STORMWATER DRAINAGE NOTES
1.ANY CHANGES SHALL BE APPROVED BY THE ENGINEER IN WRITING PRIOR TO CARRYING OUT
OF THE WORKS                                                                                                                                                                                 100MM UPVC INLET

2.ALL LEVELS TO AHD.
3.ALL DIMENSIONS ARE IN MILLIMETRES UNLESS NOTED OTHERWISE.




                                                                                                                                                                                                        MIN 2000L
4.ALL DIMENSIONS AND LEVELS ARE TO BE CHECKED ON-SITE BEFORE WORK COMMENCES.




                                                                                                                                                                                                                                                                                                                                                                                  19
                                                                                                                                                                                                                                                                                                                                                                                                                             LINDSAY CONSULTING PTY LTD




                                                                                                                                                                                                                                                                                                                                                                              1.3
5. DIMENSIONS SHALL NOT BE OBTAINED BY SCALING THE DRAWING.                                                                                                                                                                                                                                                                                                                                                                LINDSAY CONSULTING PTY
                                                                                                                                                                                                                                                                                                                                                                                                                                              LTD




                                                                                                                                                                                                                                                                                                                                                                          PL
6. FOR BUILDING SET-OUT REFER ARCHITECTURAL DRAWINGS
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    RPEQ 4928




                                                                                                                                                                                                                                                                                                                                                                                                   .
7. THE LOCATION AND DEPTH OF ALL SERVICES SHALL BE VERIFIED ON SITE WITH THE




                                                                                                                                                                                                                                                                                                                                                                                                 om
                                                                                                                                                                                                                                                                                                                                                                                                  N
                                                                                                                                                                                                                                                                                                                                                                                                                           OFF. 2C/82 PARKER STREET, MAROOCHYDORE                 PH 54 792 118
REVLEVANT AUTHORITY PRIOR TO THE COMMENCEMENT OF WORKS




                                                                                                                                                                                                                                                                                                                                                                                               90
                                                                                                                                                                                                                                                                                                                                                                                                                          THIS DRAWING REMAINS THE PROPERTY OF




                                                                                                                                                                                                                                                                                                                                                                                           1.2
8. DURING CONSTRUCTION BARRIERS, LIGHTS & SIGNS SHALL BE MAINTAINED TO ENSURE SAFE                                                                                                                                                                                                                                                                                             ATER                                       LINDSAY CONSULTING PTY LTD AND IS FOR




                                                                                                                                                                                                                                                                                                                                                                                           IL
                                                                                                                                                                                                                                                                                                                                                                        W                       APPROVED KERB ADAPTER
                                                                                                                                                                                                                                                                                                                                                                    TORM
                                                                                                                                                                                                                                                                                                                                                       PVC S                                    SEE DETAIL
                                                                                                                                                                                                                                                                                                                                                                                                                            THE SOLE USE OF THE CLIENT. NO PART
PASSAGE OF TRAFFIC AND PEDESTRIANS IN ACCORDANCE WITH THE REQUIREMENTS OF THE                                                                                                                                                                                                                                                                    MM U
                                                                                                                                                                                                                                                                                                                                           2X100           )
LOCAL AUTHORITY.                                                                                                                                                                                                                                                                                                                                D E S HOWN                                                                MAY BE USED IN PART OR WHOLE WITHOUT
                                                                                                                                                                                                                                                                                                                                           (GRA
9.ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH CURRENT LOCAL AUTHORITIES
                                                                                                TO L.P.O.D                                                                                                                                                                                                                                                                                                                   PRIOR EXPRESS WRITTEN CONSENT OF
                                                                                                                              TO L.P.O.D                                                                                                                                                                                              600X600 STORMWATER                                                                        LINDSAY CONSULTING PTY LTD
SPECIFICATIONS AND STANDARDS.




                                                                                                                                                                                                                                                                                                                                                                             14.0
                                                                                                                                                                                                                                                                                                                                      PIT WITH M/DUTY GRATE
                                                                                                                                                                                                                                                                                                                                                                                                                         CLIENT AND PROJECT DESCRIPTION




                                                                                                                                                                                                                                                                                                                                                                                 70
10.THE CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING ALL RELEVANT AUTHORITIES                                                                                                                                                                                                                                                         T.O.G - 2.000
                                                                                                                                               DETENTION TANK
AND PAYING ALL FEES NECESSARY BEFORE COMMENCING WORK, FOR LOCATING ALL EXISTING
                                                                                                                                                                                                                                                                                                                                      U.S.I.L-1.620
                                                                                                                                                                                                                                                                                                                                      D.S.I.L-1.590
                                                                                                                                                                                                                                                                                                                                                                                                                           CLOUT DESIGN
SERVICES AND FOR REPAIR OF ANY SERVICES DAMAGED AS A RESULT OF THE FOOTPATHS
                                                                                                                                                                                                                                                                                                                                                                                                                           OPERATIONAL WORKS




                                                                                                                                                                                                                                                                                 30
                                                                                                                    100mm UPVC OVERFLOW PIPE
                                                                                                                                                                                                                                                                                N)




                                                                                                                                                                                                                                                                                2 .4
AND PRIVATE PROPERTY SHALL BE REINSTATED TO THEIR ORIGINAL CONDITION.                                        50mm UPVC PIPE
                                                                                                                                                                                                                                                                         OW
                                                                                                                                                                                                                                                                                                                                                                                                                           NO. 7 WILLIAM ST




                                                                                                                                                                                                                                                                         PL
                                                                                                             (LOW FLOW)                                                                                                                                             SH
                                                                                                                                                                                                                                                               DE




                                                                                                                                                                                                                                                                                       30
11.ANY OBSOLETE/REDUNANT DRIVEWAY CROSSINGS AND DRAINAGE OUTLETS FROM THE
                                                                                                                                                                                                                                                           RA
                                                                                                                                                                                                                                                                                                                                                                                                                           NOOSAVILLE




                                                                                                                                                                                                                                                                                     2 .4
KERB AND CHANNEL INCLUDING ASSOCIATED PIPES ACROSS THE FOOTPATH SHALL BE                                                                                                                                                                                 (G




                                                                                                                                                                                                                                                                                 PL
                                                                                                                                                                                                                                                  ER
REMOVED AND THE KERB AND CHANNEL AND FOOTPATH REINSTATED TO THE LOCAL                                                                                                                           86                                              AT
                                                                                                                                                                                            42.2                                        MW




                                                                                                                                                                                                                                                                                               30
                                                                                                                                                                                                                                                                                                                                  F.S.L - 2.300
                                                                                                                                                                                                                                      R




                                                                                                                                                                                                                                                                                            2.4
AUTHORITIES CURRENT SPECIFICATIONS AND OR STANDARDS                                                                                                                                                                           S    TO




                                                                                                                                                                                                                           30




                                                                                                                                                                                                                                                                                       PL
                                                                                                                                                                                                                      VC




                                                                                                                                                                                                                         2.4
12.THE CONTRACTOR'S ATTENTION IS DRAWN TO THE REQUIREMENTS OF THE WORKPLACE                                                                                                                                         UP
                                                                                                                                                                                                         M




                                                                                                                                                                                                                    PL
HEALTH AND SAFETY ACT 1995. ALL WORK IS TO BE CARRIED OUT IN ACCORDANCE WITH THIS
                                                                                                                                                                                                   15
                                                                                                                                                                                                      0M                                                                                                                                                                                                                 DRAWING TITLE
ACT AND IN PARTICULAR THE CONTRACTOR TO ENSURE THE REQUIREMENTS OF THIS
                                                                                                                                                                                                                                                                                                                                                                     )                                                     OPERATIONAL WORKS
SPECIFICATION WITH REGARD TO 'NOTIFICATION IN RELATION TO A NOTIFIABLE PROJECT ARE                                                    600X600 STORMWATER                                                                                                                                      F.F.L - 2.450                                                       DE
                                                                                                                                                                                                                                                                                                                                                              GRA
FULFILLED.                                                                                                                            PIT WITH M/DUTY GRATE                                                                                                                                                                                                N.
                                                                                                                                                                                                                                                                                                                                                         MI
                                                                                                                                      T.O.G - 2.200
                                                                                                                                                                                                                                                                                                                                                   (1%




                                                                                                                                                                 0
                                                                                                                                                                .20
13.BENCHING OF PIT STRUCTURES SHALL HAVE A SMOOTH FINISHED SURFACE, AND PIPES
                                                                                                                                      D.S.I.L-1.850                                                                                                                                                                                           ER




                                                                                                                                                                 2
                                                                                                                                                                                                                                                                                                                                           AT




                                                                                                                                                                                                                                                          SD
                                                                                                                                                              PL
SHALL NOT PROJECT INSIDE THE SHAFT OF THE PIT.
                                                                                                                                                                                                                                                                                                                                        MW
14.STORMWATER DRAINAGE PIPES SHALL BE UPVC PIPE (MINIMUM SEWER CLASS SN8) TO AS                                                                                                                                                                                                                                                    TO
                                                                                                                                                                                                                                                                                                                                      R                             Detention tank.                                      SCALES
                                                                                                                                                                                                                                                                                                                                  S
                                                                                                                                                                                                                                                                                                                           V  C                                     80% of roof water to
14. 1260 OR APPROVED EQUIVALENT. MINIMUM COVER TO ROOFWATER PIPES SHALL BE 50mm                                                                                                                                                                                                                                         UP




                                                                                                                                                                                                                              SD
                                                                                                                                                                                                                                                                                                                    M                                               be directed to tank.




                                                                                                                                                                                0
                                                                                                                                                                                                                                                                                                                 0M




                                                                                                                                                                            .45
EXCEPT WHERE REDUCED COVER IS REQUIRED TO DISCHARGE TO THE KERB AND CHANNEL.
                                                                                                                                                                                                                                                                                                              10                                                    Location of tank to
                                                                                                                                                                                                                                                                                                                                                                                                                                                          0                   5



                                                                                                                                  50




                                                                                                                                                                         2
                                                                                                                               2.2




                                                                                                                                                                      PL
15.MINIMUM PIPE GRADES FOR STORMWATER AS 3500 PART 3: PIPES SHALL COMPLY WITH                                                                                                                                                                                                                                                                                       be determined by




                                                                                                                          PL
              - 1.0% (MIN) GRADE FOR PIPES < 150 DIA.                                                                                                                                                                                                                                                                                                               builder
                                                                                                                                                                                                                                                                                                                                  2000L (Min) water
              - 0.5% (MIN) GRADE FOR PIPES > 150 BUT < 375 DIA.
16.CONCRETE DRIVEWAY AND PARKING AREAS SHALL BE CONSTRUCTED WITH 32 MPa                                                                                                     F.F.L - 2.450
                                                                                                                                                                                                                                                                                                                                  tank to be provided.
                                                                                                                                                                                                                                                                                                                                  50mm low flow to be                                                                                                     Orig. 1:200
17.REFER HYDRAULIC DRAWINGS FOR SANITARY DRAINAGE LAYOUTS.                                                                                                                                                                                                                                                                        cut into the tank




                                                                                                                                                  SD
                                                                                                                                                                                                                                                                    86
                                                                                                                                                                                                                                                                         42.2                Detention tank.
18.COMPACTION OF MATERIAL UNDER CONCRETE DRIVEWWAYS AND PARKING AREAS SHALL BE                                                                                                                                                                                                               80% of roof water to allowing for 2000L
              (i) 75% MINIMUM DENSITY FOR COHESIONLESS MATERIAL (AS 1289 E5.1) AND                                                                                                                                                                   )                                       be directed to tank. to be released after
                                                                                                                                                                                                                                                E
                                                                                                                                                                                                                                             AD                                                                                   a rain event.                                                                          SURVEY DATUM
                                                                                                                                                                                                                                           GR                                                Location of tank to
                                                                                                                                               F.F.L - 2.700
              (ii) 90% RELATIVE DRY DENSITY (STD COMP.) FOR MATERIAL OTHER THAN (i)                                                                                                                                                   N.
                                                                                                                                                                                                                                   MI
GENERAL NOTES (SOME MAY NOT APPLY)


                                                                                                                                                                 SD
                                                                                                               F.S.L - 2.300
                                                                                                                                                                                                                                                                                             be determined by

                                                                                                                                                                                                                    ER
                                                                                                                                                                                                                           (1%                                                               builder                                                                                                                       .
                                                                                                                                                                                                             AT
1. THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL OTHER CONSULTANTS                                                                                                                               W
                                                                                                                                                                                               O     RM
DRAWINGS AND SPECIFICATIONS. 2. BEFORE PROCEEDING WITH THE WORK ANY DISCREPANCIES
                                                                                                                                                                                       C
                                                                                                                                                                                           ST                                                                                                                                                                                                                            ASSOCIATED CONSULTANTS
                                                                                                                                                                                U   PV                               Detention tank.
IN THE CONTRACT DOCUMENTS SHALL BE REFERRED FOR DECISION TO THE ENGINEER.
                                                                                                                                                       N
                                                                                                   14.0




                                                                                                                                                       ER
                                                                                                                                                       CIST




                                                                                                                                                                           MM
                                                                                                    70




                                                                                                                                                                        0                                            80% of roof water to                                       2000L (Min) water
3. DO NOT SCALE FROM DRAWINGS IF IN DOUBT, ASK!!                                                                                                                      10
                                                                                                                                                                                                                     be directed to tank.                                       tank to be provided.
4. CONTRACTOR SHALL VERIFY ALL LOCATIONS OF SERVICES, ALL DIMENSIONS AND LEVELS
                                                                                                                                                                                                                     Location of tank to                                        50mm low flow to be
5. ALL MATERIALS & WORKMANSHIP SHALL BE IN ACCORDANCE WITH AS2890, THE (INCLUDING                                                                                                                                    be determined by                                           cut into the tank
THE QUEENSLAND SUPPLEMENT), THE QUEENSLAND BUILDING ACT AMENDMENT ACT 1991 AND                                                                                                                                       builder                                                    allowing for 2000L                                                                                          20 X 40 JOINT SEALANT
                                                                                                                                                                                                                                                                                                                                      DANLEY KEY JOINT WITH
6. THE CONTRACTOR IS RESPONSIBLE TO OBTAIN RELEVANT APPROVALS PRIOR TO                                                                                                                                                                                                          to be released after
                                                                                                                                                                                                                                                                                                                                      R12 DOWELS AT 300CRS
7. ALL STORMWATER CULVERTS TO BE RCP CLASS 2. ALL ROOFWATER PIPES TO BE uPVC                                                                                                                                                                                                    a rain event.

8. SILT MANAGEMENT PLAN TO REMAIN IN PLACE UNTIL COMPLETION OF WORKS AND                                                                                                                   2000L (Min) water
                                                                                                                                                                                           tank to be provided.
9. ALL PROPOSED OPERATIONAL WORKS SHALL BE CONSTRUCTED IN ACCORDANCE WITH
                                                                                                                                                                                           50mm low flow to be
                                                                                                                                                                                                                                                                                                                                                                    TYPICAL KEY JOINT
COUNCIL'S OPERATIONAL WORKS APPROVAL LETTER AND COUNCIL'S DECISION                                                                                                                                                                                                                                                                                                       Not to scale
                                                                                                                                                                                           cut into the tank
10.CONCRETE KERB RAMPS SHALL BE ALIGNED TO COMPLY WITH COUNCIL'S STANDARD                                                                                                                                                                                                                                                                     CUT EVERY SECOND WIRE DIRECTLY
                                                                                                                                                                                           allowing for 2000L
DRAWING AND SHALL BE CONSTRUCTED STRICTLY IN ACCORDANCE WITH COUNCIL STANDARD                                                                                                                                                                                                                                                                 UNDER JOINT AND DEPRESS FABRIC LOCALLY
                                                                                                                                                                                           to be released after
11. ALL TEMPORARY AND PERMANENT ROAD SIGNS AND LINEMARKING SHALL COMPLY WITH                                                                                                               a rain event.
THE CURRENT MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES(M.U.T.C.D.). EXISTING LINE
MARKING SHALL BE REMOVED BY GRINDING NOT"BLACKING OUT". COUNCIL DOES NOT                                                                                                                                                                                                                                                                                                 SAW CUT - (SC)
                                                                                                                                                                                                                                                                                                                                                                            Not to Scale
APPROVE OF BLACKING OUT OF EXISTING LINE MARKING. KERB MARKERS SHALL BE PROVIDED
                                                                                                                                                                                                                                                                                                                                                SAW CUTS (USING A SOFT CUT SAW)                                          REVISION LIST
FOR ALL WATER, TELSTRA AND ANY OTHER SERVICE CONDUIT ROAD CROSSINGS AS
                                                                                                                                                                                                                                                                                                                                                SHALL BE INSTALLED WITHING 8HRS                                          A ORIGINAL ISSUE                                              20/11/20
APPLICABLE.                                                                                                                                                                                                                                                                                                                                     OF CONCRETE PLACEMENT. WHERE AMBIENT

VEGETATION PROTECTION NOTES                                                                                                                                                                                                                                                                                                                     TEMP IS GREATER THAN 32 DEGREES
1. TREES LOCATED ALONG THE FOOTPATH SHALL BE, TRANSPLANTED PRIORTO                                                                                                                                                         OPERATIONAL WORKS                                                                                                    THIS TIME SHALL BE REDUCED TO 4 HOURS
                                                                                       .56




CONSTRUCTION, OR REPLACED IF DESTROYED.                                                                                                                                                                                                                                                                                                                                                     SL72 FABRIC (CENTRAL)
                                                                                      51




                                                                                             PROPOSED PAVEMENT LEVEL
                                                                                      PL




2. WHEN WORKING WITHIN 4m OF TREES, RUBBER OR HARDWOOD GIRDLES SHALL BE
                                                                                             KEY JOINT
CONSTRUCTED WITH 1.8m BATTENS CLOSELY SPACED AND ARRANGED VERTICALLY FROM
                                                                                             SAW JOINT                                                                                                                                                                                      It is the responsibility of the
GROUND LEVEL. GIRDLES SHALL BE STRAPPED TO TREES PRIOR TO CONSTRUCTION AND                                                                                                                                           Protect        your
                                                                                                                                                                                                                                                 NOTE                                       Foreman to contact the
                                                                                                                                                                                                                                                 THE ENGINEER MUST BE NOTIFIED OF           relevant service authorities to
                                                                                                                                                                                                                                                                                                                                                                     PAVEMENT DESIGN
                                                                                                                                                                                                                     PERSONAL
                                                                                                                                                                                                                                                 CHANGES PLANS. IF NOT, AS CONSTRUCTED      ascertain the exact location of
REMAIN UNTIL COMPLETION.                                                                                                                                                                                             INTERESTS.
                                                                                                                                                                                                                                                 DRAWINGS WILL NOT BE ISSUED
                                                                                                                                                                                                                       HEAD
                                                                                                                                                                                                                                                                                            services prior to construction.
                                                                                                                                                                                                                                                                                                                                                                            Not to Scale
3. TREE ROOTS SHALL BE TUNNELLED UNDER, RATHER THAN SEVERED. IF ROOTS ARE                                                                                                                                            EYES




                                                                                                                                                                                                                                                                                                                                                                                                             125
                                                                                                                                                                                                                     EARS                                                                                                                                                                                               Computer File
SEVERED THE DAMAGED AREA SHALL BE TREATED WITH A SUITABLE FUNGICIDE. CONTACT                                                                                                                                                         BODY        All proposed operational works shall be constructed                                                                                                                                                           201343OW.DWG
                                                                                                                                                                                                            HANDS
                                                                                                                                                                                                                                                                                                                                                                                                                        DRAWING NUMBER                                              SHEET   REV.
                                                                                                                                                                                                                                                 in accordance with Council's Operational Works approval

                                                                                                                                                                                                                                                                                                                                                                                                                                                                20-1343-F1
RELEVANT COUNCIL ARBORIST FOR FURTHER ADVICE.
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                      1 A
                                                                                                                                                                                                                                                 letter and Council's Decision Notice - Development Permit.
                                                                                                                                                                                                                    FEET
4. ANY TREE LOPPING REQUIRED SHOULD BE UNDERTAKEN BY AN APPROVED ARBORIST.
Log in to download the original file

Engineering.pdf · 2.0 MB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.