GENERAL NOTES

1. ALL WORK IS TO COMPLY WITH THE QUEENSLAND PLUMBING & DRAINAGE ACT
2002 AND LOCAL AUTHORITY REQUIREMENTS.

2. THESE DRAWINGS ARE DIAGRAMMATIC ONLY. USE DIMENSIONED BUILDING
CONSTRUCTION PLANS FOR ANY SET OUT REQUIREMENTS.

3. OBTAIN APPROVALS FROM ALL AUTHORITIES HAVING JURISDICTION AND PAY
ALL FEES DUE.

4. THE CONTRACTOR IS TO VISIT THE SITE TO BE FULLY AWARE OF EXISTING
SERVICES AND SITE CONDITIONS PRIOR TO COMMENCEMENT OF WORK. ANY
CLAIM FOR VARIATION ON THE BASIS OF LACK OF KNOWLEDGE WILL NOT BE
ACCEPTED.

5. ENSURE INVERT LEVELS AND MINIMUM COVER IS ACHIEVABLE PRIOR TO
COMMENCEMENT OF WORK ON SITE.

6. ALL PLUMBING AND DRAINAGE SERVICES THAT PENETRATE FIRE RATED WALLS
AND FLOORS MUST BE INSTALLED TO COMPLY WITH THE REQUIRED FIRE
RESISTANCE LEVEL.

STORMWATER NOTES MATERIALS

1. ALL STORMWATER DRAINAGE SHALL BE 100MM¢% AND BE INSTALLED AT 1:100 1. WATER SERVICES — TO AS/NZS 3500
MINIMUM GRADE (UNO).
2. SANITARY DRAINAGE — PVC CLASS DWV
2. DOWNPIPES TO HAVE MINIMUM CROSS SECTIONAL AREA EQUAL TO 100MM¢

(UNO). 3. SANITARY PLUMBING — PVC CLASS DWV

3. ROOF GUTTERS AND DOWNPIPES TO FULLY COMPLY WITH THE REQUIREMENTS 4. DOWNPIPES — PVC CLASS DWV(UNO)
OF AS/NZS3500.3.
5. STORMWATER UP TO 300MM¢ — PVC CLASS SW HEAVY (UNO)

 

 

 

I

 

 

 

     

 

 

 

 

 

 

 

 

_
s ——— §

 

EXISTING WATER MAIN !

EXISTING SEWER

 

 

 

 

 

 

 

 

—
J

 

 

 

 

 

 

 

 

 

 

 

WYANDRA STREET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

uw
Ms
uo

      

> y SITE PLAN

BZ (REFER 1:100 PLAN FOR DETAILS)

SITE 1:200

 

 

ABBREVIATIONS

DP DOWNPIPE

e EXISTING

HV HYDRANT VALVE

IC INSPECTION CHAMBER

fe) INSPECTION OPENING

los INSPECTION OPENING TO SURFACE
MH MANHOLE

SW STORMWATER

UNO UNLESS NOTED OTHERWISE
LEGEND

STORMWATER _-— oO
EXIST SEWER ——s

EXIST STORMWATER —— sw

EXIST WATER ——w

EXIST OPTUS — --——_ -- ——_

NOTE:

XISTING SERVICES HAVE BEEN
COPIED FROM ’DIAL BEFORE YOU
DIG’ INFORMATION SERVICE AND

ARE NOT CONFIRMED.

 

 

 

 

 

B 01/06/12 | EXISTING SERVICES ADDED SW CLIENT IB
DISCHARGE REVISED

A 20/03/12 CLIENT IB

ISSUE | DATE REVISION STATUS IDESIGNED|

 

 

 

 

 

 

 

 

ian bradford

plumbing consultants

|

pty Itd

 

 

« P/F - (07) 5448 3875
. « M-0412654598
ian bradford * PO BOX 334
plumbing consultants PEREGIAN BEACH Q4573
pty Itd| ¢ [email protected]
« W- www.ibplumbingconsultants.com.au

 

 

 

 

 

BSA LICENCE NUMBER:- 1121367
LICENCE CLASS:- HYDRAULIC SERVICES DESIGN
(including on site wastewater management)

 

PROJECT

STORMWATER DRAINAGE ALTERATIONS
TELSTRA TELEPHONE EXCHANGE
30 WYANDRA STREET, NOOSA HEADS

 

TITLE

HYDRAULIC SERVICES

 

COVER SHEET

CLIENT DWG NO REV
McTAGGART PLUMBING 42027 -1 B
PTY LTD

 

 

 

A2 SCALE AS NOTED SHEET 1 OF 2

 

 

 
Full text of the other 1 page

Page 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

       

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

STORMWATER CALCULATIONS
oo \ ROOF AREA = 340m?
wl ( < RAINFALL INTENSITY (1 IN 20 YR) = 251mm/hr.
SW DRAINAGE THROUGH WALL TO UNDERCROFT | ESTIMATED FLOW = 24 LITRES/SECOND
| aw
| / EXISTING 100mm? DOWNPIPES
| CONNECT TO NEW 150¢
3 STORMWATER DRAINAGE (TYPICAL
|e FOR EACH DP)
! !
150 a
\ °
1 Oo O \S < !
SW DRAINAGE SUSPENDED BELOW % L
— FLOOR IN UNDERCROFT “
i |
N SW DRAINAGE THROUGH WALL
| AND DROPS ON OUTSIDE WALL
TO RUN INGROUND
KL =
1 TI \e l
<P “DP reDP> 600? GRATED GULLY PIT
\ -
SZ b
mS fi
J | N | sk \N .
° 150 Le Lr N 3
XN ke z
SW DRAINAGE CLIPPED ON N os z
OUTSIDE OF WALL ne
N
SW DRAINAGE ABOVE DOORS Nn 600? GRATED GULLY PIT
XQ l
DROPPER TO RUN BELOW Nn 3 x 125mm x 75mm STEEL
VENTILATION GRILL XY CHANNELS TO KERB. INSTALL
Ne UNDER EXISTING PATH — ALL TO
SW DRAINAGE DROPS TO RUN SUNSHINE COAST REGIONAL
INGROUND Nn COUNCIL APPROVAL
\N
N
3 x 125mm x 75mm OUTLETS
FROM GULLY PIT
iz
B 01/06/12 | EXISTING SERVICES ADDED SW CLIENT IB
DISCHARGE REVISED
( A |20/03/12 CLIENT 1B
Ss a ISSUE | DATE REVISION STATUS IDESIGNED|
S as plumbing consultants
NN 1] a © P/F - (07) 5448 3875 pty Ita
WwW Ww Ww - w w w W Ww WwW Ww Ww Ww W WwW WwW Ww ian bradford): Mo cowsean®
a plumbing consultants PEREGIAN BEACH Q4573
pty Itd| ¢ [email protected]
. /{ ¢ = W- www.ibplumbingconsultants.com.au
, BSA LICENCE NUMBER:- 1121367
/ LICENCE CLASS:- HYDRAULIC SERVICES DESIGN
\ \ ©) eSWMH (including on site wastewater management)
om g PROJECT
STORMWATER DRAINAGE ALTERATIONS
/ eKERB . TELSTRA TELEPHONE EXCHANGE
GULLY PIT 30 WYANDRA STREET, NOOSA HEADS
s Ss s Ss Ss Ss Ss Ss Ss Ss Ss s TITLE
HYDRAULIC SERVICES
y PART SITE PLAN
= NOTE:
Zp v PART SITE PLAN \ XISTING SERVICES HAVE BEEN CLIENT PWG NO m
<< SCALE 1:100 COPIED FROM ‘DIAL BEFORE YOU | McTAGGART PLUMBING B
\ DIG’ INFORMATION SERVICE AND PTY LTD 12027 -2
ARE NOT CONFIRMED.
A2 SCALE 1:100 U.N.O. SHEET 2 OF 2

 

 

 

 

Used in these records

About this file

File size
478 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

12027_SW_Telstra_30WyandraStreet_NoosaHeads_Revised.pdf · 478 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.