Verification Certificate – SQIDEP VC
Reference Number: SA-2019/009/VC
the cleaning of the Storm Sack and filter cartridge at regular intervals;
• The life expectancy of the device and the media is unknown. In discussions with the
manufacturer the testing is consistent to at least the 6 year mark. It is suggested that
an estimated lifespan of both media and the whole device be written into any technical
guidelines as the filter material will deteriorate over time;
• The acceptance of these results is reliant on the installation being similar to that shown
in this analysis. Alternative installations may result in different outcomes;
• Designs & Installations of the SPELBasin® are in accordance with the SPEL Stormwater
SPELBasin® Technical Guidelines; and
• If the media is observed to not fully drain down to its lowest level within 2 hours
following an event, investigate the media permeability, and if required replace media.
Independent
Reviewers Mr Chris Beardshaw, Afflux Consulting
Mr Mark Liebman, Sustainability Workshop
Accepted by
Governance 24/9/2020
Panel
Accepted by
Stormwater 25/9/2020
Australia
Board