D24CAL Working Drawings - Issue B

Attached to the e-mail Request for GIA - MCU220063 - General In Accordance - Amendment Request with correct plans - 25 Lawnville Rd COOROY.msg.

of 24

Page text shows just the words. Original shows the document exactly as it was published.

Original PDF page 2, section 1. The text section number identifies this passage in the reader.

GENERAL NOTES
DIMENSIONS:                                                                      CONCRETE:                                                                                        ELECTRICAL SERVICES:
- DO NOT SCALE DRAWINGS                                                          ALL CONCRETE FLOORS AND PAVING SLABS SHALL BE REINFORCED CONCRETE IN                             ELECTRICAL SERVICES TO BE PROVIDED IN ACCORDANCE WITH THE FOLLOWING:
- SET OUT DIMENSIONS SHALL NOT BE OBTAINED BY SCALING THE DRAWINGS.              ACCORDANCE WITH STRUCTURAL ENGINEER'S DRAWINGS.                                                  ELECTRICAL INSTALLATION: TO AS/NZS 3008.1.1 AND SAA HB 301.
-ALL SET OUT DIMENSIONS SHOWN ON THE DRAWINGS SHALL BE CHECKED BY THE            WAFFLE POD SLAB SYSTEM TO PROPOSED DWELLING TO ENGINEERS DESIGN AND                              TELECOMMUNICATIONS CABLING: TO AS/ACIF S008, AS/ACIF S009, AS/NZS 3080, SAA HB 29
CONTRACTOR BEFORE CONSTRUCTION                                                   SPECIFICATIONS.                                                                                  AND SAA HB 252.
- ALL DIMENSIONS SHOWN ON FLOOR PLANS DO NOT INCLUDE INTERNAL WALL               CONCRETE PATHS TO FALL AWAY FROM FOOTINGS AT 1:20 MAXIMUM.                                       DOMESTIC ELECTRICITY METER ENCLOSURES: TO AS 6002.
SHEETING OR EXTERNAL WALL CLADDING UNLESS NOTED OTHERWISE.                       SAND BED UNDER PATHS AS REQUIRED.
                                                                                                                                                                                  MECHANICAL VENTILATION:
- ALL DIMENSIONS ARE FOR CONSTRUCTION USE AND ARE FROM FRAME TO FRAME.           10mm FOAM EXPANSION JOINT TO ALL AREAS WHERE EXTERNAL CONCRETE MEETS                             ALL BATHROOMS, LAUNDRIES, AND WC'S NOT NATURALLY VENTILATED ARE TO BE
- ALL DIMENSIONS TO BE CONFIRMED ON SITE PRIOR TO CONSTRUCTION.                  MAIN HOUSE SLAB.
                                                                                                                                                                                  MECHANICALLY VENTILATED IN ACCORDANCE WITH AS1668.2 AND AS/NZS 3666.1.
- LOCATION & SIZE OF ALL STRUCTURAL COLUMNS & LOAD BEARING WALLS TO BE
                                                                                                                                                                                  EXHAUST FROM BATHROOMS, KITCHENS, SANITARY COMPARTMENTS AND
CONFIRMED ON SITE PRIOR TO CONSTRUCTION BY CONTRACTOR.                                                                                                                            LAUNDRYS MUST BE MECHANICALLY DISCHARGED DIRECTLY TO ATMOSPHERE IN
- FLOOR LEVEL DIFFERENCES TO BE CONFIRMED ON SITE PRIOR TO CONSTRUCTION          TERMITE PROTECTION:
                                                                                 TERMITE PROTECTION TO BE IN ACCORDANCE WITH AS3660.1 PT.1 AND SECTION B OF THE                   ACCORDANCE WITH NCC PART 3.8
                                                                                 NCC.                                                                                             AIR CONDITIONING SYSTEMS:
NCC REQUIREMENTS
                                                                                 FLASHINGS:                                                                                       AIR CONDITIONING SYSTEMS TO BE PROVIDED IN ACCORDANCE WITH AS/NZS 1668.1,
ALL WORKMANSHIP & MATERIALS SHALL BE IN ACCORDANCE WITH THE RELEVANT
                                                                                 FLASHINGS SHALL GENERALLY BE CORROSION RESISTANT, COMPATIBLE WITH THE OTHER                      AS 1668.2 AND AS REQUIRED BY THE NCC.
AUSTRALIAN STANDARDS, NCC CODES OF PRACTICE, EXCEPT AS VARIED BY THE
CONTRACT DOCUMENTS AND OF THE BY-LAWS OF THE RELEVANT LOCAL AUTHORITY            MATERIALS IN THE INSTALLATION, AND COATED WITH A NON-STAINING COMPOUND WHERE                     SOLAR PV SYSTEM:
                                                                                 NECESSARY IN ACCORDANCE WITH AS/NZS 2904.                                                        SOLAR PV SYSTEM TO BE LOCATED ONSITE BY SUPPLIER/INSTALLER (DRAWN LOCATION IS
SURVEY NOTE:
                                                                                 THERMAL INSULATION                                                                               APPROX ONLY).
PROPERTY BOUNDARIES, LOCATION OF EXISTING BUILDINGS, SPOT LEVELS, LOCATION
OF SEWER MAIN & SEWER MANHOLE ARE BASED OFF FEATURE SURVEY COMPLETED BY          SUPPLY & INSTALL THERMAL INSULATION IN ACCORDANCE WITH THE NCC, PART 3.12.1.                     LIGHTING:
EXTERNAL CONSULTANTS. CONTRACTOR SHALL CONFIRM SERVICES LOCATIONS ON                                                                                                              LIGHTING SHALL BE PROVIDED ACCORDANCE WITH THE NCC PART J6 & AS1680
                                                                                 PLUMBING, DRAINAGE & GAS:
SITE PRIOR COMMENCING ANY EXCAVATIONS.                                           DESIGN, SUPPLY, & INSTALL ALL PLUMBING & DRAINAGE IN ACCORDANCE WITH AS3500,                     SWITCHING & POWERPOINTS:
TEMPORARY EROSION CONTROL:                                                       AS3595 PART 6.8 AND THE NCC, PART 3.1.2.                                                         (i) ALL LIGHT SWITCHES LOCATED @1100 ABOVE FL. (TO CENTER) UNLESS OTHERWISE
CONTRACTOR TO PROVIDE ALL NECESSARY EROSION CONTROL MEASURES, SILT               AND LOCAL AUTHORITY REQUIREMENTS.                                                                NOTED & WITH LHA REQUIREMENTS.
BARRIERS, AND THE LIKE DURING CONSTRUCTION IN ACCORDANCE WITH LOCAL              GAS INSTALLATIONS TO BE IN ACCORDANCE WITH AS 5601.                                              (ii) ALL POWER OUTLETS LOCATED 300mm ABOVE FL. (TO CENTER) UNLESS OTHERWISE
AUTHORITY REQUIREMENTS AND AS APPROPRIATE TO CONTROL EROSION ON THE SITE.                                                                                                         NOTED & WITH NCC & LHA REQUIREMENTS.
                                                                                 VENT & WASTE PIPES:
                                                                                                                                                                                  (iv) A/C SWITCH, EXTERNAL GPO AND GPO FOR HOT WATER SYSTEM TO BE
STRUCTURAL ENGINEERING (FOUNDATIONS):                                            CONCEAL ALL VENT PIPES AND WASTE PIPES WITHIN WALL FRAMING UNLESS OTHERWISE
                                                                                                                                                                                  SET AT 600mm FROM FFL.
WORKING DRAWINGS AND DOCUMENTS ARE TO BE READ IN CONJUNCTION WITH THE            NOTED.
                                                                                                                                                                                  (v) EXTERNAL LIGHTS AT WINDOW AND DOOR JOINERY HEIGHT UNLESS NOTED OTHERWISE.
ENGINEERS DRAWINGS AND SPECIFICATIONS. REFER TO ENGINEERING DRAWINGS FOR
                                                                                                                                                                                  SLIGHT VARIATIONS TO HEIGHT MAY BE REQUIRED ON-SITE.
ALL FOOTINGS, SLABS, AND MASONRY DESIGN & DETAILS. SLAB TO HAVE UNDERLAY
                                                                                 FALLS IN FLOORS
WITH 200mm POLYTHENE WATERPROOF MEMBRANE AND PROTRUDE PAST 600mm FOR
                                                                                 FALL WET AREA FLOORS TO FLOOR WASTES. FLOOR WASTE POSITIONS ARE INDICATIVE                       SMOKE ALARMS:
FUTURE FOLD UP SLAB EDGE. CAST ON 50mm SAND BEDDING ON APPROVED FILL.
                                                                                 ONLY. FINAL POSITIONS TO BE DETERMINED BY LOCAL AUTHORITY PLUMBING                               SUPPLY & INSTALL PHOTOELECTRIC SMOKE ALARMS IN ACCORDANCE AS 3786 2014, AS
CONCRETE STRENGTH TO BE 20MPa AT 28 DAYS.
                                                                                 REGULATIONS. FALLS TO FLOORS INSIDE SHOWER AREAS TO BE BETWEEN 1:60 & 1:80.                      1670 2018, WITH PART E2 OF THE NCC 2019 & QLD QFE
STORMWATER:                                                                      PROVIDE A WATERSTOP TO DOORWAYS. FALL ALL EXTERNAL SURFACES AWAY FROM THE
                                                                                                                                                                                  TILING:
STORMWATER SYSTEM TO COMPLY WITH AS3500, PART 3.                                 BUILDING AND/OR TO DRAINAGE OUTLETS UNLESS OTHERWISE NOTED.
                                                                                                                                                                                  TILES TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS SPECIFICATION &
STORMWATER TO BE DISCHARGED SO AS NOT TO CAUSE ERROSION OR NUISANCE TO           PROVIDE SLAB SET-DOWNS, STRUCTURAL FALLS, & BEDDINGS AS REQUIRED.
                                                                                                                                                                                  SHALL BE INSTALLED BY AN APPROVED APPLICATOR. LAYOUT GENERALLY IN ACCORDANCE
ADJOINING PROPERTIES.
                                                                                 WATERPROOFING - WET AREAS                                                                        WITH DRAWINGS UNLESS OTHERWISE NOTED.
ROOFWATER TO DISCHARGE TO COUNCIL APPROVED SYSTEM.
YARD PIT NUMBERS & LOCATION TO BE DETERMINED ONSITE . DRAWING LOCATIONS          WATERPROOFING OF INTERNAL WET AREAS SHALL COMPLY WITH AS3740 AND THE NCC,                        SLIP RESISTANCE:
INDICATIVE ONLY.                                                                 PART 3.8.1. PROVIDE A PROPRIETARY LIQUID OR SHEET MEMBRANE SYSTEM AND FALL TO                    ALL INTERIOR & EXTERIOR FLOOR FINISHES TO COMPLY WITH AS 4586 FOR SLIP
                                                                                 WASTES. PROVIDE WRITTEN WARRANTIES COMMENCING FROM THE DATE OF PRACTICAL                         RESISTANCE INCLUDING STAIRS.
LIGHT STEEL FRAME & STRUCTURAL STEEL (WHERE APPLICABLE):                         COMPLETION.
THE BUILDING FRAMES AND STRUCTURAL STEEL MEMBERS ARE TO BE DESIGNED,                                                                                                              STAIRS, HANDRAILS & BALUSTRADES
SUPPLIED, & INSTALLED BY A SUITABLY QUALIFIED FRAMING CONTRACTOR INCLUDING       WATERPROOFING - WALL OPENINGS                                                                    STAIRS, HANDRAILS AND BALUSTRADES TO BE CONSTRUCTED IN ACCORDANCE WITH THE
BUT NOT LIMITED TO ALL ROOF, WALL, FLOOR, CEILING, POSTS, BEAMS, AND BRACING     INSTALL ALL NECESSARY FLASHINGS, MEMBRANES, DRIPS, STORM MOULDS, CAULKING ETC                    NCC, PARTS 3.9.1 & 3.9.2, INCLUDING AS1170.1 AND AS1288. BALUSTRADES TO HAVE A
MEMBERS. DESIGN IN ACCORDANCE WITH AS3623, DOMESTIC METAL FRAMING                SO THAT WATER IS PREVENTED FROM PENETRATING THE BUILDING BETWEEN FRAMES AND                      MINIMUM HEIGHT OF 1000mm ABOVE FINISHED SURFACE LEVEL UNLESS NOTED
CLASSIFICATION AND THE NCC.                                                      THE BUILDING STRUCTURE. PROVIDE WRITTEN WARRANTIES COMMENCING FROM THE DATE                      OTHERWISE. STAIR BALUSTRADE TO HAVE A MINIMUM HEIGHT OF 865mm ABOVE STAIR
DESIGN AND ENGINEERING TO BE PROVIDED TO CERTIFIER PRIOR TO FRAME INSTALL.       OF PRACTICAL COMPLETION.                                                                         NOSING UNLESS NOTED OTHERWISE. TREADS TO BE 250mm UNLESS OTHERWISE NOTED.
STEEL MEMBERS SHALL MEET THE REQUIREMENTS OF AS 4100 STEEL STRUCTURES,           WINDOW FRAMES & GLAZING                                                                          RISERS TO BE NO MORE THAN 190mm. ENSURE MAX 125mm GAP BETWEEN TREADS
AS/NZS 4600 COLD-FORMED STEEL STRUCTURES. PROVIDE STRUCTURAL                     WINDOW FRAMES AND GLAZING SHALL BE CONSTRUCTED IN ACCORDANCE                                     (PROVIDE NOSING UNDER TREAD AS REQUIRED)
CERTIFICATION AND WARRANTIES AS REQUIRED BY THE CERTIFIER AND PROPRIETOR         WITH AS2047 & AS1288                                                                             INTERNAL DOORS:
RESPECTIVELY.                                                                    WINDOW SIZES SHOWN ARE NOMINAL ONLY                                                              ALL HINGE DOORS TO BATHROOMS & ROOMS WITH WC TO HAVE LIFT OFF HINGES
TIMBER (WHERE APPLICABLE):                                                                                                                                                        WHERE REQUIRED.
                                                                                 INTERIOR LININGS & PLASTERBOARD
TIMBER CONSTRUCTION TO BE IN ACCORDANCE WITH AS 1684 AND THE NCC.
                                                                                 ALL INTERIOR LININGS ARE TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
PARTICLEBOARD FLOORING MATERIAL TO AS/NZS 1860.1.
                                                                                 SPECIFICATIONS, INCLUDING ALL FASTENERS, EXPANSION JOINTS, TRIMS, AND THE LIKE.
FIBRE CEMENT FLOORING COMPRESSED SHEETS TO AS/NZS 2908.2 TYPE A, CAT 5.
                                                                                 PLASTERBOARD SHALL BE INSTALLED IN ACCORDANCE WITH AS 2589 GENERALLY, WET
PLYWOOD FLOORING STANDARD TO AS/NZS 2269.0, BOND TYPE A, TONGUE AND GROOVE
                                                                                 AREA'S TO AS 3740. LININGS TO EXTERNAL BLOCK WALLS SHALL BE INSTALLED ON A
EXTERIOR ROOFING & CLADDING SYSTEMS                                              PROPRIETARY STEEL FURRING CHANNEL SYSTEM - REFER TO DRAWINGS FOR WALL
ALL EXTERIOR ROOFING & CLADDING SYSTEMS ARE TO BE INSTALLED IN ACCORDANCE        DETAILS AND SCHEDULES FOR FINISHES.
WITH THE MANUFACTURER'S SPECIFICATIONS, INCLUDING ALL FASTENERS, EXPANSION
                                                                                 PAINTING
JOINTS, GASKETS, TRIMS, AND THE LIKE. ROOF TO BE BRACED WITH SPEEDBRACE OR
                                                                                 COMPLY WITH THE RECOMMENDATIONS OF AS/NZS 2311.
ANGLE BRACE IN ACCORDANCE WITH TRUSS MANUFACTURERS SPECIFICATIONS.
SHEET METAL ROOFING: TO AS 1562.1. CORROSION PROTECTION TO NCC TABLE 3.5.1.1.A
FIBRE CEMENT CLADDING: TO AS/NZS 2908.2 TYPE A
                                                                                                                                                                                                                                                                        HORNSBY - MODIFIED
                                                                                                               ISSUE                                    PROJECT DESCRIPTION:                                                                    SITE ADDRESS:
                                                                                                                #    DATE          DETAILS         BY   Proposed Dwelling for:                                   GENERAL NOTES                  25 LAWNVILLE ROAD,                    DESIGNED BY   AUSMAR
                                                                                                                -
                                                                                                                A
                                                                                                                    09-05-24
                                                                                                                    13-05-24
                                                                                                                               NHP ISSUE           JS
                                                                                                                               2452 PLD & KIT SINK JS
                                                                                                                                                                                     AUS MAR                                                    COOROY QLD 4563                       DRAWN BY      DPC
                                                                                                                -   24-06-24   WD ISSUE            JS                                                                                                                                 SCALE          JOB CODE
                                                                                                                A   10-07-24   WD ISSUE           DPC
                                                                                                                                                                                 CLIENT:                                                        po box 6384        p (07) 5442 6413
                                                                                                                B   15-07-24   W6 POSITION         JS
                                                                                                                                                                                 CALLAN LEEMAN                                                  maroochydore     f (07) 5450 6437                    D24CAL
                                                                                                                                                                                                                                                qld 4558        QBCC 1083000
                                                                                                                                                                                 & AMY LEEMAN
                                                                                                                                                                                                                                                  WRITTEN DIMENSIONS TO TAKE
                                                                                                                                                                                                                                                   PRECEDENCE OVER SCALE
                                                                                                                                                                                                                                                                                      SHEET         02    OF 23
Log in to download the original file

D24CAL Working Drawings - Issue B.pdf · 4.3 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.