Electrical AC1286 Preliminary Design Sub 2 Pearsons Road, Cooroy 4563 [20-08-2021]
Original PDF page 1, section 1. The text section number identifies this passage in the reader.
SURVEY DETAILS
203 AS/NZS 3000:2018 STREET LIGHTING CERTIFICATE LEGEND
3.11.5 Spacing from other underground services PRINCIPAL'S SURVEYOR TO PEG ALL BOUNDARIES PRIOR TO
CONSTRUCTION AND AFTER CONSTRUCTION TO PROVE ACCURACY SYMBOL DESCRIPTION
ROAD AND PUBLIC SPACE LIGHTING IS CERTIFIED
TO COMPLY WITH THE NOMINATED CATEGORIES OF OF ASSET INSTALLATION.
All underground wiring systems shall be spacing not less than 100 mm from 1 STATION NUMBER
other underground services. AS/NZS 1158.1.1:2005 AND AS/NZS 1158.3.1:2020.
CONSTRUCTION NOTES EXISTING OH CONDUCTOR
BLUE WREN PLACE - PR5 PROPOSED OH CONDUCTOR
Wiring systems shall be suitably marked with warning tape in accordance 1. CONTRACTOR TO INCLUDED PROVISIONAL SUM FOR VACUUM HV and LV POLE
with Clause 3.11.4.5 and maintain a separation from telecommunications, THE DESIGN ASSUMES MAINTENANCE FACTORS OF EXCAVATION AS U.G. SERVICES HAVE BEEN IDENTIFIED IN THE POLE TRANSFORMER
gas and water services in accordance with Table 3.7. 0.7 FOR MINOR ROAD LIGHTING, 0.75 FOR MAJOR VICINITY.
HV AIR BREAK OPEN
ROAD LIGHTING, 0.75 FOR LED LIGHTING, BASED ON 2. CONTRACTOR INCLUDE PROVISIONAL SUM FOR 'CUT AND
THE FOLLOWING SCHEDULE. REINSTATE' CONCRETE FOOTPATH, FULL PANEL AND FILL HV AIR BREAK CLOSED
Further requirements for the separation of telecommunications, gas and
WIDTH AT STATION 5 TO TRANSFER EXISTING CROSSROAD LV DISC LINK OPEN
water systems from low voltage wiring systems are provided in
1. LAMPS ARE TO BE REPLACED AT 36 MONTH CONDUIT TO EXISTING SPARE LV CONDUIT FROM STATION 4 LV DISC LINK CLOSED
Clause 3.9.8.4. INTERVALS, AT WHICH TIME LUMINAIRES ARE TO AND AT STATION 2 TO INSTALL LV CONDUIT/TERMINATION FROM HV POLE TERMINATION
TABLE 3.7 BE INSPECTED, CLEANED AND MAINTAINED. POLE AT STATION 1.
LV POLE TERMINATION
2. VEGETATION IS TO BE KEPT CLEAR OF STREET 3. TRAFFIC CONTROL REQUIRED.
PRELIMINARY ISSUE
MINIMUM SEPARATION OF UNDERGROUND SERVICES GROUND STAY
LIGHTS.
3. INSPECTION PATROLS AND SPOT LAMP EXISTING UG CABLE
Minimum separation to low Minimum separation REPLACEMENT SHALL MAINTAIN SERVICE
CONSTRUCTION NOTES - PRIVATE PROPERTY PROPOSED UG CABLE
voltage electrical service of conductive THE CLIENT'S ELECTRICAL CONTRACTOR WILL BE RESPONSIBLE
AVAILABILITY AT NOT LESS THAN 95%.
NOT FOR CONSTRUCTION
EXISTING SUPPLY PILLAR
identified in accordance with enclosures to low FOR THE FOLLOWING:
4. LUMINAIRES AND LAMPS SHALL BE REPLACED PROPOSED SUPPLY PILLAR
Type of service Clause 3.11.4.5 and mechanically voltage electrical · INSTALL CONDUITS THE FULL LENGTH OF THE ACCESS
WITH EXACT EQUIVALENTS.
protected (1) earthing electrode (1) CORRIDOR OR SUPERVISE INSTALLATION BY OTHERS. LINK PILLAR
· REMOVE REDUNDANT ELECTRICAL WIRING. PADMOUNTED TRANSFORMER
mm mm
EXISTING CABLE IN CONDUIT
Water service not ELECTRICITY CONNECTION PROCESS PROPOSED CABLE IN CONDUIT
100 500
greater than DN65 (2)
MEN (EARTH GROUND STAKE)
1. DEVELOPER'S REPRESENTATIVE SUBMITS CERTIFICATE OF
Water service greater
300 500 RESIDENTIAL AND ELECTRICITY SUPPLY TO COUNCIL. E ELECTRICAL CABLE MARKER
than DN65 (2) CUSTOMER SWITCHBOARD
COMMERCIAL / INDUSTRIAL 2. DEVELOPER'S REPRESENTATIVE SUBMITS PLANS TO THE
Sanitary drainage 100 500 TITLES OFFICE. PIT
SUBDIVISIONS 3. ENERGEX ESTABLISHES A NATIONAL METER IDENTIFIER (NMI).
Stormwater drainage S70 STREET LIGHT
100 600 4. NEW CUSTOMER REFERENCES NMI AND MAKES AN
ONLY ENERGEX APPROVED MATERIALS, S250 STREET LIGHT
Gas 100 500 APPLICATION WITH THEIR ELECTRICITY RETAILER.
INSTALLATION EQUIPMENT, AND 5. ELECTRICAL CONTRACTOR REFERENCES NMI AND SUBMITS LED STREET LIGHT
Telecommunications 100 INSTALLATION TECHNIQUES SHALL BE THE APPLICATION WITH ENERGEX. TREE
USED DURING CONSTRUCTION. 6. ENERGEX MAKES CONNECTION.
NOTES: LV SWITCH FUSE UNIT
1 Authorities, such as water and as suppliers and electricity distributors, may
require their services to be spaced at a greater distance from underground wiring
systems. Also see Figure 3.10.
2 DN = internal diameter of pipe.
GENERAL NOTES
1. ALL CABLES TO BE INSTALLED IN CONDUIT WITHIN THE
STANDARD ELECTRICITY ALIGNMENT OF 250-900mm FROM
PROPERTY BOUNDARY.
2. CONSTRUCTION PERSONNEL SHALL MEASURE ACTUAL
CABLE LENGTHS REQUIRED ON SITE AFTER INSTALLATION
OF CONDUITS THEN NOTIFY SUPPLIER WHEN CONFIRMING
CABLE ORDER.
3. ALL BENDS INSTALLED ON 125mm RETICULATION
CONDUITS MUST BE 1830mm RADIUS UNLESS OTHERWISE
SPECIFIED.
AD
4. CONTRACTOR TO SUPPLY ALL LABELS AND SITE ID
WORK SITE
RO
NUMBERS TO ENERGEX SPECIFICATION.
ELM
5. DEVELOPERS CIVIL CONTRACTOR TO SUPPLY AND
NS
INSTALL CONDUITS AS SHOWN IN CIVIL WORK SCHEDULE.
SO
STR
6. INSTALL ELECTRICAL CONDUIT AND
CARRU
THERS TELECOMMUNICATIONS PIT AND PIPE IN JOINT USE
AR
C OURT TRENCH - REFER PROJECT NUMBER AC1286-T
EET
PE
STANDARDS AND SPECIFICATIONS
Lot Lot Lot Lot THIS WORKS PLAN IS TO BE READ IN CONJUNCTION AND
11 12 Lot
13 COMPLY WITH THE FOLLOWING ENERGEX MANUALS AND
D
14 15
OA
Lot Lot 100 SPECIFICATIONS:
10 - UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
R
Lot BLUE W Park
- OVERHEAD CONSTRUCTION MANUAL
Lot
9 R EN PLA NS
16 Lot CE - PUBLIC LIGHTING MANUAL
SO
8 Lot Lot Proposed - NETWORK LABELLING AND SIGNAGE MANUAL
7 Lot Lot Proposed Proposed
AR
6 5 Lot Lot Lot 11 Lot 12
4 Lot Lot 13 Proposed FOR DETAILS OF ADDITIONAL TRENCH CROSS-SECTIONS,
3 2 Proposed
PE
1 Lot 14 REFER TO ENERGEX UNDERGROUND DISTRIBUTION
Lot 15
CONSTRUCTION MANUAL.
Proposed Proposed
Lot 10 Lot 100
CE
Park
SPOTT UG SERVICES INFORMATION
ED GUM
A
COURT Proposed BLUE W
RT
REN PL
Lot 9 REN PL UNDERGROUND SERVICES SHOWN ON THIS WORKS PLAN
Proposed A CE
COU
Lot 16 IN THE VICINITY OF PROPOSED EXCAVATION WORKS ARE
Proposed INDICATIVE ONLY.
Lot 8
BLUE W
Proposed
OAK
ELM S
Lot 7 Proposed CONSTRUCTION PERSONNEL SHALL REQUEST ON-SITE
Lot 6 Proposed IDENTIFICATION AND LOCATION OF EXISTING BURIED
Lot 5 Proposed
SERVICES FROM THE QUEENSLAND DIAL BEFORE YOU DIG
EST
Lot 4 Proposed
Lot 3 Proposed SERVICE. PH:1100 FAX:1300 652 077 (A MINIMUM OF TWO DAYS
TREE
Lot 2 Proposed
NOTICE IS REQUIRED)
FOR
Lot 1
REFER JOB No: 21623980.
T
BLU
E W
REN P CONDUIT CROSS SECTION - FOOTPATH & ROADWAY
L
TR EET
GEM S SURVEY PLAN 600 FOOTPATH
SCALE 1:1000 750 MINOR ROAD
1200 MAJOR ROAD
LOCALITY MAP
SCALE 1:2000 DETAIL O DETAIL D DETAIL P DETAIL E
600 FOOTPATH
750 MINOR ROAD
1200 MAJOR ROAD
c c c
DETAIL H DETAIL N DETAIL Z
NOTE: 5mm PROTECTION COVER STRIP REQUIRED WHEN NOT IN ALLOCATED ENERGEX UG ALIGNMENT
ISSUE DESCRIPTION DATE AUSPOWER CONNECT IS THE FIRST POINT OF DEVELOPER DETAILS ALIGNMENTS WORKS COORDINATOR - APPROVED: SUBDIVISION AUSPOWER CONNECT
AC1286
P PRELIMINARY DESIGN 20/08/2021 CONTACT FOR CONSTRUCTION ENQUIRIES. Auspower Connect Pty Ltd Ventralia Pty Ltd ENERGEX OH 3.0m PARENT PROJECT NO. - RECONFIGURE 1 LOT INTO 16 LOTS PROJECT NO.
Darren Matthews ENERGEX UG 0 - 0.9m WORK REQUEST NO. - RAL 20/0021 SCALE: 1:2000 & 1:1000
PO Box 531
0499 339 155 STREETLIGHTS 0.7m I.O.K LOTS 1-16 ENERGEX PROJECT NO.
Buddina, QLD 4575 ELECTRICAL RETICULATION
[email protected] NBN REFER DBYD
Mob 0419 707 166 INSTALL 9 PILLARS, 441m OF 240 AL 4C UG LV CABLE
[email protected]
PROJECT MANAGER DETAILS GAS - CANCELLING LOTS 3 on RP113733 APPROVED DATE: N/A AND 5 STREET LIGHTING COLUMNS S4400244
Ventralia Pty Ltd HP GAS - D.A RAL 20/0021 CHECKED: J McKenna
ABN 74 166 366 883
Darren Matthews WATER REFER DBYD LOCAL AUTHORITY Noosa Council DESIGNER: I Lubacheski
This drawing is the property of Auspower Connect Pty Ltd and 2 PEARSONS ROAD
0499 339 155 STORMWATER REFER DBYD UBD REF Map 5 A-20 PHONE: 0419 707 166
must not be used, retained or copied without written permission
COOROY 4563 ISSUE NO. P SHEET 1 OF 5 A1
[email protected] SEWER REFER DBYD PEGGED On Request ISSUE DATE: 20/08/2021
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalSearchable page text hides email addresses. Original files are unchanged and may show email addresses.
Full text of the other 5 sections
Section 2
PILLARS OFFSET FOR LOTS 6 & 7 PILLARS OFFSET FOR LOTS 3 & 7
OFFSET PILLAR BASE (SHORTER SIDE) TO ALIGN IF CLEARANCE (STN11 & 18) TO DRIVEWAY IS
WITH CENTRE LINE OF SURVEY PEG (STN 8 & 11) LESS THAN 1m INSTALL PROTECTIVE BOLLARDS
24
75 (HV)
0
)
24 AL
(LV
71
0 A 3C
3-
Lot 12
4-7 /3.75
L 3 (H
6/4
C ( V)
.75
/4.
HV
240 AL 3C (HV)
RP881300 Lot 11
3 -7
)
77 .60
+7
D
RP881300 Lot 10
/1
OA
RP881300
36
Lot 9
SR
(H
V)
RP881300
N
Lot 1
52
SO
Proposed Proposed
) RP113733
(SL Lot 12
AR
Lot 11 Proposed
u 2C
16 C #6 Bɸ Cɸ Lot 13
240 AL 4C (LV
PE
Aɸ
Proposed
24
4 C AL 4
P42655 Lot 14
0
3-7/3.75 (HV)
240 AL 4C (LV)
u2 C(
4-7/4.75 (LV) Bɸ
C LV
P87352
1-9
(S )
16 3.5m 13 Proposed
L)
)
5AB 8
W
W
U2251866 Lot 15
Lot 2 Proposed Cɸ
C4
14
1
RP113733 Lot 10
U2251865 12
C (L
Aɸ 12 14 U2251868 Proposed
#4 240 AL
V)
4C (LV) W
W
16 Lot 100
13L
15
P63902 Park
W
P2251872 31
4-7/4.75
2B2 7
W
W
5 (S
11 U2251864
51
H
1
9L P2251871
ER)
(LV)
Proposed 11B 9 13
H
2.5
56
W
Lot 9 8 38 17L P2251873
240 AL 3C (H
m
V) Cɸ it 13 BLUE W
Existing nd
u 10 W W
R EN PLA
Co 11A U2251863
W
1.9m 24 CE
2x
Dwelling m 8 U2251862
Proposed
C (LV)
m 9
80
80 15 19L P2251874
V)
Lot 16 17 W
W
24
m
5.5m
4C (L
29
240 AL 4 (SL)
U2251867
m
C (LV)
Aɸ
240 AL 4
Co
18
C (LV)
Proposed
4 Cu 2C
W W
nd
L
240 A
Proposed 19
uit
Lot 8 U2251869 5.6m
80
240 AL 4 (SL)
C (LV)
11C Lot 7
mm
Bɸ
19
240 AL 4
P2166157 Aɸ
4 Cu 2C
Co
)
Proposed (LV
nd
P90208 4C
u
Lot 44 Lot 6 L 20L P2251875
it
Proposed
Cɸ 4 0A 20
SP305293 Lot 43 Lot 5 Proposed 2
Bɸ Proposed
Lot 4 Proposed
#22 SP305293 Lot 1
Aɸ Proposed
Lot 3 Aɸ
#20 Lot 2
Lot 42 Cɸ 4 Cu 2C
Bɸ 240 AL 4 (SL)
3-7/4.75 (H
4-7/4.75 (L
SP305293 Lot 41
67
C (LV)
240 AL
24
#18 SP305293 4C (LV
43
Lot 40 )
Normally Open
#16 SP305293 Lot 39 LP2251870 21 CAUTION - STN 21
)
V)
(LV
V)
1m
Lot 45 #14 Lot 38
SP305293
4C
SP305293 SP305293 Lot 37
240 AL 4C (L
V)
W H
HANDSINK
C (LV)
C
Cu
240 AL 4 LV)
(SL)
#23 Lot 36
10
SP305293
16
Lot 33
C(
FULL DEPTH & FULL WIDTH MAJOR
4 Cu 2C
SP305293 Lot 35
16 Cu 4
U1420224 SP305293 4 Cu 2C (SL) 22 P1420245 PLANT IN VICINITY
SP90209 240 AL SP305293 240 AL 4C (L
4C (LV) 28 V) 450mm MIN & FULL WIDTH
200kVA U1420225 C
14
A
10
U1420223 U1420228 6 TO LOCATE U/G WATER MAIN
P1420241
SPOTT U1420229
ED GUM 16 4 Cu 2C (SL) 23 U1420236
COURT
15
Lot 46 240 AL 6 7 240 AL 4C (L
4C (LV) V) C
240 AL U1420231 ARRANGE FOR LOCATIONS PRIOR TO ANY
SP305293 ) P1420239 4C (LV) Lot 34
LV 26
17
EXCAVATIONS
14
( 36
#21 4C U1420233
SP305293
AL 16 Cu 4
C (LV)
C
0 4 U1420226
24
3-7/4.75 (H
3
4-7/4.75 (L
C
13
ELM ST
P2166156 18
U1420222 P1420240 16 Cu 4
U1420227 5 18 C (LV)
42
13
240 AL 4 Section 3
(LV)
U2142030
C (LV)
36
240 AL 4 (LV)
C (LV)
CONTRACTOR TO 'CUT & SPOTT P1420243
C
46 Lot 47
C
V)
E
V)
D GUM
C
REET
REINSTATE' CONCRETE
COURT
240 AL 4
C
SP305293 P1420242
C
C
240 AL 4
Lot 48 FOOTPATH AT STATION 5 46 C 240 A
18
L 4C (L
V)
CAUTION - STN 1-2 #19 TO TRANSFER EXISTING U1420232
240 AL 4 (SL)
CONTRACTOR TO 'CUT &
C (LV)
SP305293
(LV)
24 0 A C (
REINSTATE' CONCRETE CROSSROAD CONDUIT TO
C
24 Cu 2
#17
0 A L 4 SL
C (LV)
4 Cu 2C
SPARE LV CONDUIT FROM
4
C
FOOTPATH BETWEEN
HANDSINK
L4 C( )
240 AL 4
STATIONS 1 & 2 TO INSTALL P90210 1 STATION 4 U1420234
C LV
240 AL 4
LV CONDUIT/TERMINATION 2 U1420221 Lot 49 Lot 56
(L )
C (LV)
V)
FULL DEPTH & FULL WIDTH MAJOR FROM POLE AT STATION 1
A Lot 50 P1420244
SP305293 SP305293
PLANT IN VICINITY
CAUTION SP305293 Lot 51
240 AL 4
450mm MIN & FULL WIDTH #15
LIVE UG CABLES #13 SP305293 Lot 52
TO LOCATE U/G TELSTRA/NBN SERVICE
CAUTION Lot 3 STATIONS 2 TO 7 #11 SP305293 Lot 53
C 240 A
31
TO LOCATE U/G WATER MAIN Lot 54 L 4C (L
SP305293 V)
TO LOCATE U/G STORM WATER PIPE LIVE OVERHEAD RP206856
SP305293 Lot 55
ACE
Lot 4
CABLES STATION 1 #156 Lot 57
ARRANGE FOR LOCATIONS PRIOR TO ANY RP206856 #5 SP305293
EXCAVATIONS SP305293
REN PL
#154 #3
Lot 5 #23
3-7/4.
4-7/4.
RP206856
53
75 (HV
75 (LV
#152
BLUE W
P2166155
)
)
U1420235
SITE PLAN
PRELIMINARY ISSUE 10 0 10 20 30 40 50 METRES
NOT FOR CONSTRUCTION
SCALE 1:500 AT A1
ISSUE DESCRIPTION DATE AUSPOWER CONNECT IS THE FIRST POINT OF DEVELOPER DETAILS ALIGNMENTS WORKS COORDINATOR - APPROVED: SUBDIVISION AUSPOWER CONNECT
AC1286
P PRELIMINARY DESIGN 20/08/2021 CONTACT FOR CONSTRUCTION ENQUIRIES. Auspower Connect Pty Ltd Ventralia Pty Ltd ENERGEX OH 3.0m PARENT PROJECT NO. - RECONFIGURE 1 LOT INTO 16 LOTS PROJECT NO.
Darren Matthews ENERGEX UG 0 - 0.9m WORK REQUEST NO. - RAL 20/0021 SCALE: 1:500
PO Box 531
0499 339 155 STREETLIGHTS 0.7m I.O.K LOTS 1-16 ENERGEX PROJECT NO.
Buddina, QLD 4575 ELECTRICAL RETICULATION
[email protected] NBN REFER DBYD
Mob 0419 707 166 INSTALL 9 PILLARS, 441m OF 240 AL 4C UG LV CABLE
[email protected]
PROJECT MANAGER DETAILS GAS - CANCELLING LOTS 3 on RP113733 APPROVED DATE: N/A AND 5 STREET LIGHTING COLUMNS S4400244
Ventralia Pty Ltd HP GAS - D.A RAL 20/0021 CHECKED: J McKenna
ABN 74 166 366 883
Darren Matthews WATER REFER DBYD LOCAL AUTHORITY Noosa Council DESIGNER: I Lubacheski
This drawing is the property of Auspower Connect Pty Ltd and 2 PEARSONS ROAD
0499 339 155 STORMWATER REFER DBYD UBD REF Map 5 A-20 PHONE: 0419 707 166
must not be used, retained or copied without written permission
COOROY 4563 ISSUE NO. P SHEET 2 OF 5 A1
[email protected] SEWER REFER DBYD PEGGED On Request ISSUE DATE: 20/08/2021
Section 4
PRELIMINARY ISSUE
NOT FOR CONSTRUCTION
ISSUE DESCRIPTION DATE AUSPOWER CONNECT IS THE FIRST POINT OF DEVELOPER DETAILS ALIGNMENTS WORKS COORDINATOR - APPROVED: SUBDIVISION AUSPOWER CONNECT
AC1286
P PRELIMINARY DESIGN 20/08/2021 CONTACT FOR CONSTRUCTION ENQUIRIES. Auspower Connect Pty Ltd Ventralia Pty Ltd ENERGEX OH 3.0m PARENT PROJECT NO. - RECONFIGURE 1 LOT INTO 16 LOTS PROJECT NO.
Darren Matthews ENERGEX UG 0 - 0.9m WORK REQUEST NO. - RAL 20/0021 SCALE: NOT APPLICABLE
PO Box 531
0499 339 155 STREETLIGHTS 0.7m I.O.K LOTS 1-16 ENERGEX PROJECT NO.
Buddina, QLD 4575 ELECTRICAL RETICULATION
[email protected] NBN REFER DBYD
Mob 0419 707 166 INSTALL 8 PILLARS, 401m OF 240AL 4C UG LV CABLE
[email protected]
PROJECT MANAGER DETAILS GAS - CANCELLING LOTS 3 on RP113733 APPROVED DATE: N/A AND 5 STREET LIGHTING COLUMNS S4400244
Ventralia Pty Ltd HP GAS - D.A RAL 20/0021 CHECKED: J McKenna
ABN 74 166 366 883
Darren Matthews WATER REFER DBYD LOCAL AUTHORITY Noosa Council DESIGNER: I Lubacheski
This drawing is the property of Auspower Connect Pty Ltd and 2 PEARSONS ROAD
0499 339 155 STORMWATER REFER DBYD UBD REF Map 5 A-20 PHONE: 0419 707 166
must not be used, retained or copied without written permission
COOROY 4563 ISSUE NO. P SHEET 3 OF 5 A1
[email protected] SEWER REFER DBYD PEGGED On Request ISSUE DATE: 20/08/2021
Section 5
COMMISSIONING PLAN
SIMPLE LV SWITCHING SHEET
AD
1. P87352 - CHECK OPEN
2. P90211 - CHECK OPEN
RO
P87352
Normally 3. LP1420235 - CHECK OPEN
NS
Open 4. SP90209 - OPEN LV ISOLATORS
5. UNDERTAKE WORK
SO
6. REVERSE SWITCHING
AR
PE CIRCUIT LABEL LABEL LETTER
LABEL INFORMATION
No. SIZE COLOUR SIZE
EX 4-7/4.75 (LV)
P90208 TO ELM ST P90210/
1 150 X 50 WB 5 BLUE WREN PL LP1420235
& SERVICES
EX 16 Cu 4C (LV)
150 X 50 5
TO ELM ST P90210
2 WB
& SERVICES
U1420224
SP90209
200kVA U1420225
U1420228 6 EX 16 Cu 4C (LV) LABEL AT STATION 21 - LP2251870 BLUE WREN PLACE
U1420223 EX 16 Cu 4C (LV)
U1420229 24 U1420236 LINK PILLAR
EX 240 AL 4C (LV)
ELM ST
U1420231
EX 240 AL 4C (LV) U1420233
4 U1420226 EX 240 AL 4C (LV)
3 U1420222
5 SPOTT
REET
E D GUM
ACE
AD
EX 240 AL 4C (LV)
U1420227 U2142030
U1420232
CT
RO
P87352
REN PL
EX 240 AL 4C (LV) Normally
S
P90210 1 U1420234 Open
2 U1420221
ON
IN 16 Cu 4C (LV)
S
AR
BLUE W
EX 4-7/4.75 (LV)
EX 240 AL 4C (LV) U2251865 12 14 U2251866
PE
U2251868 17
25 U2251864 11 IN 16mm² Cu 4C (LV)
EXISTING LP1420235 IN 240 AL 4C (LV) 8 U2251862 BLUE W
Normally
U2251863 10 REN PL
LV SCHEMATIC Open
16 U2251867
ACE
HWAY
NOT TO SCALE U2251869 19
P90211
Normally P90208 IN 240 AL 4C (LV)
EX 4-7/4.75 (LV)
Open 21 LP2251870
H PAT
Normally
IN 240 AL 4C (LV)
Open
EX 16 Cu 4C (LV)
NORT
IN 240 AL 4C (LV)
U1420224
SP90209 EX 16 Cu 4C (LV)
200kVA U1420228 6
U1420223 U1420225 EX 16 Cu 4C (LV)
U1420229 24 U1420236
EX 240 AL 4C (LV) IN 240 AL 4C (LV)
ELM ST
U1420231
IN 240 AL 4C (LV) REC 240 AL 4C (LV) U1420233
SITE LOCATION FOR 4 U1420226 EX 240 AL 4C (LV)
LABEL SIZE LABEL INFORMATION 3 U1420222
ATTACHING OF LABEL
5 SPOTT
REET
ED GUM
ACE
LV CABLE EX 240 AL 4C (LV)
300 X 100 POLE No. P90210
U1420227 U2142030
U1420232
CT
LOCATION ELM STREET TO BLUE WREN PL (NORTH) LP2251870/
REN PL
BLUE WREN PL (SOUTH) LP1420235 EX 240 AL 4C (LV)
P90210 1 U1420234
2 U1420221
& SERVICES
LV CABLE
BLUE W
300 X 100 POLE No. P90210 EX 4-7/4.75 (LV)
TO SPOTTED GUM CT U1420228 DIRECT/ EX 240 AL 4C (LV)
LOCATION ELM STREET
BLUE WREN PL LP2251870
& SERVICES 25
LABEL AT STATION 1 - P90210 ELM STREET PROPOSED LP1420235
Normally
LV POLE TERMINATIONS LV SCHEMATIC Open
LABELS TO BE MADE FROM KOLANA BRONZE 1.6mm THICK ANODISED ALUMINIUM PLATE NOT TO SCALE
P90211
REFER - NETWORK LABELLING & SIGNAGE MANUAL, DRAWING NO. 6448-A4 REV. C Normally
Open
CIRCUIT LABEL LABEL LETTER
LABEL INFORMATION
No. SIZE COLOUR SIZE
TO ELM ST P90210/
1 150 X 50 WB 5 BLUE WREN PL LP2251870
& SERVICES
TO LAKE MCDONALD DR SP15247/
2 150 X 50 WB 5 FOREST OAK CT U1325244/
PRELIMINARY ISSUE MARBLE WOOD CT U1325247 & SERVICES
LABEL AT STATION 25 - LP1420235 BLUE WREN PLACE
NOT FOR CONSTRUCTION LINK PILLAR
ISSUE DESCRIPTION DATE AUSPOWER CONNECT IS THE FIRST POINT OF DEVELOPER DETAILS ALIGNMENTS WORKS COORDINATOR - APPROVED: SUBDIVISION AUSPOWER CONNECT
AC1286
P PRELIMINARY DESIGN 20/08/2021 CONTACT FOR CONSTRUCTION ENQUIRIES. Auspower Connect Pty Ltd Ventralia Pty Ltd ENERGEX OH 3.0m PARENT PROJECT NO. - RECONFIGURE 1 LOT INTO 16 LOTS PROJECT NO.
Darren Matthews ENERGEX UG 0 - 0.9m WORK REQUEST NO. - RAL 20/0021 SCALE: NOT TO SCALE
PO Box 531
0499 339 155 STREETLIGHTS 0.7m I.O.K LOTS 1-16 ENERGEX PROJECT NO.
Buddina, QLD 4575 ELECTRICAL RETICULATION
[email protected] NBN REFER DBYD
Mob 0419 707 166 INSTALL 8 PILLARS, 401m OF 240AL 4C UG LV CABLE
[email protected]
PROJECT MANAGER DETAILS GAS - CANCELLING LOTS 3 on RP113733 APPROVED DATE: N/A AND 5 STREET LIGHTING COLUMNS S4400244
Ventralia Pty Ltd HP GAS - D.A RAL 20/0021 CHECKED: J McKenna
ABN 74 166 366 883
Darren Matthews WATER REFER DBYD LOCAL AUTHORITY Noosa Council DESIGNER: I Lubacheski
This drawing is the property of Auspower Connect Pty Ltd and 2 PEARSONS ROAD
0499 339 155 STORMWATER REFER DBYD UBD REF Map 5 A-20 PHONE: 0419 707 166
must not be used, retained or copied without written permission
COOROY 4563 ISSUE NO. P SHEET 4 OF 5 A1
[email protected] SEWER REFER DBYD PEGGED On Request ISSUE DATE: 20/08/2021
Section 6
PRELIMINARY ISSUE
NOT FOR CONSTRUCTION
0.14 Lux
0.14 Lux
13L CATEGORY PR5
0.14 Lux
P2251872
BLUE WREN PLACE
9L P2251871
17L P2251873
BLUE W P Category Lighting - AS/NZS 1158.3.1:2005
REN PL ******************************************
ACE
19L P2251874
0.14 Lux Auspower Connect
----------------
0.14 Lux I-table Filename: C:\Users\Auspower\Desktop\Modular LED 15W 4K 17032
0.14 Lux
6PHM.CIE
Job Name: AC1286 - 2 PEARSONS ROAD COOROY
20L P2251875
Luminaire Description: Modular LED 15W 4K 170326PHM use 1899lms
Initial Lamp Flux: 1899 lms
Maintenance Factor: 0.75
Stores Code:
Upcast Angle: 0 degrees
Arrangement: Single Side
Offset Distance: 1/4 Road Reserve
Upward Waste Light Ratio: 2.8 %
0.14 Lux
Light Source: LED - Light Emitting Diode
Luminaire Classification: Not specified
Lighting Category: P4 (Local Area Roads - Tables 2.1 & 2.6)
Illuminance Criteria: Average Illuminance (Eav) >= 0.85 lx
(Maintained values) Minimum Illuminance (Eph) >= 0.14 lx
ISOLUX CONTOUR Illuminance Uniformity (Up) <= 10
10 0 10 20 30 40 50 METRES
Calculation Grid: 20 x 11 points - Figure 3.7 of AS/NZS 1158.2
Mounting Maximum Spacing for different
SCALE 1:500 AT A1 Height Road Reserve Widths
15.0
+---------------------+
5.1 I 61.0 I
+---------------------+
Value/s in above table are all in metres.
The table contains maximum spacings which, for the specified luminaire
and lamp combination, provide compliance with the light technical
parameters (LTPs) of Table 2.6 of AS/NZS 1158.3.1:2005.
Light Technical Parameters at Maximum Spacing
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
Mounting Road Maximum Eav Eph Up Emax
Height Reserve Spacing (Emax/Eav)
(m) (m) (m) (Ix) (Ix) (Ix)
5.1 15.0 61.0 1.12 0.14 5 6.04
---------------------------------------------------------------------------
PlePcat - Vers 3.10 (Built: 10/ 4/13)
Run: 28/06/2021 at 14:44:44
ISSUE DESCRIPTION DATE AUSPOWER CONNECT IS THE FIRST POINT OF DEVELOPER DETAILS ALIGNMENTS WORKS COORDINATOR - APPROVED: SUBDIVISION AUSPOWER CONNECT
AC1286
P PRELIMINARY DESIGN 20/08/2021 CONTACT FOR CONSTRUCTION ENQUIRIES. Auspower Connect Pty Ltd Ventralia Pty Ltd ENERGEX OH 3.0m PARENT PROJECT NO. - RECONFIGURE 1 LOT INTO 16 LOTS PROJECT NO.
Darren Matthews ENERGEX UG 0 - 0.9m WORK REQUEST NO. - RAL 20/0021 SCALE: 1:500
PO Box 531
0499 339 155 STREETLIGHTS 0.7m I.O.K LOTS 1-16 ENERGEX PROJECT NO.
Buddina, QLD 4575 ELECTRICAL RETICULATION
[email protected] NBN REFER DBYD
Mob 0419 707 166 INSTALL 5 LED 15W AERO 4K STREET LIGHTS
[email protected]
PROJECT MANAGER DETAILS GAS - CANCELLING LOTS 3 on RP113733 APPROVED DATE: N/A ENGINEERING INFORMATION S4400244
Ventralia Pty Ltd HP GAS - D.A RAL 20/0021 CHECKED: J McKenna
ABN 74 166 366 883
Darren Matthews WATER REFER DBYD LOCAL AUTHORITY Noosa Council DESIGNER: I Lubacheski
This drawing is the property of Auspower Connect Pty Ltd and 2 PEARSONS ROAD
0499 339 155 STORMWATER REFER DBYD UBD REF Map 5 A-20 PHONE: 0419 707 166
must not be used, retained or copied without written permission
COOROY 4563 ISSUE NO. P SHEET 5 OF 5 A1
[email protected] SEWER REFER DBYD PEGGED On Request ISSUE DATE: 20/08/2021