RESPONSE TO SARA IR - Attachment 1A - RFA24-059-SARA IR Response 310725
4
8. This will result in the loss of 166.03 sq.m. of Category B regulated vegetation (green
polygon). This additional clearing may be included within what is defined as a firebreak as
part of the MCU under the State Code 16.
9. However, we further note that the fact sheet provides with the following clarification with
respect to a necessary firebreak or necessary fire management line. The fact sheet states
in reference to what is necessary clearing “Landholders intending to operate under this
exemption may only clear firebreaks and fire management lines where they are necessary
to protect lives and property”.
10. Therefore, the necessary clearing is only that which is required to provide an acceptable
level of bushfire risk for the proposed development.
11. The State Planning Policy, Natural Hazards, Risk and Resilience Technical Guideline
indicates that an acceptable risk as achieve a Radiant Heat Flux of no greater than
29kW/m2.
12. The minimal separation distance that achieves a Radiant Heat Flux of 29kW/m2 is
calculated using the Flamesol Method 2 minimal distance calculator with the local input
values for the FFDI and attributed fuel load values for the mapped Vegetation Hazard
Class. Table 1 below provides the minimal distance calculation that achieves the Radiant
heat flux value of 29kW/m2.
Table 1 – Minimal distance Calculation
Doonan Waste Management Facility - Minimum Distance Calculator - AS3959-2018 (Method 2)
(Calculated July 25, 2025, 4:39 pm (MDc v.4.9))
Inputs Outputs
Fire Danger Index 48 Rate of spread 1.25 km/h
Vegetation Forest Flame length 11.04 m
Classification
Understorey fuel load 21 t/ha Flame angle 53.5 °, 63.5 °, 72.5 °, 77.5 °, 78.5 ° &
84.5 °
Total fuel load 24.2 t/ha Elevation of receiver 4.35 m, 4.83 m, 5.1 m, 5.16 m, 5.13 m
& 4.79 m
Vegetation height n/a Fire intensity 15,654 kW/m
Effective slope .5 ° Transmissivity 0.879, 0.863, 0.841, 0.816, 0.803 &
0.736
Site slope .5 ° Viewfactor 0.5971, 0.4385, 0.2966, 0.2007,
0.1633 & 0.0445
Flame width 100 m Minimum distance to < 40 9.1 m
kW/m²
Windspeed n/a Minimum distance to < 29 12.4 m
kW/m²
Heat of combustion 18,600 Minimum distance to < 19 18.2 m
kJ/kg kW/m²
Flame temperature 1,090 K Minimum distance to < 12.5 26.3 m
kW/m²
Minimum distance to < 10 31.5 m
kW/m²
Rate of Spread - Mcarthur, 1973 & Noble et al., 1980
Flame length - NSW Rural Fire Service, 2001 & Noble et al., 1980