4.2 Townhouse Site An assessment completed of the existing stormwater drainage network to determine if it can convey the additional flow from the Townhouse site and achieve compliance with the QUDM drainage criteria. It was found that with the increase in flows that some of the minor storm (10% AEP) drainage criteria became exceeded. As such, a detention tank is proposed to be installed within the townhouse site to ensure the 10% AEP peak flows are detained back to the development intensity that the drainage system was designed upon. The existing drainage network assumed the contributing catchment of the original development had an imperviousness of 50%. With the Townhouse site increasing the imperviousness of this catchment to 90%, the detention tank has therefore been sized to mitigate flows back to the original design intent. 4.2.1 Catchment The catchment reporting into the existing drainage network is catchment 1/3, which is 0.687 ha, of which 0.506 ha is the townhouse site. An excerpt of the catchment plan from the original design drawing is detailed in Figure 2.3. Figure 2.3: Excerpt of the Catchment Plan from Design Drawing (catchment 1/3) TABLE 4.8: WBNM SUB-CATCHMENT FRACTION IMPERVIOUS VALUES – DEVELOPED SCENARIO WBNM Sub-Catchment Area (ha) Design Impervious (%) Proposed Impervious (%) Townhouse 0.506 50 90 Balance 0.181 50 50 Total 0.687 - - 4.2.1 Results The aim of this assessment is to size a detention tank within the townhouse site to ensure peak flows in the 10% AEP are reduced to be below the existing 10% AEP, from which the drainage network was design (that is going from 50% to 90% impervious). The drainage design flows reporting from Catchment 1/3 are 0.24m3/s in the 10% AEP, which align with estimates from the WBNM model (0.26m3/s). A summary of the storage size and outlet configuration and key details provided below: 73 EUMUNDI - NOOSA ROAD, NOOSAVILLE I BBNE00529_0002_0001-REP-001-1 17
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalLog in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.