06/1354 - Response to Information Request [As Published] · 132006.1354
6. Effluent Disposal Area Design Type and Size From Clause 4.2A7.3.2 of ASNZ1547-2000, disposal area size is determined from The formula: L= QADLRxW) or Area = Q/DLR Where: L= length in metres Q daily design rate in I/day DLR= design load rate in mm/day W= width in metres If a daily design flow (Q) OF 840 I/day is adopted and given that the DLR is insert 30mm/day, as stated above, the reduired disposal area is as follows; Area = 840/20 = 42.0 m2 Therefore it is considered that a maximum area of 42m2 of conventional absorption bed, disposing of secondary treated effluent, will be required for effective effluent disposal of Lots 8 and 9. 6.1 Effluent Disposal Bed Layout Refer to Annexure B for the recommended effluent disposal bed layout over an area of 3.25m wide and 13.0m length. 7, Conclusion For Lots 8 and 9 the maximum disposal area that will 42 m2 per lot. COLIN PYWELL RPEQ 1003