Minor Change Report MCU17 0559 05 (As Published) · MCU17/0559.05
APPLICATION FOR A MINOR CHANGE TO A DEVELOPMENT APPROVAL
Author Coordinator Planning, Ben Micallef
Development Assessment
APPLICATION DETAILS
Application No. MCU17/0559.05
Development Approval Development Permit for Material Change of Use - Multiple
Housing - Type 2 Duplex
Applicant Maan Investments P/L
Request Received On 19 February 2026
Report Reviewed By G.Schramm 2.06.2026
Decision Due Date N/A
PROPERTY DETAILS
Property Address 2/16 Grant St Noosa Heads Qld 4567
RP Description Lot 2 SP 326085
Land Area 166m2 (Lot 2)
Existing Use of Land Duplex
STATUTORY DETAILS
SEQRP Designation Urban Footprint
Zone Medium Density Residential Zone
Precinct Not applicable
Local Area Plan Noosa Heads
Overlays Landslide Hazard
Assessment Type Minor Change to Development Approval
1. PROPOSAL
The applicant seeks approval to change an existing development approval by requesting a change
to the plans and conditions to remove the requirement for planter boxes along the external walls
of the lower floor unit 2.
Page 1 of 9
Document Set ID: 24630994
Version: 5, Version Date: 02/06/2026
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 8 pages
Page 2
The locality and proposal plans are included below.
Figure 1 – Locality
Figure 2 - Approved Plan – showing location of planter boxes
Figure 3 Render of Planter Boxes – Northern Elevation
Page 2 of 9
Document Set ID: 24630994
Version: 5, Version Date: 02/06/2026
Page 3
Figure 4 Render of Planter Boxes – Southern Elevation
2. BACKGROUND
A Development Permit for Material Change of Use - Multiple Housing- Type 2 Duplex was issued
on 1 August 2020. The plans indicated that sections of the lower level were to be below ground
level and considered as a basement to ensure compliance with gross floor area provisions.
On February 2020, a minor change to the original development approval was issued (Council ref.
MCU17/0559.02). The main change related to the development’s roof form, a reduction to the roof
pitch from 8 to 1 degrees and reduction in the extent of eaves.
On 20 November 2020, a Generally in Accordance Letter (Council ref. MCU17/0559.03) was
issued, relating to revised location of the swimming pools and roof pitch from 1 to 2 degrees.
A Plan Seal application (Council ref. PS23/0020) and Operational Works (Council
ref..OPW20/096.01) off-maintenance request was lodged in September 2023. Following a site
inspection carried out by Council Officers’, it was identified that there were inconsistencies between
Council approved plans and the constructed dual occupancy.
The variations to the approved plans included:
a) Shade structure at the rear of each unit
b) Internal reconfiguration to the upper level and lower levels of each unit, creating self contained
dwellings on the lower level of each unit.
c) Spiral staircase within the southeastern side boundary setback.
d) Storage areas on the lower level below the outdoor recreational areas of each unit.
e) Extent of earthworks carried out contrary to Condition 5, the approved plans, and maximum
plot ratio permitted for the development.
f) Variation to the approved window placement along both side elevations.
A minor change application (MCU17/0559.04) was submitted October 2023 seeking retrospective
approval for the matters listed above. The assessment for the change application noted that the
original approval required backfilling to ensure the lower level met the definition of a basement
under The Noosa Plan. This work was not completed and as a result the lower level contributed to
Page 3 of 9
Document Set ID: 24630994
Version: 5, Version Date: 02/06/2026
Page 4
gross floor area and increased the total GFA to 391.6 m² and a plot ratio of 0.658:1 which exceeded
the 0.45:1 maximum.
To address the area of non-compliance the applicant proposed 1.5 m high planter boxes to screen
the non-compliant section in lieu of backfilling. Council did not consider this a good planning
outcome however after considerable discussions with the applicant and builder, accepted the
proposal as it avoided structural risks associated with earthworks and provided a landscaped
outcome that screened the lower exposed floor level.
The minor change application was approved 31 January 2024.
3. ASSESSMENT
3.1. Instruments for Statutory Assessment
Under the Planning Act 2016 the application must be assessed against each of the following
statutory planning instruments to the extent they are relevant to the development:
• State Planning Policy;
• South East Queensland Regional Plan;
• Planning Regulation 2017; and
• 2006 Noosa Plan (version. 3 July 2017).
3.2. Statutory Process
The applicant has requested to make a minor change to a development approval under s78 of the
Planning Act 2016. An application for a minor change to a development approval can only be made
in circumstances where a change would constitute a ‘minor change’.
The proposed change to the development approval requested by the applicant is determined to
constitute a minor change on the grounds that:
• the development would not result in substantially different development as the established use
remains the same;
• the change does not include prohibited development;
• the change would not require the application to be referred to an additional referral agency or
cause a referral agency to have regard to new matters prescribed by regulation;
• where the original application was code assessable, the change would not cause the
application to become impact assessable.
3.3. Statutory Instruments – Planning Scheme
The original application was lodged and assessed under the now superseded 2006 Noosa
Planning Scheme.
Page 4 of 9
Document Set ID: 24630994
Version: 5, Version Date: 02/06/2026
Page 5
The following codes from the Noosa Plan are applicable to this development:
• Noosa Heads Locality Code;
• Residential Uses Code;
• Landscaping Code;
• Engineering Works Code.
Pursuant to s81 of the Planning Act 2017, Council must consider the planning scheme in effect
when the original development application was lodged, however Council may give weight to Noosa
Plan 2020 (Amendment 2 - 26 September 2025) as the planning scheme in effect at the time of
the minor change application being lodged.
Due weight can be given to the following codes from Noosa Plan 2020 (Amendment 2 – 26
September 2025) are applicable to this development:
• Medium Density Residential Zone Code;
• Noosa Heads Local Plan Code;
• Dual Occupancy and Multiple Dwelling Code;
• Works Codes;
• Landslide Hazard Overlay Code.
Existing Conditions 2 and 5
2. Development undertaken in accordance with this approval must generally comply with the
approved plans of development. The approved plans are listed in the following table unless
otherwise amended by these conditions.
Plan No. Rev. Plan Name Date
001 18 Site Plan by H4 10.09.2019
002 18 Site Cover by H4 10.09.2019
100 22 Lower Floor Plan by H4 10.01.2024
101 22 First Floor Plan by H4 10.01.2024
200 18 Roof Water Discharge Plan by H4 10.09.2019
300 22 Elevations by H4 10.01.2024
301 22 Elevations by H4 10.01.2024
302 22 Front Entry Elevation prepared by H4 Plan + Design 10.01.2024
+ Build
500 22 3D Perspectives – Unit 16 prepared by H4 Plan + 10.01.2024
Design + Build
501 22 3D Perspectives – Unit 16 prepared by H4 Plan + 10.01.2024
Design + Build
900 22 Details – Unit 16 Planter Box prepared by H4 Plan + 10.01.2024
Design + Build
Page 5 of 9
Document Set ID: 24630994
Version: 5, Version Date: 02/06/2026
Page 6
901 22 Details – Unit 16 Planter Box prepared by H4 Plan + 10.01.2024
Design + Build
4. The landscape planter boxes, as detailed on the approved plans, must be provided to the
area adjacent to the rumpus room and bedroom 2 of both dwelling units (northern and
southern elevations). The planter boxes must not be removed.
Applicant’s Request
The applicant has requested existing condition 2 be amended to cross out the planter box
associated with unit 2. Condition 5 is also requested to be deleted.
The timber planter box along the southern façade of Unit 2 is proposed to be removed with the
applicant citing structural deterioration, movement in the posts and sleepers, moisture
accumulation at the slab edge and increased termite risk identified in structural and pest inspection
reports. The applicant submits that the planter box restricts natural light and ventilation to the
rumpus and Bedroom 2, narrows the approved side access from 1.8 m to 0.7 m which impedes
movement (including for people with disabilities) and prevents proper inspection of building and
termite barriers. The applicant further argues that the structure provides no meaningful landscape,
amenity or screening benefit, is not visible from the adjoining property and diminishes the liveability
and functionality of Unit 2.
The applicant submits that the development was originally approved with a compliant 39% site
cover and 0.45:1 plot ratio under the superseded Planning Scheme and argues that the downstairs
area should continue to be treated as a ‘basement’ rather than GFA. It is contended that previous
approvals over the site accepted this level as a basement and that a new topographic survey
confirms the ceiling does not exceed 1 m above ground level and the building remains two storeys.
The applicant asserts that Council’s reclassification of this level as GFA creates an artificial
non-compliance with the former 0.45:1 plot ratio and that the planter box was introduced only to
fabricate compliance by creating a false ground level. Further they argue that the planter box does
not influence true ground level and that the development therefore remains compliant with the
superseded scheme.
The applicant further details that under the current Noosa Plan 2020 (Amendment 2) plot ratio and
site cover are no longer applicable benchmarks for this form of development and the removal of
the planter box does not change the approved built form and maintains compliance with all relevant
assessment benchmarks, including the Medium Density Residential Zone Code.
Assessment of Request
The applicant seeks the removal of the planter boxes as prescribed in condition 2, based on the
following grounds:
a) The approval was assessed under the superseded planning scheme which prescribed a
maximum plot ratio of 0.45:1 and site cover of 40%. The current planning scheme does not
prescribe a plot ratio or site cover for this type of development
Response
This is incorrect. The acceptable outcomes for the medium density residential zone detail site
cover and plot ratio for a dwelling house. The approval seeking variation is not for a dwelling,
but for a duplex. The Noosa Plan 2020 Performance Outcome is applicable which prescribes
a plot ratio of 0.4:1 and site cover of 40% is applicable. In accounting for the lower ground level
and extent of lower ground that now protrudes above 1 metre NGL, the existing building has a
total GFA of 340sqm and a plot ratio of 0.57:1 which is considerably higher than that envisaged
by the Planning Scheme. The development exceeds both the nominated plot ratio under the
2006 Noosa Plan and the current scheme in effect.
b) The applicant has submitted a survey plan suggesting the lower floors constitute basements
as they are below the surveyed ground level, that the building does not exceed 2 storeys and
the planter boxes do not influence ground level and creates an artificial non-compliance.
Page 6 of 9
Document Set ID: 24630994
Version: 5, Version Date: 02/06/2026
Page 7
Response
The applicant relies on a survey plan to assert that the lower level constitutes a basement as it
is located approximately 1 metre below the surveyed ground level. The survey plan, however,
relates to the undercroft area behind the unit, rather than the ground floor area that has
historically been assessed by Council for gross floor area (GFA) purposes. The undercroft area
was never included in Council’s GFA or plot ratio calculations, whereas the subject ground floor
level has previously been assessed as above-ground and not a basement under the Noosa
Plan 2006.
Under the applicable Noosa Plan 2020, a basement is defined as a space no part of which is
more than 1 metre above ground level, with ground level being the natural ground or the level
as lawfully changed, being the level shown on the first registered plan of survey. In this instance,
the ground levels shown on the approved building plans were created as part of development
works and do not constitute the natural ground level or a lawfully changed ground level for the
purposes of the Planning Scheme.
While the applicant asserts that the subject level is located approximately 1 metre below the
surveyed ground level, this fact alone is not determinative. Having regard to the lawful ground
level and the planning context, the space does not properly characterise as a basement and
continues to perform as an above-ground storey. Accordingly, the area must be included in GFA
calculations, with the result that the proposal significantly exceeds the GFA anticipated for
development within the zone and does not achieve the zone’s overall intent or planned built
form outcomes.
c) The installed planter boxes are deteriorating resulting in maintenance issues for the boxes and
the overall the unit.
Response
This is not a planning matter. The planter boxes were installed to comply with the previous
minor change approval. The deterioration is clearly due to poor materials and workmanship in
their construction. It is Council’s expectation that the planter boxes be repaired or replaced to
address the maintenance concerns. This is not considered valid grounds for their removal.
d) The applicant raised amenity issues due to loss of light and air flow in the lower ground floor,
as well as access around the planters.
Response
It is acknowledged that the planters result in some reduction to light and airflow. However, the
lower ground floor levels were approved as a basement level with limited openings and the
inherent amenity constraints anticipated for that built form. This is a building certification
matter.
In this respect, the development continues to achieve the purpose and overall outcomes of
the relevant zone and use codes, which recognise that building design must respond to site
constraints and approved building typologies, while still providing an acceptable level of
amenity commensurate with the nature of the accommodation provided. The marginal
reduction in light and airflow does not result in any unacceptable amenity outcome, nor does
it conflict with the relevant performance outcomes relating to residential amenity or building
functionality.
Council Officers have inspected the site following installation of the planters and confirmed
that pedestrian access around the building remains functional and unobstructed. Accordingly,
the planters do not materially compromise access outcomes or compliance with the relevant
performance and overall outcomes.
Recommendation
It is recommended existing condition 2 remain unchanged.
Page 7 of 9
Document Set ID: 24630994
Version: 5, Version Date: 02/06/2026
Page 8
Existing Condition
5. The landscape planter boxes, as detailed on the approved plans, must be provided to the
area adjacent to the rumpus room and bedroom 2 of both dwelling units (northern and
southern elevations). The planter boxes must not be removed.
Applicant’s Request
The applicant has requested existing condition 5 be amended and replaced with the following
amended condition:
5. The landscape planter box, as detailed on the approved plans, must be provided to the area
adjacent to the rumpus room and bedroom 2 of dwelling unit 1 (northern elevation). The
planter box must not be removed
Assessment of Request
Refer response to condition 2 above.
Recommendation
It is recommended existing condition 5 remain unchanged
6. CONSULTATION
6.1. Referral Agencies
Not applicable
6.2. Internal Council Referrals
Not applicable
7. CONCLUSION & REASONS FOR DECISION
The constructed development does not comply with the requirements of the planning scheme and
raises significant issues that cannot be addressed by reasonable and relevant conditions. The
existing development, with particular reference to the lower ground level section and how it is
viewed from the northern and southern elevations, is contrary to the outcomes sought as part of
the original approval. The design ‘solution’ to deliver a landscape planter box was suggested by
the applicant in 2024 as part of minor change application MCU17/0559.04. While the landscape
planter does not resolve the extent of non-compliance with regard to site coverage and plot ratio,
it does screen the lower ground built form and provide for an outcome that is more consistent with
the original approval. Accordingly, the application is therefore recommended for refusal.
The report is provided in accordance with Section 83(9) of the Planning Act 2016.
RECOMMENDATION
With regard to Application No. MCU17/0559.05 to make a minor change to an existing approval
for Development Permit for Material Change of Use – Multiple Housing - Type 2 Duplex situated
at 2/16 Grant St Noosa Heads Qld 4567 and described as Lot 2 SP 326085, Council on 2 June
2026 decided to:
A. Refuse to amend condition 2 and 5 for the following reasons:
1. The proposed changes are contrary to Specific Outcome 011, and Overall Outcome (oo)
of the Noosa Heads Locality Code of the 2006 Noosa Plan, and Performance Outcome
PO13, and Overall Outcomes of (2) (c) (d) of the Medium Density Residential Code of
the Noosa Plan 2020.
1.1. The subject level does not constitute a basement under either the Noosa Plan
2006 or the Noosa Plan 2020 and must therefore be included in gross floor area
calculations. When included, the development exceeds the acceptable gross floor
area and plot ratio outcomes anticipated under both planning schemes.
Page 8 of 9
Document Set ID: 24630994
Version: 5, Version Date: 02/06/2026
Page 9
1.2. The resulting development represents an intensity and built form outcome that is
materially greater than that envisaged for the site and surrounding area. The
absence of visual impact does not mitigate the non-compliance with density
controls, which regulate development intensity rather than visibility alone.
1.3. The proposed removal of the planter boxes is not warranted, as they are capable
of being reinstated in accordance with the approved development and do not justify
the recharacterisation of the subject level as a basement.
1.4. Approval of the proposed amendments would result in an undesirable planning
outcome and precedent by allowing non-complying above-ground floor area to be
excluded from gross floor area calculations, undermining the intent and consistent
application of gross floor area and plot ratio controls under the Planning Scheme.
Page 9 of 9