Report No: W6107 de. Client Name: K Grandemange Report Date: August 24, 2016 Site Address: No 61 Morinda Circuit, Noosaville.
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 3 pages
Page 2
Report No: W6107 de. Client Name: K Grandemange Report Date: August 24, 2016 Site Address: No 61 Morinda Circuit, Noosaville.
Page 3
MASONRY SPECIFICATION
Construction, masonry work to comply with AS3700.
Masonry Unit Strength, f'uc = 15mPa (unconfined strength)
Mortar, cement 1, lime 1/2 , sand 41/2 + melthyl cellulose water thickener
Grout, f'c = 20mPa (confined test)with 10mm aggregrate with pouring consistency & a minimum
cement content of 300kg/cubic metre
Steelwork cover, as indicated on drawings but not less than 20mm fromthe face of the grout to the
reinforcement face.
Reinforcement laps, deformed bars - 40 times* bar diameter Grout placement & compaction, carefull
placement to avoid segregation and disturbance of mortar joints and compact with a 25mm rod.
Note - all lintels must be fully propped during & for a mimimun of 14 days (or for longer if required)
after the construction of upper walls, slabs, roofs or other structural elements
Report No: W6107 de.
Client Name: K Grandemange
Report Date: August 24, 2016
Site Address: No 61 Morinda Circuit, Noosaville.
Page 4
Report No: W6107 de. Client Name: K Grandemange Report Date: August 24, 2016 Site Address: No 61 Morinda Circuit, Noosaville.