20200903OBA_R1_Loading_Dock_Operational_Conditions · OPW20/0145

of 31

Text shows just the words. Original shows the document exactly as it was published.

Check the original when the exact wording matters.

                                                                                                         MATTHEW PALAVIDIS
                                                                                                         VICTOR FATTORETTO
                                                                                                         MATTHEW SHIELDS




20191414.2/0309A/R1/OB

3/09/2020

Stockwell Development Group Pty Ltd
399 Montague Road
WEST END QLD 4101

Attn: Harrison Hurst

Noosa Civic - Loading Dock Operational Conditions

This letter addresses the following recent clarifications regarding loading dock operating times and
conditions for Noosa Civic:

    a) The loading times are between 3am and 10 pm.
    b) Refrigeration trucks would need to idle whilst loading/unloading due to food safety requirements

We note the following:

Loading Times

The previous assessment and analysis in the acoustic report prepared by ALC (revision 2, ref:
20191414.2/2708A/R2/OB, dated 27/08/2020) took into consideration day, evening and night time loading
activities (i.e. 5am to 7am for night time, and 7am to 10pm for day and evening). Given that night time noise
impacts were assessed already and the additional hours of 3am to 5am fall in the same period, no changes
to the acoustic assessment is required.

Refrigeration Truck Idling

Due to food safety requirements, refrigeration trucks must remain idling whilst they are being
loaded/unloaded. An impact assessment of the idling has been included in the revised report, with
assumptions and predicted incident noise levels in Section 5 of the attached revised acoustic report.
Recommendations to address the impacts from idling refrigeration truck have also been updated.

A revised acoustic report addressing these issues above has been attached in the Appendix of this letter and
includes updated acoustic treatment and management recommendations based on the revised operational
requirements.




 BRISBANE                                                                                                    ABN 11 068 954 343
 Level 1                                                                                                 www.acousticlogic.com.au
 82 Arthur Street
 FORTITUDE VALLEY QLD 4006
 (07) 3211 5591

 The information in this document is the property of Acoustic Logic Consultancy Pty Ltd 11 068 954 343 and shall be returned on
 demand. It is issued on the condition that, except with our written permission, it must not be reproduced, copied or communicated
 to any other party nor be used for any purpose other than that stated in particular enquiry, order or contract with which it is issued.

 I:\Jobs\2019\20191414\20191414.2\20200903OBA_R1_Loading_Dock_Operational_Conditions.docx                                             1
Full text of the other 30 pages

Page 2

We trust this information is satisfactory. Please contact us should you have any further queries.

Yours faithfully,




Acoustic Logic Consultancy Pty Ltd
Omar Busaidi




 I:\Jobs\2019\20191414\20191414.2\20200903OBA_R1_Loading_Dock_Operational_Conditions.docx           2

Page 3

APPENDIX A – UPDATED ACOUSTIC REPORT (REVISION 4)




I:\Jobs\2019\20191414\20191414.2\20200903OBA_R1_Loading_Dock_Operational_Conditions.docx   3

Page 4

poe oe wera
LOG iC MATTHEW SHIELDS

Noosa Civic

Noise Impact Assessment

 

BRISBANE ABN 11 068 954 343
Level 1 www.acousticlogic.com.au
82 Arthur Street

FORTITUDE VALLEY QLD 4006

(07) 3211 5591

The information in this document is the property of Acoustic Logic Consultancy Pty Ltd 11 068 954 343 and shall be returned on
demand. It is issued on the condition that, except with our written permission, it must not be reproduced, copied or communicated

to any other party nor be used for any purpose other than that stated in particular enquiry, order or contract with which it is issued.

I\Jobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 1

Page 5

 

Project ID

20191414.2

 

Document Title

Noise Impact Assessment

 

Attention To

Stockwell Development Group Pty Ltd

 

 

 

 

 

 

 

 

Revision Date Document Reference Prepared By | Checked By | Approved
By
0 24/07/2020 | 20191414.2/2407A/RO/OB OB
1 26/08/2020 | 20191414.2/2608A/R1/OB OB TS
2 27/08/2020 | 20191414.2/2708A/R2/OB OB OB
3 2/09/2020 | 20191414.2/0209A/R3/OB OB TS
4 3/09/2020 | 20191414.2/0309A/R4/OB OB OB

 

 

 

 

 

 

 

 

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx

 

Page 6

TABLE OF CONTENTS

INTRODUCTION. ............csccsscssccssssssssssssssssssesssscsssssssssssssssssesssecssssssssessesssessssseesoessessessonssees 4

SITE DESCRIPTION...

NOISE TARGETS

NOISE MEASUREMENTS.

4.1 MEASUREMENT LOCATIONS..
4.2 MEASURED NOISE LEVELS
4.2.1 Unattended Measurements Results
4.2.2 Attended Measurement Results...
5 NOISE SOURCES/IMPACTS......

5.1 LOADING DOCKS....
5.1.1 Trolley Collection
5.1.2 Delivery Trucks.
5.1.3 Mechanical Plant
5.1.4 Compactor.

5.2 NOISE CALCULATION...

6 RECOMMENDATIONS

6.1 MANAGEMENT CONTROLS ....

6.2 ACOUSTIC BARRIER.

6.3. RESIDENTIAL BUILDINGS FACADE CONSTRUCTION

6.4 MECHANICAL PLANT NOISE LEVELS o

7 CONCLUSION... cee ceccssceesssscsessscssssscsssssesssscsessssssssssssssssssssscsssssscssssssssessessessosssssossoess

 
 
  
 
 
 
 
 
  
 
  
 
 
 
 
 
 

RhWN =

 

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 3

Page 7

1 INTRODUCTION

Acoustic Logic consultancy (ALC) have been engaged to conduct an assessment of major noise source
impacts from the Noosa Civic Shopping Centre onto proposed adjacent residential development.

The report is in response to the Council’s request:

1.

Prepare and submit to Council for approval with and Operational Works application a revised acoustic
report which includes measures to mitigate noise generated from the shopping centre operations and
equipment, including deliveries, truck movements and rubbish collection. This report should consider
attenuation at the noise source as well as a noise barrier along the shared boundary of Lots 19 and
217. All measures to mitigate noise must be implemented prior the submission of the subdivision plan
to Council.

Noise attenuation is required to achieve the following acoustic quality for potential residential uses on
Lots 17-19. The measurement location must include receivers being places at the closest point to the
future residential and office buildings.

 

 

 

 

 

Criteria (measured at the receptor) dB(A)
Sensitive receptor Time of Day LAeq.adj, Thr? LAT adj, Th
Daytime and evening
(habitable spaces) 35 e
Dwelling (indoors)
Night-time (sleeping
areas) 30 40

 

 

 

 

 

"Acoustic descriptor/noise target for continuous noise sources (eg. Mechanical plant).
“Acoustic descriptor/noise target for transient impacts arising from loading dock activities (e.g. truck
movements, reversing alarms, compactor, trolley etc.)

The purpose of this assessment is the following:

Establish the predicted intrusive noise levels at the proposed subdivision site on Hofmann Road for
lots 17-21.

Provide acoustic attenuation recommendations to meet the indoor acoustic criteria set by Noosa
Shire Council. These are applied at the source, boundary, and receiver.

This report includes attended and unattended noise measurements from the previous ALC acoustic report
(ref: 20191414.1/1501A/R2/SS, dated 15/01/2020).

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 4

Page 8

2 SITE DESCRIPTION

The site comprising the proposed lots 17, 18, 19, and 21 is bound by the following:
e North, North-east - Noosa Civic Shopping Precinct
e¢ West — Commercial precinct

e South - Townhouses across Hofmann Drive.

The loading docks are indicated in Figure 1 below.

Site (Lots 17,18,19,21)

Noosa Civic Loading Docks

 

Figure 1 — Site Location

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 5

Page 9

3 NOISE TARGETS

In accordance to the Information Request, Noosa Shire Council has requested that the development be
assessed in accordance with the criteria below.

Table 1 - EPP Noise 2008, Schedule 1 - Acoustic Quality Objectives for Residential

 

 

 

 

 

Sensitive Time of Day Criteria (measured at the receptor)
receptor dB(A)
Laeq.adj,thr’ Latadj, thr”
daytime and evening 35 45
dwelling (indoors) (habitable spaces)
night-time (sleeping areas) 30 40

 

 

 

 

 

' Acoustic descriptor/noise target for continuous noise sources (e.g. mechanical plant).
2 Acoustic descriptor/noise target for transient impacts arising from loading dock activities (e.g. truck
movements, reversing alarms, compactor, trolley etc.).

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 6

Page 10

4 NOISE MEASUREMENTS

Measured noise levels are obtained from the previous ALC acoustic report (ref: 20191414.1/1501A/R2/SS,
dated 15/01/2020) and are presented below.

4.1 MEASUREMENT LOCATIONS

Monitor locations were selected upon accessibility and accuracy in considering ambient conditions whilst
capturing dominant noise sources around site.

 

Unattended ® Attended

Figure 2- Noise Measurement Locations

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 7

Page 11

4.2 MEASURED NOISE LEVELS

 

 

 

 

 

 

 

 

 

 

 

 

4.2.1 Unattended Measurements Results
Table 2 -NGARA Measurement Summary
Date Average Acoustic Descriptor, dB(A)
Leq Loo Lio Li

D* E* N* D* E* N* D* E* | N* | D* E* N*
20/11/19 59 48 48 57 45 42 60 50 50 61 53 53
21/11/19 57 52 50 55 50 45 59 54 51 61 56 54
22/11/19 58 48 48 56 44 43 59 50 | 49 61 53 53
23/11/19 58 | 52 | 48 56 46 43 59 | 54 | 49 | 60 | 56 | 53
24/11/19 58 45 49 56 42 43 59 | 46 50 60 | 48 54
25/11/19 59 | 49 | 50 57 45 46 | 60 | 50 | 51 | 62 | 53 | 54
26/11/19 59 48 48 57 46 44 60 50 50 62 52 54
27/11/19 59 57 61 63
AVERAGE 58 49 49 56 45 44 60 | 50 | 50 | 61 53 54

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* D- Day (7:00-18:00), E- Evening (18:00 — 22:00), N-Night (22:00-7:00)

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx

 

Page 12

Table 3 -Rion NL42 Measurement Summary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Date Average Acoustic Descriptor, dB(A)
Leq Loo Lio Li

D* E* N* D* E* N* D* E* N* D* E* N*
20/11/19 54 48 44 51 46 37 56 50 | 46 66 56 59
21/11/19 52 | 49 | 44 49 46 36 | 53 | 50 | 46 | 66 | 59 | 61
22/11/19 52 49 44 49 46 36 53 50 | 45 66 | 60 61
23/11/19 52 48 44 49 46 35 54 | 49 | 46 66 58 60
24/11/19 53 | 48 | 43 49 45 36 | 56 | 50 | 45 | 67 | 58 | 61
25/11/19 52 49 43 49 46 37 54 51 45 66 | 61 61
26/11/19 57 51 44 52 47 37 59 54 | 46 70 59 60
27/11/19 54 51 56 67
AVERAGE 53 49 44 50 46 36 55 51 46 | 67 | 59 | 60

 

* D- Day (7:00-18:00), E- Evening (18:00 — 22:00), N-Night (22:00-7:00)

4.2.2 Attended Measurement Results

Table 4 -Loading Dock Activity, Attended Measurements

 

 

 

 

 

 

Location’ Noise Source Acoustic Descriptor, dB(A)
Leq Lax Lpeak
1 Mechanical plant @ 25 57 62 78
metres
2 Reversing signal from trolley 69 76 83
collection truck
3 Mechanical plant noise 71 73 85

 

through exhaust/grille @ 1

metre away

 

 

 

 

' Refer to Figure 2 for location on map.

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx

 

 

Page 13

5 NOISE SOURCES/IMPACTS

The following sections outline current major noise sources that were identified upon the previous site visit
to have potential impact on site.

5.1 LOADING DOCKS
5.1.1 Trolley Collection

During time on site, it was observed that trolley activity is a regular occurrence across both loading docks.
Noise level that was measured in relation to noise produced by trolley activity was 69 dB(A) Leg. Trolley
collections is understood to only occur during day and evening periods (i.e. 7am to 10pm) which is also
considered in this assessment.

5.1.2 Delivery Trucks

It was observed that small to medium sized delivery trucks were present within the loading docks during
time of site visit with no more than 1 truck in each hour at the loading docks. As advised by the client, we
note that the loading dock operational hours start at 3am and can run up to 10pm. Truck (incl. refrigeration
truck) idling was only assumed to occur in the loading dock during nominal 15minute loading period, and
not along the boundaries or at the entrance to the loading docks. Where trucks enter the site to wait for
loading and generally during loading (unless short-time drop-off/pick-up), engines must be turned off and
in case of refrigeration trucks, these should just come in and leave site after loading as no idling would be
allowed at other times. Such restrictions should be included if not yet followed (e.g. signs installed at the
entry and along the boundaries and within the shopping centre loading docks).

5.1.3. Mechanical Plant
The following mechanical plant was observed and noted in Figure 2.

e Eastern Loading Dock Plant deck above loading dock ‘5’ emitting a calculated sound power level
of 93dB(A).

e Kitchen exhaust sound power level of 99dB(A).

e Western Loading Dock - Plant room/exhaust adjacent loading dock ‘2’ were measured and
calculated to have a sound power level 90 dB(A).

Other plant is generally located on the rooftop of the shopping centre and therefore, providing significant
noise shielding. In any case, the assessment is based on a sound power level of 90dB(A)

At night, our predictions are based on kitchen exhaust fan being turned off together with other plant
adjacent to loading docks.

No other mechanical plant was considered and located during site inspections. In case of additional other
plant, these must operate to ensure that the Loo background noise levels at the future residential buildings
are not exceeded.

5.1.4 Compactor

A compactor was noticed located by the ‘Big W’ loading dock 3 with an assumed Lmax Sound power level of
100 dB(A). Compactor operation has been excluded from night time assessments as it should only operate
between the hours of 7am and 6pm.

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 10

Page 14

5.2 NOISE CALCULATION

Measured noise levels and mechanical plant noise data and operational conditions highlighted in the
previous section have been used to calculate the predicted intrusive noise levels at the sensitive noise
receptors (lots 17, 18, 19, and 21) based on the expected building layouts of the Lots as described below
and indicated in the figures below.

A SoundPLAN™ computer model was developed for these noise sources as described activities and used to
predict noise emissions from the compactor and loading docks to the sensitive receptors (lots 17, 18, 19,
and 21). Predictions were made for the following scenarios:

e Allloading docks and compactor operating concurrently, representing the worst-case scenario
for day time noise emissions.

e All loading docks operating concurrently, representing the worst-case scenario for evening and
night time noise emissions as per the description in Section 5.1;

e Only the compactor operating within the hours nominated and assumed.

e Mechanical plant operational scenarios as described in this report.

The analysis was conducted based on the following assumptions:

e Mechanical plant decks indicated in Figure 2 have a sound power level of 90 dB(A) Leg each.

e Kitchen exhaust fan indicated in Figure 2 has a sound power level of 99dB(A) Lea;

¢ Loading dock trucks have a sound power level of 101 dB(A) Linax.

e Refrigeration trucks were assumed to idle for 15 minutes whilst unloading, with a sound power
level of 95dB(A) Leq at a height of 3m above the ground level. This idling was only assumed to
occur in the loading dock, and not along the boundaries or at the entrance to the loading docks.
The refrigeration trucks, therefore, must not enter the site prior to loading to wait for their turn.
Such restrictions should be included if not yet followed (e.g. signs installed at the entry and
along the boundaries of the shopping centre loading docks).

¢ For all other trucks, no idling was assumed within the sites within short term drop-off/pick-up
occurring at the loading docks only (less than 10minutes) and such restrictions should be
included if not yet followed (e.g. signs installed at the entry and along the boundaries of the
shopping centre loading docks).

¢ Compactor indicated in Figure 2 has a sound power level of 100dB(A) Linax.

e Kitchen exhaust fans being turned off between 10pm and 7am and other plant adjacent and
within loading docks not operational after 10pm and prior to 7am.

¢ Compactor is not operational between 6pm and 7am;

« No trolley collection between 10pm and 7am.

e The presence of a 6m wide plantation buffer between the northern boundary of the residential
lots and the shopping centre paved loading dock and entry boundary.

e Facade line of proposed residential development approximately 8 metres from loading dock
boundary (refer to the closest sensitive receiver buildings used in calculations indicated in figure
below)

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 11

Page 15

     

Assumed receiver
building locations
for Lots 17,18,19
and 21.

 

¢ Assessed habitable space taken as a typical bedroom with a floor area of 11m, and volume of
27m.

* Typical fagade/glazing area of typical bedroom - 7.7m’, with the assumed typical layout
presented below

¢ Assessed typical living room with a floor area of 20m?, and volume of 50m? with total fagade
glazing area 8m’, with the assumed typical layout presented below;

¢ 1.8m high acoustic barrier along the boundary of lots 19, and 21 as indicated in Section 6.

Other configurations and activities/plant must be re-assessed during detailed design review of the
residential development to ensure that indoor noise limits can be achieved.

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 12

Page 16

 

Glazing 2.1m x 1.5m

 

 

Glazing 3.0m x 0.5m Glazing 3.0m x 0.5m

DD

Balcony Balcony

 

   

     

    

Bedroom

   

Bedroom

 

Glazing 3.0m x 1.2m
Glazing 3.0m x 1.2m

Living Room Living Room

Unit 1 Unit 2

 

 

 

eee= Facade Wall
== = internal Partition Wall
Figure 3- Assumed Typical Unit Layout

Figure 4 to Figure 6 present the SoundPLAN™ model of the day time period emissions for all loading docks
and the compactor operating concurrently. To assess compliance against the Laz,aqj1nr Noise criteria for the
worst-case conditions, the model presents the Lmax dB(A) noise levels. The model includes the existing 1.0m
high wall in the loading area, as well as the proposed 1.8m high acoustic barrier along the boundary of the
sensitive receivers (lots 19, and 21 as indicated in Section 6).

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 13

Page 17

 

Noosa Civic
Shopping Centre

 

 

Loading dock barrier (1000mm)
Residential barrier (1800mm)

Loading dock Lmax 101 dB(A) SWL
‘Compactor Lmax 100 dB(A) SWL
Ground Level

4.8m above building pad level

Prepared by: 08
Date: 28/07/2020

Noise Level Signs and symbols

 

Linax Line source
Be

[ZZ won batons

wal

 

 

 

 

acousTe

Figure 4- SoundPLAN™ Day Time Modelling of All Loading Docks and Compactor — Ground Level

 

 

 

NN Noosa Civic

Shopping Centre

 

 

 

Loading dock barrier (1000mm)
Residential barrier (1800mm)

Loading dock Lmax 101 dB(A) SWL
‘Compactor Lmax 100 dB(A) SWL
Level 1

4.8m above building pad level

Prepared by: 08
Date: 28/07/2020

Noise Level Signs and symbols

 

 

 

 

acousTe

Figure 5- SoundPLAN™ Day Time Modelling of All Loading Docks and Compactor — Level 1

 

 

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 14

Page 18

 

 

Noosa Civic
Shopping Centre

 

 

Loading dock barrier (1000mm)
Residential barrier (1800mm)

Loading dock Lmax 101 dB(A) SWL
‘Compactor Lmax 100 dB(A) SWL
Level 2

7.8m above building pad level

Prepared by: 08
Date: 28/07/2020

Noise Level Signs and symbols

Line source

 

Lax
aS

mm - «4 iain builcing
© Dy man outone

wal

 

 

 

 

 

acousTe

 

 

Figure 6- SoundPLAN™ Day Time Modelling of All Loading Docks and Compactor — Level 2

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx

15

Page 19

Figure 7 to Figure 9 present the SoundPLAN™ model of the evening/night time period emissions for all
loading docks operating (note: loading dock not operational after 10pm and before 3am).

 

Sr

Noosa Civic
Shopping Centre

Loading dock barrier (100mm)
Residential barrier (1800mm|

Loading dock Lmax 101 dB(A) SWL

Ground Level
4.8m above building pad level

Prepared by: 08
Date: 26/07/2020

Noise Level Signs and symbols

ne source

 

= ‘Main buitsing
SB. : 4 8
Wai

 

  
  

<x ACOUSTIONS

 

Figure 7- SoundPLAN™ Evening/Night Time Modelling of Loading Docks Only - Ground Level

 

~ Noosa Civic

Shopping Centre

Loading dock barrier (100mm)
Residential barrier (1800mm|

Loading dock Lmax 101 dB(A) SWL

Level 1
4.8m above building pad level

Prepared by: 08
Date: 26/07/2020

Noise Level Signs and symbols

  

©
Man uli
3 2

wal

 

 

<x ACOUSTIONS

 

 

Figure 8- SoundPLAN™ Evening/Night Time Modelling of Loading Docks Only - Level 1

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 16

Page 20

 

Noosa Civic
Shopping Centre

     
     

Loading dock barrier (100mm)
Residential barrier (1800mm|

Loading dock Lmax 101 dB(A) SWL

Level 2
7.8m above building pad level

Prepared by: 08
Date: 26/07/2020

Noise Level Signs and symbols

ne source

 

Lmax
naa oie source

= ‘Main buitsing
SB. : 4 8
Wai

 

 

x ACOUSTIONS

 

Figure 9- SoundPLAN™ Evening/Night Time Modelling of Loading Docks Only — Level 2

Figure 10 to Figure 12 present the SoundPLAN™ model of the day time period emissions for only the
compactor operating.

 

Noosa Civic
Shopping Centre

Loading dock barrier (1000mm)
Residential barrier (1800mm)

Compactor Lmax 100 dB(A) SWL

Ground Level
1.8m above building pad level

Prepared by. OB
Date: 28/07/2020

Noise Level Signs an
L

max
ingsay

 

mm

Go - 3
8. 48
6 49
49-52

 

 

 

 

ACOUSTICNG

Figure 10- SoundPLAN™ Day Time Modelling of Compactor Only - Ground Level

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 17

Page 21

 

Noosa Civic
Shopping Centre

Loading dock barrier (1000mm)
Residential barrier (1800mm)

Compactor Lmax 100 dB(A) SWL

Level 1
4.8m above building pad level

Prepared by. OB
Date: 28/07/2020

Noise Level Signs and symbols

Une source

  

max
ingsay

mm

Go - 3
8. 48
6 49
49-52

Gi 2 - 55

  

ACOUSTICNG

Figure 11- SoundPLAN™ Day Time Modelling of Compactor Only — Level 1

 

Noosa Civic
Shopping Centre

Loading dock barrier (1000mm)
Residential barrier (1800mm)

Compactor Lmax 100 dB(A) SWL

Level 2
7.8m above building pad level

Prepared by: OB
Dato: 28/07/2020

Noise Level Signs and symbols
L, —— Une source

ingsiA)
Point source

mm Main buildin
ms J s

 

Walt

  

 

 

ACOUSTICNG

Figure 12- SoundPLAN™ Day and Evening Time Modelling of Compactor Only — Level 2

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 18

Page 22

Figure 13 and Figure 14 present the SoundPLAN™ model mechanical plant day and evening time period

emissions.

 

   
 
 
  
   
 
  

 

Noosa Civic
Shopping Centre

Loading dock barrier (1000mm)
Residential barrier (1800mm)

Propared by: OB
Date: 26/08/2020

Noise Level Signs and symbols
4 LAeq — wall
{ in dBA)

mmm <0
Mo 3
43-48
4%. 49
49 - 52

 

AcOUSTICNG

Figure 13- SoundPLAN™ Day and Evening Time Modelling of Mechanical Plant — Lots 17 and 18

 

 

 

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx

      
  

Noosa Civic
Shopping Centre

Loading dock barrier (1000mm)
Residential barrier (1800mm)

Propared by: OB
Date: 2608/2020

Noise Level Signs and symbols
LAeq — wal

naa)

mmm

MB wo - 3
43 - 48
4%. 49

lm «9 - 52

 

 

ACOUSTICN

19

Page 23

Figure 14- SoundPLAN™ Day and Evening Time Modelling of Mechanical Plant - Lots 17, 18 and 19

Noosa Civic
Shopping Centre

Loading dock barrier (1000mm)
Residential barrier (1800mm)

Propared by: OB
Date: 2608/2020

Noise Level Signs and symbols
LA — wal
ncaa)

=

MB wo - 3
43 - 48
4%. 49

=

      

 

ACOUSTICN

Figure 15- SoundPLAN™ Day and Evening Time Modelling of Mechanical Plant - Lot 21

 

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 20

Page 24

Figure 16 to Figure 18 present the SoundPLAN™ model mechanical plant night time period emissions (note:
kitchen exhaust and any mechanical plant adjacent to loading docks or any other major plant turned off).

 

 

 

Noosa Civic
Shopping Centre

Loading dock barrier (1000mm)

Residential barrier (1800mm)

Source Noise Levels LAeq SWL
Chiller Plant 85 dB(A)

Ground Level
4.8m above building pad level

Prepared by: OB
Date: 2807/2020

Noise Level Signs and symbols

 

Une source

inca)

£  Point source

[Z Win bung

Walt

 

Point receiver

 

 

Figure 16- SoundPLAN™ Night Time Modelling of Mechanical Plant - Ground Level

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx

21

Page 25

 

Noosa Civic
Shopping Centre

Loading dock barrier (1000mm)
Residential barrier (1800mm)

Source Noise Levels LAeq SWL

Chiller Plant 85 dB(A)

Level 1
4.8m above building pad level

Prepared by: OB
Date: 2807/2020

Noise Level Signs and symbols

 

seuereasesss

acoustic We

LOG

 

Figure 17- SoundPLAN™ Night Time Modelling of Mechanical Plant - Level 1

 

~ | Noosa Civic

Shopping Centre

Loading dock barrier (1000mm)
Residential barrier (1800mm)

Source Noise Levels LAeq SWL

Chiller Plant 85 dB(A)

Level 2
7.8m above building pad level

Prepared by: OB
Date: 2807/2020

Noise Level Signs and symbols

 

seuereasesss

acoustic We

LOG

 

 

 

 

Figure 18- SoundPLAN™ Night Time Modelling of Mechanical Plant — Level 2

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 22

Page 26

Table 5 - Predicted Shopping Centre Noise Impacts at the Proposed Residential Lots

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Receiver’ Time Predicted Incident Noise Level at Facade Internal Acoustic
dB(A) Noise Level | Treatment
Criteria Required
. Compact. | Mech.
Loading Docks La? Plant? dB(A) to Achieve
Laeq Indoor
La Laeq Noise
Limit*
Day 28 52 45 Latad,thr
Evenin 35 Laeqadj.th
Lot v Ground ig 57 AG eq,adj,1hr Type A
eve . N/A 40 Latadjthr
Night 4
30 Lpeg,adj,1hr
Day 28 56 45 Latad,thr
Evening 35 Laeguadj,thr
Lot 17 Level 1 60 50 Type B
Night N/A 4s AO Latadjthr
30 Lheg,adj.thr
Day 29 45 Latad,thr
57
Evening 61 35 Laeg,adj,thr
Lot 17 Level 2 53 Type B
N/A 40L, 1
Night 48 Atadiin
30 Lheq,adj.thr
Day 37 45 Lat,adjhr Acoustic
Evening >! 35 Laeqadj,thr Seals to
Lot 18 Ground 46 32 windows,
level ; N/A AO Laradthe Non glazed
Night 43 wall to Type
30 Lpcg,adj,thr A
Day 37 57 45 Latad,thr
Evening 35 Laeqadj,thr
Lot 18 Level 1 47 39 Type A
Night N/A 4s 40 Lat ad, thr
30 Laeg,adj,thr
Day 41 57 45 Lat adj thr
Evening 35 Laeq,adj.thr
Lot 18 Level 2 51 45 Type A
. N/A 40 Latadjthr
Night 46
30 Laeg,adj,thr
Day 55 53 45 Latad)thr
Evenin N/A 35 Laeguadj.th
Lot 19 Ground g 59 48 / eq.adj Ahr Type B
level 40 Latadjthr
Night 39
30 Leg,adj,thr
Lot 19 Level 1 Day 61 49 63 56 45 Lat,adjthr Type B
I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 23

 

Page 27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

| . Predicted Incident Noise Level at Facade Internal Acoustic
Receiver Time .
dB(A) Noise Level | Treatment
Loading Dock Compact. | Mech. Criteria Required
oadiing Nock La? Plant? dB(A) to Achieve

Laeq Indoor

Lat Laeq Noise

Limit*
Evening 35 Laeqadj,thr

N/A 40 L,

Night 4A A1,adj, Thr
30 Lheg,adj,thr
Day 63 56 45 Latad,thr
Evening 35 Laeqadj,thr

Lot 19 Level 2 62 49 Type B

N/A 40 L,

Night A5 A1,adj,1hr
30 Laeg,adj,thr
Day 64 58 45 Latad,thr
Lot 21 Ground | Evening 35 Lacq,adj.thr

level 66 53 N/A WO lesan Type C

Night 38 a

30 Laeg,adj,thr
Day 69 61 45 Lat,adjthr
Evening 35 Laeqadi,thr

Lot 21 level 1 70 58 Type C
Night N/A 4s 40 Latadjthr
30 Lieq,adj,thr
Day 69 62 45 Lat,adjthr
Evening 35 Lheg,adj,thr

Lot 21 level 2 70 58 Type C
Night N/A a7 40 Latadjthr
30 Laeg,adj.thr

 

' Refer to Figure 2 for location on map

2 Compactor and associated plant only operational between 7am and 6pm. On that basis, at other times

noise impact is N/A — not applicable

3 Exhaust fan and other plant adjacent to loading docks only operational between 7am and 10pm.

* Based on most exposed rooms and building locations as per Figure 4 The rooms assume typical bedroom
and living room dimensions with bedroom glazed facade area of 7.4m”. Subject to final room and building
layouts and the shielding offered by other buildings, the facade acoustic treatment requirements may differ
and would need to be reviewed after plans are finalised.

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx

24

 

Page 28

6 RECOMMENDATIONS

6.1 MANAGEMENT CONTROLS

It is recommended that operation of the compactor to be limited to the day time period only (7am - 6pm)
and not use kitchen exhaust and other mechanical plant adjacent to the loading docks between 10pm and
7am.

Furthermore, trolley collection must not occur after 10pm and prior to 7am.

Loading dock operation is to be limited to the time period between 3am and 10pm only, with refrigeration
trucks recommended to idle for a maximum of 15 minutes during unloading. This idling shall only occur
during the loading/unloading activity at the loading dock, and not whilst waiting to enter the loading dock
or along the boundaries. In the case of refrigeration trucks, planned entry times could be scheduled before
hand to ensure that no idling occurs along the boundaries or at the entry to the loading docks.

For all other trucks, no idling should occur within the sites at any time also with the exception of a short-
time pick-up/drop-off within the loading dock.

Such restrictions should be included if not yet followed (e.g. signs installed at the entry and along the
boundaries of the shopping centre loading docks and within loading docks). Furthermore, If trucks are to
remain idling whilst waiting to enter the loading dock, it is recommended that this is done away from the
site as otherwise the impacts can be adverse.

6.2 ACOUSTIC BARRIER

An acoustic barrier is recommended along the northern boundary of lots 21 and 19 adjacent to the
blockwork loading dock wall as shown in Figure 19. The height of the barrier must be a minimum of 1.8
metres above the loading dock ground level or top of the existing loading dock blockwork wall whichever
is higher, with a minimum surface density of 12 kg/m. This assumes that the pad heights of the residential
buildings do not exceed that of the loading dock concrete pad level.

Figure 19- Acoustic Barrier

+ coor
Pore

     

05"
2 505

Acoustic barrier 1.8m high above loading dock ground level or top of loading dock blockwork wall,
whichever is higher

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 25

Page 29

6.3 RESIDENTIAL BUILDINGS FACADE CONSTRUCTION

In addition to the management controls, to achieve the indoor noise levels within the considered habitable
areas (refer to Section 5.2), the following minimum facade construction is proposed. Refer to Table 5 for
specific locations where each Facade Type applies.

Table 6 - Fagade Construction Recommendations

 

Type Glazing Systems Facade Wall

 

A Nominal openable glazing system - Rw33 Masonry construction or Cladded
nominally with 6.38mm lam glass and seals | facade (9mm fibre cement sheet)
on 90mm timber studs - cavity
insulation (e.g. 75mm thick
11kg/m3 glasswool) — min 10mm
thick plasterboard internally

 

B Nominal openable glazing system - Rw35 Masonry construction or Cladded
nominally with 10.38mm lam glass and facade (9mm fibre cement sheet)
acoustic seals on 90mm timber studs - cavity

insulation (e.g. 75mm thick
11kg/m3 glasswool) — min 13mm
thick Fyrchek plasterboard

 

internally
Cc Nominal openable glazing system - Rw37 Masonry construction or Cladded
nominally with 10.76mm lam glass and fagade (9mm fibre cement sheet)
acoustic seals on 90mm timber studs - cavity

insulation (e.g. 75mm thick
11kg/m3 glasswool) — min 2 layers
of 13mm thick Fyrchek
plasterboard internally

 

 

 

 

 

In the case where any of the apartments/habitable areas are elevated with the floor exposed to noise from
the shopping centre, the floor is assumed to be of concrete construction (nominally 150mm thick). Other
construction details may be acceptable but must be reviewed and approved by an acoustic consultant in
order to achieve indoor noise levels of finalised building layouts.

The minimum roof construction must be of concrete or alternative colorbond with Anticon 145 and
plasterboard ceiling with 75mm thick glasswool (11kg/m3) overlay.

Where building layouts and locations or habitable areas differ from what has been considered, additional
assessment is required.

Buildings located further from the loading docks in comparison to the ones considered in this report must
be constructed based on Type A construction as a minimum.

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 26

Page 30

6.4 MECHANICAL PLANT NOISE LEVELS

In order to achieve compliance with the continuous noise criteria outlined in Table 1, the operational
conditions must follow the recommendations in Section 5.

a) )
; i Va. fa ‘ays
eo) “i
7 Mech. plant deck
Exhaust/Mech. plant AL fl /

nea > aS J

Mech Plant Adjacent
to Loading Docks

Mech Plant Adjacent
to Loading Docks

Figure 20- Mechanical Plant Locations

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx

 

27

Page 31

7 CONCLUSION

ALC have conducted a noise impact assessment of the loading dock activities and mechanical plant located
at Noosa Civic Shopping Centre, 28 Eenie Creek Road, Noosaville. The purpose of the assessment was to
determine the predicted intrusive noise levels at the proposed subdivision site on Hofmann Road for lots
17, 18, 19, and 21. Previous noise monitoring data conducted by ALC (ref: 20191414.1/1501A/R2/SS, dated
15/01/2020) has assisted in establishing the acoustic environment associated to the subject site (Table 1 and
2).

Provided the recommendations in Section 6 are implemented, the development is predicted to achieve
compliance with the Noosa Shire Council assessment indoor noise criteria.

We trust this information is satisfactory. Please contact us should you have any further queries.

Yours faithfully,

Gnil

Acoustic Logic Consultancy Pty Ltd
Omar Busaidi

I\Mobs\2019\20191414\20191414.2\202009030BA_R4_Noise_Impact_Assessment.docx 28

Used in these records

About this file

File size
5.9 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

20200903OBA_R1_Loading_Dock_Operational_Conditions.pdf · 5.9 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.