DRAWING SIZE — A2
REQ. —118.0kN
(Nom. not inc.)
+
=z
<a
So
mD-
I
>
oS
a
a
REQ. —86.9kN
S
=
oS
€
€
S
2
BRACING PROVISION
Oo
ALL LINTEL SIZES NOTED ON
PLAN ARE TO BE (LVL’S)
U.N.O
BRACING KEY
BRACING PANEL LENGTH.
1.8 (PB) <——BRACING PANEL TYPE.
(PB) - 4.0mm F27 PLY FIXED IN ACCORDANCE WITH
THE MANUFACTURERS REQUIREMENTS TO
ACHIEVE 6.0kN/m
LEGEND
\
BEAM /TOP PLATE TO FLOOR ‘BEARER/FLOOR
SLAB U.N.O.
——— BRACING PANEL, REFER BRACING KEY FOR SIZE
TYPE AND STRENGTH.
FB OVER FLOOR BEAM OVER REFER FLOOR FRAMING PLAN
(P1) 89 x 89 x 3.5 SHS POST.
(P2) 200 x 100 x 5.0 SHS POST. (Galv.)
(P3) 90 x 4.0 CHS POST. (Galv.)
3(No.) M10 MASONRY BOLTS FROM STUD WALL
TO CORE FILLED BLOCK WALL, EQUALLY SPACED
UP STUD.
(ZzzzzzzZ) 190 GROUT FILLED BLOCK WALLS, N12
VERTICALS AND HORIZONTALS AT 400 CTRS AND
FULL PERIMETER OF ALL OPENINGS, ADDITIONAL
VERTICALS WHERE NOTED ON PLAN.
* (ve)
N12-400 BOTH
DIRECTIONS
N12-400 BOTH
DIRECTIONS
&
a
2/200 x 45
2/200 x 45
Voip | 1 |
.
nfo
w
-
2/200 x 45
(WB)
150 x 45)
WALL FRAMING, BRACING, AND TIE DOWN PLAN
10mm MS WEB END
PLATE 5.0 C.F.W —]
C.F.W EITHER SIDE | |
.0 (PB |
a
le leel |
is js By ]
JF) | Fe !
| D2\ |
- ' I - |
| | | |
pox | |
—_——_—_— —_—_- I 7 —_ i
Let 3)
ye |
aS |
| oy!
| |
| | &
| | oOo
| | 2
| |
| |
| |
| | (P3)
a ae —| —-—_- ¢
eee a
| |
| |
| |
J ud
mo LS ny
= a) TU ia
1 Frans |
| Lal FB2
8mm MS WEB 10mm MS WEB ENS
STIFFENER 5.0 i | PLATE 5.0 CF.W
4/M16.
OF WER. (P2)
a UB/SHS POST CONNECTION
\ = / DETAILS
Revision | Description Date
A REVISED POST LOCATIONS 24.02.14
B. REVISED SUPPORT TO REAR DECK,
. CARPORTS ADDED. /
Cc DETAIL 2 ADDED 25.05.15
TIMBER FRAME SPECIFICATION NS
UPPER FLOOR — LOAD BEARING
| MEMBER SIZE/GRADE | COMMENT
Top Plates | 1/90x45 (F8) +] Not trenched
1/90x35 (F8
Studs @ 450} 90 x 35 (
Btm. Plate | 90 x 45
ri 2700(H) Max.
F8) | Not trenched
F8) | Where on slab
Noggins 90 x 35 (F8) | At 1100cts max.
LOWER STOREY OF 2 — LOAD BEARING
MEMBER SIZE/GRADE COMMENT
| Top Plate 90 x 45 (F8) | Not trenched
Studs @ 450 | 90 x 35 (F8) | 2700(H) Max.
Not notched
2/90 x 35 (F8) | 3600(H) Max.
Not notched
Btm. Plate | 90 x 35 (F8) | Not trenched
Noggins 90 x 35 (F8) | At 1100cts max.
Jamb studs as per AS 1684.2.
NON-LOAD BEARING
MEMBER SIZE/GRADE COMMENT
Top Plate 90 x 35 (F8) -
Studs @ 450} 90 x 35 (F8) -
Btm. Plate | 90 x 35 (F8) -
Noggins 90 x 35 (F8) Mid Ht.
NOTE : 70x 35 (F8) can be used in lieu of 90 x 35 (F8)
internal non—loadbearing where approved by architect
r—— SIDE BOLTED TO
{ A M12—-600 STAGGERED.
EXISTING ROOF BEAM.
10mm MS END PLATE
TT 5.0 CFM. TYPICAL SECTION A-A
A
90 x 4.0 CHS POST.
10mm MS END PLATE 5.0
CF.W.
2/M16 x 300 (L) CHEMSET.
EXPOSED REINFORCING
TO BE TREATED &
EXISTING |CARPORT SEALED FROM MOISTURE.
BLOCKWORK.
/D2\, CHS POST CONNECTION
\-/ DETAILS
THIS DRAWING AND ASSOCIATED DETAILS
MUST BE READ IN CONJUNCTION WITH THE
NOTES CONTAINED ON 23262-N.
rm1:100 @ A2
Issue:
CONSTRUCTION
STRUCTURAL eCIVILeGEOTECHNICAL
ABN 40 098 481 899
SCG)consulting ENGINEERS
1/11 PROJECT AVE NOOSAVILLE QLD 4566
Ph (07) 5455 5604 Fax (07) 5455 5696
Title: Wall Framing, Bracing, And Tie Down
‘ Plan.
Project. 20 & 22 Tristania Drive
Marcus Beach
Rev.
30.01.05
Date: Jan 2014 Drg No. 23262 -S3
Rev. -
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
SCG Plan.pdfRelated documentApplication case desk ↗
About this file
- File size
- 275 KB (small file)
- File type
No other editions are linked here.