Reference Document - EXE25 0032 (As Published)
2800 1. GENERAL NOTES: 4. SIGNAGE:
2800 · MINIMUM UNOBSTRUCTED WIDTH FOR AN ACCESSIBLE PATH OF TRAVEL SHALL BE · ALL DOOR SIGNAGE TO AMENITIES SHALL COMPLY WITH BCA SPECIFICATION D3.6 BCA
950 TPH 850 HD 1000mm MEASURED BETWEEN FINISHED WALL FACES, BALUSTRADES AND HANDRAILS, 2011 AND BE IN ACCORDANCE WITH AS 1428.1 BRAILLE AND TACTILE SIGNAGE. ALL
850 HD 950 TPH
560 SD 700 EC 700 EC 560 SD WITH THE MINIMUM UNOBSTRUCTED HEIGHT OF 2000mm EXCEPT AT DOORWAYS WHICH BRAILLE AND TACTILE SIGNAGE SHALL BE A MIN OF 1200mm ABOVE FLOOR TO A
ARE PERMITTED TO BE 1980mm MAXIMUM OF 1600mm ABOVE FLOOR.
· NO FIXTURES OR FITTINGS SHALL BE PERMITTED TO ENCROACH ONTO OR WITHIN THE · IF LOCATED ON WALL SIGNAGE SHALL BE ON HANDLE SIDE OF DOOR MIN 50mm FROM
GR GR PATH OF TRAVEL SIDE OF ARCHITRAVE TO A MAXIMUM OF 300mm FROM ARCHITRAVE
SD HD TPH EC EC TPH HD SD
450
450
450
450
· MINIMUM WIDTH OF ACCESSIBLE DOORWAYS SHALL BE 850mm MEASURED FROM FACE · TACTILE AND BRAILLE SIGNS:
675
WHBR WHBL
MR
MR
BT WC TBR TBR WC BT OF DOOR WHEN OPEN TO FACE OF DOOR STOP ON OPPOSITE DOOR JAMB (1020mm · AS PER SPEC D3.6 BUILDING CODE OF AUSTRALIA 2011 - NATIONAL CONSTRUCTION
995
DOOR LEAF TO BE USED) CODE
320
A A SIGNAGE · MINIMUM WIDTH OF DOORS TO AMBULANT SANITARY FACILITIES SHALL BE 700mm · LOCATION OF TACTILE AND BRAILLE SIGNS
GPO
GPO
2080
2080
F A401 E D A401 B PROVIDE PVC BRAILLE SIGNAGE TO WALL (770mm DOOR LEAF TO BE USED) · SIGNS INCLUDING SYMBOLS, NUMBERINGS AND LETTERING MUST BE DESIGNED AND
FW FW
1556
IN ACCORDANCE WITH AS 1428.1 · FOR CAVITY OR FACE SLIDING DOORS INTO AN ACCESSIBLE SANITARY FACILITY A INSTALLED AS FOLLOWS
1630
C C
D01
D02
TF TF MINIMUM CLEAR OPENING WIDTH OF 850mm IS REQUIRED · BRAILLE AND TACTILE COMPONENTS OF A SIGN MUST BE LOCATED NOT LESS THAN
· ALL DOOR THRESHOLDS INTO ACCESSIBLE AND AMBULANT SANITARY FACILITIES SHALL 1200mm AND NOT HIGHER THAN 1600mm ABOVE THE FLOOR OR GROUND SURFACE
BE LEVEL AND EVEN WITH NO CHANGE IN HEIGHT OR GRADE PERMITTED. SIGNS WITH SINGLE LINES OF CHARACTERS MUST HAVE THE LINE OF THE TACTILE
210
· DOOR HANDLES AND LOCKS SHALL BE CAPABLE OF BEING OPENED BY ONE HAND IN A CHARACTER NOT LESS THAN 1250mm AND NOT HIGHER THAN 1350mm ABOVE THE
CH CH
SINGLE DOWNWARD MOTION, ALL DOOR HANDLES SHALL BE LOCATED AT 1000mm FLOOR OR GROUND SURFACE
ABOVE FINISHED FLOOR LEVEL (NOT LESS THAN 900 AND NO GREATER THAN 1100mm · SIGNS IDENTIFYING ROOMS CONTAINING FEATURES OF FACILITIES LISTED IN D3.6 MUST
NEW ACCESSIBLE TOILET: LAYOUT 1 X 4 NEW ACCESSIBLE TOILET: LAYOUT 2 X 4
ABOVE FLOOR LEVEL) BE LOCATED
RIGHT HAND TRANSFER LEFT HAND TRANSFER · ALL FITTINGS AND FIXTURES TO ACCESSIBLE AND AMBULANT SANITARY FACILITIES SUCH ON THE WALL ON THE LATCH SIDE OF THE DOOR WITH THE LEADING EDGE OF THE SIGN
A FLOOR PLAN: PROPOSED AS, WC PANS, CISTERNS, HAND BASINS, GRAB RAILS AND THE LIKE SHALL BE INSTALLED
IN ACCORDANCE WITH THE RELEVANT BUILDING CODE OF AUSTRALIA CLAUSE AND
LOCATED BETWEEN
·
50mm AND 300mm FROM THE ARCHITRAVE; AND
WHERE IS NOT POSSIBLE, THE SIGN MAY BE PLACED ON THE DOOR.
- Scale 1:50 @ A3
RELEVANT AUSTRALIAN STANDARD
· UNDER NO CIRCUMSTANCES SHALL FITTINGS AND OR FIXTURES BE SUBMITTED 5. ITEMS BE AWARE OF:
2800 2800 REPLACED OR ALTERED IN ANY WAY WHICH MAY CAUSE SUCH FIXTURE OF FITTING TO
COUNCIL ANNOTATION:
810 1180 810 810 1180 810 BECOME NON-COMPLIANT WITH THE CURRENT BUILDING CODE OF AUSTRALIAN · WHEN THERE ARE TWO OR MORE ACCESSIBLE SANITARY FACILITIES ( DISABLED TOILET)
Exemption Certificate EXE25/0032 STANDARD ON A SITE ONE MUST BE RIGHT HANDED AND ONE MUST BE LEFT HANDED
only relates to the replacement of the · THE BUILDER IS RESPONSIBLE TO ENSURE ALL FIXTURES AND FITTINGS ARE INSTALLED · ALL DISABLED TOILET SIGNS MUST INDICATE WHICH HAND THE TOILET IS EVEN IF ONLY
existing roof and upgrade of ground AS PER SUPPLIED DRAWINGS WHICH SHALL BE READ IN-CONJUNCTION WITH THE ONE ON THE SITE
floor toilets from code assessment for RELEVANT AUSTRALIAN STANDARD, ANY ERRORS OR OMISSIONS SHALL BE REPORTED TO · COAT HOOK FOR AMBULANT TOILET DOOR SWINGS OUTWARD AGAINST A WALL OR
THE SUPERINTENDENT PRIOR TO INSTALLATION PARTITION
building works within the Medium 2. WALL SUPPORT NOTE: · ALLOW FOR DOOR STOP WHERE TOILET DOOR SWINGS OUTWARD AGAINST A WALL OR
1040
1040
Impact Industry Zone. · BUILDER SHALL ALLOW FOR BLOCKING OF WALLS WITH EITHER 12mm MARINE PLY PARTITION
DLR DLR DLR DLR SHEETING FIXED FLUSH WITH FACE OF WALL STUDS OR WITH 140X45 TIMBER NOGGINS · ALL AMBULANT TOILET DOORS MUST HAVE SIGN TO STATE "AMBULANT TOILET"
2080
2080
NAILED BETWEEN STUDS, BLOCKING IS REQUIRED FOR ALL GRAB RAILS WALL FIXTURES · WAYFINDING SIGNAGE WILL BE REQUIRED WHERE AMBULANT TOILETS ARE LOCATED
SUCH AS HAND DRYERS BASINS RAILS AND THE LIKE, ALSO FOR LIGHT FITTINGS, WITH A TOILET BLOCK
P1 P1 NEW ACCESSIBLE TOILETS: CEILINGS CO-ORDINATE LOCATION WITH INTERNAL ELEVATIONS. IF UNSURE OF LOCATIONS OR · GENERAL RULE OF THUMB - ALLOW FOR 1800 WIDE PASSAGEWAYS THIS WILL ENSURE
13mm SUSPENDED PLASTERBOARD CEILING FROM THE
1040
1040
EXTENT REFER TO SUPERINTENDENT FOR PLACEMENT INSTRUCTIONS WHERE WALLS ARE DDA COMPLIANCE
EXISTING STRUCTURE OVER. PAINT FINISH AS SPECIFIED.
PART OF AMENITIES OR WET AREAS THEY SHALL BE LINED WITH 12mm VILLABOARD TO · COMPLYING WITH THE AUSTRALIAN STANDARD AS1428.1 DOES NOT MEAN DDA
CEILING HEIGHT 2400 mm
ALL AMENITIES AND DISABLED TOILETS COMPLIANCE HAS BEEN MET IN ALL CIRCUMSTANCES AND YOU SHOULD CONSULT
3. GRAB RAILS: YOUR DDA CONSULTANT (IF NOT APPOINTED)
· GRAB RAILS SHALL BE INSTALLED IN ACCORDANCE WITH CLAUSE 17 & FIGURE 53(A) AS · IF NO DDA SIGN OFF - THIS WILL MEAN THAT THEY WILL NOT ALLOW ANY
NEW ACCESSIBLE TOILET: LAYOUT 1 X 4 NEW ACCESSIBLE TOILET: LAYOUT 2 X 4 PER AS1428 INTERPRETATION OR MODIFICATION TO THE CODE, THEY EXAMINE THE DOCUMENTS
PURELY ON THE BASIS OF WHAT IS STATED IN THE BCA AND AS1428.1
B REFLECTED CEILING PLAN FITTINGS & FIXTURES SCHEDULE
- Scale 1:50 @ A3
FIXTURE WATER CLOSET OPTION 01 SAMPLE IMAGE FIXTURE WATER CLOSET OPTION 2 SAMPLE IMAGE FIXTURE BASIN TAPWARE SAMPLE IMAGE ACCESSIBLE TOILET: GR
CODE WC CODE WC CODE BT PROVIDE STANDARD CHROME ACCESSIBLE TOILET GRAB RAILS TO
BE COMPLIANT WITH AS1428.1 2009. BUILDER TO INSURE
MANUFACTURER CAROMA MANUFACTURER CAROMA MANUFACTURER CAROMA SUFFICIENT SUPPORT IN THE WALL IS PROVIDED
MODEL CAROMA 800 INVISI II MODEL / Care 400 Connector Suite MODEL CARE PLUS BASIN MIXER
PRODUCT CODE with Backrest / 987900BSB CARE HANDLE H/C
COLOUR / FINISH WHITE / BLUE SEAT
COLOUR / FINISH CHROME
SUPPLIER CAROMA COLOUR / FINISH WHITE / BLUE SEAT
NOOSA COUNCIL QUANTITY 08 SUPPLIER CAROMA
SUPPLIER CAROMA
QUANTITY 08
REFERENCE DOCUMENT NOTES Backrest curved arm included. In
wall cistern to suit 75 mm stud
QUANTITY 08
To be installed to comply to
NOTES
EXE25/0032 25 AUG 2025 wall, code718310BSB NOTES AS1428.1–2021
NOTE: OPTION 01 - CAROMA 800 INVISI II SHOWN ON DRAWINGS FIXTURE ACCESSIBLE BASIN SAMPLE IMAGE FIXTURE HAND DRYER SAMPLE IMAGE
CODE WHBR X 4 WHBL X 4 CODE HD
ACCESSIBLE TOILET: MIRROR
MANUFACTURER CAROMA MANUFACTURER DYSON PROVIDE STANDARD ACCESSIBLE TOILET MIRROR TO BE
LIGHTING SCHEDULE LEGEND COMPLIANT WITH AS1428.1 2009. SIZE: APPROX. 460 X 900mm
KEY DESCRIPTION MODEL Cube Extension 864215W MODEL Dyson Airblade V (Nickel)
ALERT CALL SYSTEM:
DLR DESCRIPTION: RECESSED LED CH COAT HOOK TBR TOILET BACK REST COLOUR / FINISH WHITE COLOUR / FINISH NICKEL PROVIDE STANDARD ACCESSIBLE TOILET ALERT CALL SYSTEM TO
DOWNLIGHT EC EMERGENCY CALL BUTTON TPH TOILET PAPER HOLDER BE COMPLIANT WITH AS1428.1 MANUFACTURER: ALERT
SUPPLIER CAROMA SUPPLIER DYSON
AREA: AMENITIES GR GRAB RAIL - BLACK WC WATER CLOSET TEL. 02 9879 5823 Email: [email protected]
COLOUR: TBA HD HAND DRIER WHB WASH HAND BASIN 4 X Right Hand Shelf, one taphole QUANTITY 08 OR SIMILAR
COLOUS: TBA QUANTITY – centre option Code No.864115
MR MIRROR FW FLOOR WASTE NOTES ACCESSIBLE TOILET: COAT HOOKS
SUPPLIER: TBA 4 X Left Hand Shelf, one taphole Provide Power as Required PROVIDE STANDARD DOOR MOUNTED ACCESSIBLE TOILET COAT
Quantity: NAME / CODE: T B A SD SOAP DISPENSER GPO POWER OUTLET – centre option Code No.864215 HOOKS (2 No) TO BE COMPLIANT WITH AS1428.1 2009.
16 SH TOILET SHELVING
DESCRIPTION: EMERGENCY REFER TO DRAWING A040 FOR FINISHES SCHEDULE
LIGHT PROJECT ISSUE: FOR CONSTRUCTION
Quantity:
GENERAL NOTES NOTE: TO COMPLY WITH No. AMENDMENT DATE IN ASSOCIATION WITH: project :
8
A.S. 2293.1-2005
Architectural documents to be read in conjunction with relevant Structural, Fire Service, Mechanical, Hydraulic, JANE PROPERTY
Electrical, Civil and Landscaping documents. Technical drawings to be read in conjunction with appropriate Project No. Drawing No. north
sections of technical specification.
144 Eumundi Noosa Rd, Noosaville QLD 4566 address : AS74
N
Contractor to verify all dimensions / condition on site prior to commencement of works. Contractor to seek
Total Area
clarification of all inconsistencies and resolve all discrepancies on plans and site conditions prior to
description : - A400
commencement of any works on site. Commencement of works on site by the contractor is deemed to be
acceptance of all conditions and plans and any variations will be the responsibility of the contractor expense. INTERNATIONAL First Drawn Scale Revision
Figured dimensions shall take precedence to scaled dimensions.
Copyright of designs shown herein is retained by Allister Sarris. Written authority is required for any reproduction.
TOTAL PROPERTY DEVELOPMENT SOLUTIONS ACCESSIBLE TOILET DETAILS AND drawing title : September 2024
Date Issued Paper Size
Notify SARRIS ARCHITECTURE of any changes. No changes to occur without SARRIS approval.
Document Set ID: 24027286 CHECKED BY: S.E. HARDY (QBSA LICENCE NUMBER 65539) SCHEDULES - A3
Version: 1, Version Date: 13/08/2025