ACOUSTICS & AIR QUALITY
9 Recommendations & Conclusion
A road and rail noise assessment has been conducted for the proposed retirement community
and aged care facility at Trading Post Road, Cooroy. The results and recommendations of the
assessment are as follows:
A noise barrier is proposed for the roadside boundary as shown in Figure 6.1. The
barrier is modelled as 2.0 metres to 3.5 metres high based on the proposed ground
levels provided to ASK. It is noted that the proposed noise barrier is very long and
relatively high for what appears to be a road carrying only minor to moderate traffic
volumes. This is due in part to the strict noise criterion being a quiet area, and the
undulating terrain. It is noted that in the previous ASK noise report for this site, the
barrier height was restricted to 2.1m, resulting in higher noise exposures at dwellings
but accommodating this through more significant acoustic upgrades for the dwellings. It
is likely that any relaxation of the barrier height would require acceptance from TMR and
Council.
To achieve the target noise reductions from external noise to internal noise levels in
MP4.4 will require the construction details are of an appropriate acoustic standard, and
that all external openings to be closed when these habitable rooms are occupied. The
required noise categories for all allotments and aged care home facades are included in
Table D.1, including the effect of the proposed noise barrier. The construction
requirements associated with these noise categories are included in Appendix E.
To achieve the target noise reductions from external noise to internal noise levels in
MP4.4 will require the construction details are of an appropriate acoustic standard, and
that all external openings to be closed when these habitable rooms are occupied.
Therefore, an air-conditioning/mechanical ventilation system that does not degrade the
internal acoustic environment or the sound isolation of the building envelope, and also
meets the ventilation requirements of the Building Code of Australia may need to be
installed.
Compliance with the above recommendations is predicted to result in compliance with relevant
noise criteria.
7617R01V01.docx Page 26
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
J ACOUSTIC REPORT.PDFRelated documentApplication case desk ↗
About this file
- File size
- 7.1 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.