Council archive · source document
RFI - Eng Response Letter · MCU22/0172
09 November 2022
Ref: MCU22/0172, OPW22/0243, RAL22/0024
Ms L Pienaar
PO Box 141
Tewantin, QLD 4565
Attention: Lisa Pienaar
Dear Ms Pienaar,
Re: Information Request
At: 22 Grant St Noosa Heads Qld 4567
With reference to the abovementioned development application and the subsequent
further advice from Council, we have prepared a response to the engineering matters
raised as follows.
Sustainable Building Code
6. Provide amended plans that provide for rain water storage and provide an
amended stormwater management plan that incorporates tanks.
The Stormwater Management Plan has been amended to reflect a 3kL rainwater tank
or equivalent storage per dwelling as per the Sustainable Building Design and Water
Quality and Drainage codes. Drawing 040 has been updated to reflect these changes.
Driveway Access
8. Provide additional detail on the proposed driveway and crossover. The detail
must be prepared by a suitably qualified person (RPEQ – Registered
Professional Engineer of Queensland) and include, but not be limited to:
a. a design generally in accordance with RS-049, RS-050 and any associated
addendum;
b. levels and grade of the access driveway;
c. a longitudinal section extending from the centre of the formation along
Grant Street to the finished floor level of the proposed garages; and
d. demonstrate that a B99 vehicle will not scrape or bottom out while
entering or exiting the driveway.
Drawing 062 has been updated to provide this information.
9. Provide additional detail demonstrating how trip hazards will be eliminated
within the road reserve due to the construction of the proposed driveway
crossover. The amended plan must be prepared by a suitably qualified person
(RPEQ – Registered Professional Engineer of Queensland) and include, but not
be limited to:
P +61 7 5211 1003 A 75 Noosa Dr, Noosa Heads Qld 4567 E [email protected] recorconsulting.com
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 3 pages
Page 2
a. the full extent of the transition to the adjoining areas of verge.
Where possible the design is sympathetic to the existing conditions and localised grading
will be used to eliminate trip hazards within the road reserve.
External Works (Footpath)
10. Provide an amended plan that demonstrates a 1.5m wide footpath will be
constructed along the frontage of the subject site that connects to the adjoining
existing footpaths. The amended plan must be prepared by a suitably qualified
person (RPEQ – Registered Professional Engineer of Queensland).
Drawing 010 has been updated to provide this information.
Stormwater Infrastructure Works in Road Reserve
11. Provide additional information regarding the construction methodology of the
proposed stormwater pit and its’ integration into Council’s existing stormwater
infrastructure network. The detail should be prepared by a suitably qualified
person (RPEQ – Registered Professional Engineer of Queensland) and include,
but not be limited to:
a. demonstrate the extent of works required to remove the existing pit,
stormwater pipe and any kerb and reinstate the road and associated kerb;
b. demonstrate the extent of works required to install the proposed
stormwater pit and associated stormwater pipes, include levels (surface
and invert) and grades; and
c. demonstrate how the proposed stormwater pit will integrate into Council’s
existing stormwater infrastructure.
A review of Council’s mapped stormwater network has identified that these assets are not
captured in current Intramaps layer. Based on the site’s elevation and surrounding
landform, it is likely that these assets are discharging into Pinaroo Park (Lot 84 on SP248300)
detailed in Figure 2.
The existing pit appears to be a non-standard ‘Noosa Style’ Type B pit (STD DWG 9223A)
without the required transition lengths of 1m to kerb and channel, as shown in Figure 1. A
new on grade lip in line inlet pit is proposed for reconstruction and connection to Council’s
stormwater assets as there is no worsening of surface flow quantity from the development
to this catchment. Details related to levels and grades are provided on the Stormwater
Layout Plan.
P +61 7 5211 1003 A 75 Noosa Dr, Noosa Heads Qld 4567 E [email protected] recorconsulting.com
Page 3
Figure 1 Existing non-compliant ‘Noosa Style’ pit (inspected 9 November 2022)
Subject site
Pinaroo Park
Figure 2 Mapped stormwater infrastructure in area (Noosa Council Intramaps 2022)
P +61 7 5211 1003 A 75 Noosa Dr, Noosa Heads Qld 4567 E [email protected] recorconsulting.com
Page 4
Stormwater Catchment
12. Provide comment certifying that any potential additional catchment volume
from the uphill property (11 Katharina Street) has been accounted for during
the preparation of the Stormwater Management Plan for the subject site.
The Stormwater Management Plan’s internal drainage system has been designed for the
effects of the development. Whilst overland flows from upstream neighbouring properties
are possible, the potential overland volumes are unknown. However, the rear of the subject
site is in an area of cut and will require retaining walls and subsurface drainage for the pool
area. The plans have been updated to accommodate future connection for retaining wall
surface and subsurface drainage to the internal drainage network, thereby managing any
overland flows from upstream properties.
On-site Manoeuvrability
13. Provide an amended Turning Path Plan demonstrating that vehicles are able to
enter the proposed garages and exit the site in a reverse gear (or forward gear
if achievable) without colliding with any future landscaping or structures. The
additional detail must be prepared by a suitably qualified person (RPEQ –
Registered Professional Engineer of Queensland).
Drawing 060 and 061 has been updated to provide this information.
We believe that the above satisfactorily addresses the engineering matters raised in the
information request however, should additional information be required, please contact
our office directly.
Yours faithfully,
RECOR Pty Ltd
Prepared by
Ben Parry
Civil Engineer
BEng (Hons), MIEAust CPEng NER
RPEQ: 28084