Electrical AC1286 Preliminary Design Sub 2 Pearsons Road, Cooroy 4563 [20-08-2021]
Original PDF page 1, section 1. The text section number identifies this passage in the reader.
SURVEY DETAILS
203 AS/NZS 3000:2018 STREET LIGHTING CERTIFICATE LEGEND
3.11.5 Spacing from other underground services PRINCIPAL'S SURVEYOR TO PEG ALL BOUNDARIES PRIOR TO
CONSTRUCTION AND AFTER CONSTRUCTION TO PROVE ACCURACY SYMBOL DESCRIPTION
ROAD AND PUBLIC SPACE LIGHTING IS CERTIFIED
TO COMPLY WITH THE NOMINATED CATEGORIES OF OF ASSET INSTALLATION.
All underground wiring systems shall be spacing not less than 100 mm from 1 STATION NUMBER
other underground services. AS/NZS 1158.1.1:2005 AND AS/NZS 1158.3.1:2020.
CONSTRUCTION NOTES EXISTING OH CONDUCTOR
BLUE WREN PLACE - PR5 PROPOSED OH CONDUCTOR
Wiring systems shall be suitably marked with warning tape in accordance 1. CONTRACTOR TO INCLUDED PROVISIONAL SUM FOR VACUUM HV and LV POLE
with Clause 3.11.4.5 and maintain a separation from telecommunications, THE DESIGN ASSUMES MAINTENANCE FACTORS OF EXCAVATION AS U.G. SERVICES HAVE BEEN IDENTIFIED IN THE POLE TRANSFORMER
gas and water services in accordance with Table 3.7. 0.7 FOR MINOR ROAD LIGHTING, 0.75 FOR MAJOR VICINITY.
HV AIR BREAK OPEN
ROAD LIGHTING, 0.75 FOR LED LIGHTING, BASED ON 2. CONTRACTOR INCLUDE PROVISIONAL SUM FOR 'CUT AND
THE FOLLOWING SCHEDULE. REINSTATE' CONCRETE FOOTPATH, FULL PANEL AND FILL HV AIR BREAK CLOSED
Further requirements for the separation of telecommunications, gas and
WIDTH AT STATION 5 TO TRANSFER EXISTING CROSSROAD LV DISC LINK OPEN
water systems from low voltage wiring systems are provided in
1. LAMPS ARE TO BE REPLACED AT 36 MONTH CONDUIT TO EXISTING SPARE LV CONDUIT FROM STATION 4 LV DISC LINK CLOSED
Clause 3.9.8.4. INTERVALS, AT WHICH TIME LUMINAIRES ARE TO AND AT STATION 2 TO INSTALL LV CONDUIT/TERMINATION FROM HV POLE TERMINATION
TABLE 3.7 BE INSPECTED, CLEANED AND MAINTAINED. POLE AT STATION 1.
LV POLE TERMINATION
2. VEGETATION IS TO BE KEPT CLEAR OF STREET 3. TRAFFIC CONTROL REQUIRED.
PRELIMINARY ISSUE
MINIMUM SEPARATION OF UNDERGROUND SERVICES GROUND STAY
LIGHTS.
3. INSPECTION PATROLS AND SPOT LAMP EXISTING UG CABLE
Minimum separation to low Minimum separation REPLACEMENT SHALL MAINTAIN SERVICE
CONSTRUCTION NOTES - PRIVATE PROPERTY PROPOSED UG CABLE
voltage electrical service of conductive THE CLIENT'S ELECTRICAL CONTRACTOR WILL BE RESPONSIBLE
AVAILABILITY AT NOT LESS THAN 95%.
NOT FOR CONSTRUCTION
EXISTING SUPPLY PILLAR
identified in accordance with enclosures to low FOR THE FOLLOWING:
4. LUMINAIRES AND LAMPS SHALL BE REPLACED PROPOSED SUPPLY PILLAR
Type of service Clause 3.11.4.5 and mechanically voltage electrical · INSTALL CONDUITS THE FULL LENGTH OF THE ACCESS
WITH EXACT EQUIVALENTS.
protected (1) earthing electrode (1) CORRIDOR OR SUPERVISE INSTALLATION BY OTHERS. LINK PILLAR
· REMOVE REDUNDANT ELECTRICAL WIRING. PADMOUNTED TRANSFORMER
mm mm
EXISTING CABLE IN CONDUIT
Water service not ELECTRICITY CONNECTION PROCESS PROPOSED CABLE IN CONDUIT
100 500
greater than DN65 (2)
MEN (EARTH GROUND STAKE)
1. DEVELOPER'S REPRESENTATIVE SUBMITS CERTIFICATE OF
Water service greater
300 500 RESIDENTIAL AND ELECTRICITY SUPPLY TO COUNCIL. E ELECTRICAL CABLE MARKER
than DN65 (2) CUSTOMER SWITCHBOARD
COMMERCIAL / INDUSTRIAL 2. DEVELOPER'S REPRESENTATIVE SUBMITS PLANS TO THE
Sanitary drainage 100 500 TITLES OFFICE. PIT
SUBDIVISIONS 3. ENERGEX ESTABLISHES A NATIONAL METER IDENTIFIER (NMI).
Stormwater drainage S70 STREET LIGHT
100 600 4. NEW CUSTOMER REFERENCES NMI AND MAKES AN
ONLY ENERGEX APPROVED MATERIALS, S250 STREET LIGHT
Gas 100 500 APPLICATION WITH THEIR ELECTRICITY RETAILER.
INSTALLATION EQUIPMENT, AND 5. ELECTRICAL CONTRACTOR REFERENCES NMI AND SUBMITS LED STREET LIGHT
Telecommunications 100 INSTALLATION TECHNIQUES SHALL BE THE APPLICATION WITH ENERGEX. TREE
USED DURING CONSTRUCTION. 6. ENERGEX MAKES CONNECTION.
NOTES: LV SWITCH FUSE UNIT
1 Authorities, such as water and as suppliers and electricity distributors, may
require their services to be spaced at a greater distance from underground wiring
systems. Also see Figure 3.10.
2 DN = internal diameter of pipe.
GENERAL NOTES
1. ALL CABLES TO BE INSTALLED IN CONDUIT WITHIN THE
STANDARD ELECTRICITY ALIGNMENT OF 250-900mm FROM
PROPERTY BOUNDARY.
2. CONSTRUCTION PERSONNEL SHALL MEASURE ACTUAL
CABLE LENGTHS REQUIRED ON SITE AFTER INSTALLATION
OF CONDUITS THEN NOTIFY SUPPLIER WHEN CONFIRMING
CABLE ORDER.
3. ALL BENDS INSTALLED ON 125mm RETICULATION
CONDUITS MUST BE 1830mm RADIUS UNLESS OTHERWISE
SPECIFIED.
AD
4. CONTRACTOR TO SUPPLY ALL LABELS AND SITE ID
WORK SITE
RO
NUMBERS TO ENERGEX SPECIFICATION.
ELM
5. DEVELOPERS CIVIL CONTRACTOR TO SUPPLY AND
NS
INSTALL CONDUITS AS SHOWN IN CIVIL WORK SCHEDULE.
SO
STR
6. INSTALL ELECTRICAL CONDUIT AND
CARRU
THERS TELECOMMUNICATIONS PIT AND PIPE IN JOINT USE
AR
C OURT TRENCH - REFER PROJECT NUMBER AC1286-T
EET
PE
STANDARDS AND SPECIFICATIONS
Lot Lot Lot Lot THIS WORKS PLAN IS TO BE READ IN CONJUNCTION AND
11 12 Lot
13 COMPLY WITH THE FOLLOWING ENERGEX MANUALS AND
D
14 15
OA
Lot Lot 100 SPECIFICATIONS:
10 - UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
R
Lot BLUE W Park
- OVERHEAD CONSTRUCTION MANUAL
Lot
9 R EN PLA NS
16 Lot CE - PUBLIC LIGHTING MANUAL
SO
8 Lot Lot Proposed - NETWORK LABELLING AND SIGNAGE MANUAL
7 Lot Lot Proposed Proposed
AR
6 5 Lot Lot Lot 11 Lot 12
4 Lot Lot 13 Proposed FOR DETAILS OF ADDITIONAL TRENCH CROSS-SECTIONS,
3 2 Proposed
PE
1 Lot 14 REFER TO ENERGEX UNDERGROUND DISTRIBUTION
Lot 15
CONSTRUCTION MANUAL.
Proposed Proposed
Lot 10 Lot 100
CE
Park
SPOTT UG SERVICES INFORMATION
ED GUM
A
COURT Proposed BLUE W
RT
REN PL
Lot 9 REN PL UNDERGROUND SERVICES SHOWN ON THIS WORKS PLAN
Proposed A CE
COU
Lot 16 IN THE VICINITY OF PROPOSED EXCAVATION WORKS ARE
Proposed INDICATIVE ONLY.
Lot 8
BLUE W
Proposed
OAK
ELM S
Lot 7 Proposed CONSTRUCTION PERSONNEL SHALL REQUEST ON-SITE
Lot 6 Proposed IDENTIFICATION AND LOCATION OF EXISTING BURIED
Lot 5 Proposed
SERVICES FROM THE QUEENSLAND DIAL BEFORE YOU DIG
EST
Lot 4 Proposed
Lot 3 Proposed SERVICE. PH:1100 FAX:1300 652 077 (A MINIMUM OF TWO DAYS
TREE
Lot 2 Proposed
NOTICE IS REQUIRED)
FOR
Lot 1
REFER JOB No: 21623980.
T
BLU
E W
REN P CONDUIT CROSS SECTION - FOOTPATH & ROADWAY
L
TR EET
GEM S SURVEY PLAN 600 FOOTPATH
SCALE 1:1000 750 MINOR ROAD
1200 MAJOR ROAD
LOCALITY MAP
SCALE 1:2000 DETAIL O DETAIL D DETAIL P DETAIL E
600 FOOTPATH
750 MINOR ROAD
1200 MAJOR ROAD
c c c
DETAIL H DETAIL N DETAIL Z
NOTE: 5mm PROTECTION COVER STRIP REQUIRED WHEN NOT IN ALLOCATED ENERGEX UG ALIGNMENT
ISSUE DESCRIPTION DATE AUSPOWER CONNECT IS THE FIRST POINT OF DEVELOPER DETAILS ALIGNMENTS WORKS COORDINATOR - APPROVED: SUBDIVISION AUSPOWER CONNECT
AC1286
P PRELIMINARY DESIGN 20/08/2021 CONTACT FOR CONSTRUCTION ENQUIRIES. Auspower Connect Pty Ltd Ventralia Pty Ltd ENERGEX OH 3.0m PARENT PROJECT NO. - RECONFIGURE 1 LOT INTO 16 LOTS PROJECT NO.
Darren Matthews ENERGEX UG 0 - 0.9m WORK REQUEST NO. - RAL 20/0021 SCALE: 1:2000 & 1:1000
PO Box 531
0499 339 155 STREETLIGHTS 0.7m I.O.K LOTS 1-16 ENERGEX PROJECT NO.
Buddina, QLD 4575 ELECTRICAL RETICULATION
[email protected] NBN REFER DBYD
Mob 0419 707 166 INSTALL 9 PILLARS, 441m OF 240 AL 4C UG LV CABLE
[email protected]
PROJECT MANAGER DETAILS GAS - CANCELLING LOTS 3 on RP113733 APPROVED DATE: N/A AND 5 STREET LIGHTING COLUMNS S4400244
Ventralia Pty Ltd HP GAS - D.A RAL 20/0021 CHECKED: J McKenna
ABN 74 166 366 883
Darren Matthews WATER REFER DBYD LOCAL AUTHORITY Noosa Council DESIGNER: I Lubacheski
This drawing is the property of Auspower Connect Pty Ltd and 2 PEARSONS ROAD
0499 339 155 STORMWATER REFER DBYD UBD REF Map 5 A-20 PHONE: 0419 707 166
must not be used, retained or copied without written permission
COOROY 4563 ISSUE NO. P SHEET 1 OF 5 A1