of the stone pitching will also provide an “energy dissipation”
effect.
The following calculations demonstrate adequacy for lot 9: -
Running the RIP spreadsheet for 100year ARI storm of 5-minute
duration we note the following (refer Appendix D)
Qi (max) = 355 L/s at 5-minutes.
We also note that this corresponds with an available head of
3.2m (weir height above base of RIP’s) and an infiltration rate
through the RIP’s of: -
Maximum discharge outflow Qo (2.77m) = 245 L/s
Hence emergency overflow via the weir will not engage for
events <Q100 and will be contained within the designated RIP
system.
__________________________________________________________________________
A6107/L9/SMP/RevA/Aug 2021 Page 6 of 7
SH/pl