scheme identifies the Defined Flood Event, from which freeboard is set is the 1% (2100)
AEP flood event. Flood levels around the site for the 1% (2100) AEP are detailed for various reporting
locations as shown in Figure 2-4. This shows the proposed new lots are above the 1% (2100) AEP peak flood
levels. The peak flood level, minimum finished flood level and proposed lot level is shown in Table 2-12. It
is seen that greater than 500mm freeboard is provided to lot. It is recommended that future buildings on
each lot achieve a minimum of 500mm freeboard above the regional 1% (2100) AEP flood level.
Table 2-12: Lot Levels Compared to Adjacent 1% AEP Peak Flood Levels
Lot 1% AEP Peak Flood Minimum Freeboard Min Finished Floor Proposed Min Lot
Level (m AHD) to Floor (m) Level (m AHD) Level (m AHD)
8 83.44 0.5 83.94 87.61*
*Reported level is min lot level within the proposed building footprint area
23-0167SMP01-V2 | Stormwater Management Plan | 33 Pavilion Street, Pomona Page 21