4.0 LOCAL HAZARD MAP
4.1 GENERAL
The SPP reference documentation sets out the following methodology for preparing a Local
Hazard Area Map:
• Categorising the vegetation within the site in accordance with the vegetation hazard classes
derived from QFES (2019)
• Using the patch and corridor filtering process to remove narrow corridors and small patches
of hazardous vegetation
• Subdividing the identified vegetation hazard classes into bushfire hazard sub-units based on
slope differences and vegetation hazard classes
• Assigning SPP Potential Bushfire Intensity classes to the sub-units
• Application of 100m Potential Impact Buffers to the amended sub-units to derive an overall
Local Hazard Map.
4.2 PATCH AND CORRIDOR FILTERING
Section 4.2.6 of Bushfire Resilient Communities (QFES (2019) outlines the patch and corridor
filtering process to modify potential intensity of small patches and corridors (based on Leonard et.
al. 2017). The process involves the following three stages:
• Merging small patches of a single Vegetation Hazard Class less than 0.5 ha;
• Merging small Vegetation Hazard Class patches between 0.5 and 1 ha with higher or moderate
fuel loads (greater than 8 tonnes/ha); and
• Removing narrow corridors of vegetation less than 50m wide through a process of patch
erosion and dilation. These small patches are merged with surrounding vegetation by
allocating a patch to the Vegetation Hazard Class that is most common to the patch boundary
(Leonard et al., 2017).
4.3 CALCULATION OF POTENTIAL BUSHFIRE INTENSITY
Potential Bushfire Intensity is calculated by inputting the site-specific input parameters discussed
in Section 3.1 into the FLAMESOL computer model. FLAMESOL uses industry standard bushfire
equations and allows numerous input variables to be adjusted including fuel loads, fire danger
index, site slope and distance to vegetation.
The table below details the Potential Bushfire Intensity classes and their corresponding potential
fire-line intensity (KW/m) values as prescribed within Leonard et. al. 2017.
POTENTIAL BUSHFIRE INTENSITY POTENTIAL FIRELINE INTENSITY
Very High >40,000 kW/m
High 20,000-39,999 kW/m
Medium 4,000 – 19,999 kW/m
5 April 2022 Mr Kim Carroll and Mrs Heidi Meyer Page: 10
Job No. 21-046 Bushfire Hazard Assessment – 41 Picture Point Crescent, Noosa Heads
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Bushfire Hazard Assessment - 41 Picture Point Cres Carroll and Meyer.pdfRelated documentApplication case desk ↗
About this file
- File size
- 8.9 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.