QC100259_Pomona Exchange_DD_Rev01-220630
Attached to the e-mail Operational Works Application OP"W22/0174 - DA Form 1 & 2 - Plans - 25 Railway Pde, Pomona.
1 2 3 4 5 6
NOTES (CONT'D): NOTES:
13. EARTH CABLE LUGS SHALL HAVE HEAT SHRINKS TO COVER 1. REFER TO DRAWING 017866P201 SHEET 1
A LUG BARREL EXTENDING OVER CABLE. FOR ADDITIONAL CONNECTION DETAILS. A
14. PROPOSED 35mm² G/Y INSULATED EARTH CABLES INSTALLED 2. ALL EARTH STRAPS TO BE 50 x 3mm HOT
WITHIN SAN COMPOUND AMONG EARTH BARS AND DIPPED GALVANISED MS FLAT AND LAID TO
FENCES/EARTH ELECTRODES SHALL RUN IN FLEXIBLE MINIMUM DEPTH OF 500mm.
GREY CONDUIT TO BE INSTALLED UNDER GEOTEXTILE MAT 3. TELSTRA EXCHANGE SITES WILL HAVE AN
AND 100mm COMPACTED ROAD BASE. EXISTING EARTHING SYSTEM PRESENT.
15. FENCE AND GATE POST CONNECTIONS ARE TO BE TREATED CHECK RECORDS FOR LOCATION. NOTE
WITH DENSO PASTE AND TAPE. THAT THERE MAY BE AN OBSOLETE SYSTEM
16. IF INTERCONNECTION OF SAN GROUND ROD TO TELSTRA IN SITU, TESTING WILL BE REQUIRED TO
GROUND/TOWER STRUCTURE EARTH IS COMPLEX/ ENSURE THAT EARTHING SYSTEM IS IN
TO MAST SEB DIFFICULT THEN TELSTRA EARTHING SHALL BE CONNECTED SERVICE.
DIRECTLY TO THE H FRAME GROUND BAR AS AN 4. SEB/SPC FOR SAN INSTALLATION SHALL BE
B ALTERNATIVE. CONNECTED TO EXISTING SERVICE EARTH B
VIA A BOLTED CONNECTION THAT CAN BE
BROKEN FOR EARTH SYSTEM TESTING. THE
BOND IS TO BE UNDERTAKEN EXTERNAL TO
COMPLIANCE BOX THE BUILDING AND MUST NOT RUN VIA
EQUIPMENT AREAS.
COMPLETED AS PER DESIGN
5. STANDARD ELECTRODES TO BE STAINLESS
ALTERATIONS IN RED STEEL CLAD ROD (S/I 446/16) 1440mm LONG
NAME (PRINT)
AT SPACING OF MINIMUM 2 ELECTRODES
SIGNATURE DATE
DEEP.
6. ALL ELECTRODES ARE TO BE INSTALLED AND
PLACED WITHIN P1/P2 INSPECTION PIT.
C 7. 19/1.53mm GREEN AND YELLOW COPPER C
UNISTRUT CABLE PATHS (2 OFF)
SHALL BE BONDED TO ANTENNA CABLE SHALL RUN FROM THE PROPOSED
SEB/SPC SHALL BE SEB/SPC FOR SAN INSTALL, TERMINATE AT
MAST EARTH BAR IN A PIGGY
MOUNTED AT LOWER
BACK ORIENTATION
LEGEND ELECTRODE AND CONTINUE TO EXISTING
LEVEL ON H-FRAME VIA SERVICE EARTH SYSTEM.
INSULATORS PROPOSED INSTALL 35mm² G/Y EARTH STRAP 8. REFER TO EARTHING GUIDELINES SHEET
EARTH CABLE IN CONDUIT. 35mm² G/Y INSULATED CABLE (19/1.53). G4-2 AND G4-3.
FENCE CONNECTION. ALSO REFER TO NOTE 16. 9. ALL CONNECTIONS TO EARTH ELECTRODES
REFER NOTE 11 EARTH INSPECTION PIT AND JOINTS ARE TO BE TREATED WITH
DENSO PASTE AND TAPE.
SITE FENCING 10. WHERE ELECTRODES CAN NOT BE DRIVEN
D EARTH ELECTRODE OR EARTH RESISTIVITY IS HIGH, DRILLING D
MAY BE REQUIRED. PRE-DRILLED HOLES
SERVICE EARTH BAR SEB SHALL BE BACK FILLED WITH EARTH
ENHANCING COMPOUND (E.G CALCIUM
BENTONITE AND GYPSUM SLURRY)
11. ALL FOUR FENCE CORNER POSTS SHALL BE
EARTH ELECTRODE SCHEDULE CONNECTED TO THE SAN EARTH.
35mm² G/Y CABLE IN 12. CABLES AND/OR CONNECTIONS FROM
TYPE DIAMETER QUANTITY DEPTH EXISTING TELSTRA EARTHING SYSTEM SHALL
FLEXIBLE GREY CONDUIT.
STAINLESS STEEL CLAD BE LABELLED IN RESPECTIVE EARTH PITS TO
REFER TO NOTE 14 14mm 2 2.88m
ROD IDENTIFY CONNECTION TO SAN EARTH.
EARTH GRID SCHEDULE ALL OTHER EARTH CABLES THAT CANNOT BE
E VISUALLY TRACED FROM SEB TO E
TYPE DIMENSIONS DESTINATION MUST ALSO BE LABELLED.
HOT DIPPED GALVANISED MS FLAT 50 x 3mm
NOTE: THIS DRAWING TO BE READ IN CONJUNCTION WITH SHEET G4-1
FOR CONSTRUCTION
ORDER DRAWN CHKD AMENDMENT EXAM APPD DATE ISS
183929 JM MF FOR CONSTRUCTION - SP30092467WO015DOWN - SATELLITE RC PG 17.06.22 0.1
PLAN VIEW SATELLITE ACCESS NODE SITE 183929
SCALE 1:25 POMONA EXCHANGE
F SITE EARTHING F
25 RAILWAY PARADE, POMONA, QLD 4568
DWG SHT G4
C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved. NO. QC100259 NO. .
1 2 3 4 5 Cad file: QC100259.dwg A3