Stormwater Management Report

Proposed Residential Development




183 Weyba Road
Noosaville




For: Cooper & Small Pty Ltd



22 September 2021
Ref: S21-074
Log in to download the original file

Stormwater Report.pdf · 5.0 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

Full text of the other 39 pages

Page 2

DO C UM E NT I NFO RM ATIO N

Project Name:                Proposed Residential Development
Westera Partners Ref:        S21-074


Westera Partners Contact:
Jared Hill                   Phone: 0437 335 403
                             Email: [email protected]




Certified for Issue by:

Jared Hill                   RPEQ 19891

                             22 September 2021
Document Control:


 Revision                  Author                   Certified for Issue       Date

 A                         J. Hill   RPEQ 19891     J. Hill   RPEQ 19891      22.09.2021




This report has been prepared for Cooper & Small Pty Ltd for the purpose of accompanying a
development application lodged to Noosa Council. This report must only be used by Cooper & Small
Pty Ltd for this purpose and must not be used or relied upon by any other person for any other purpose.

The assessment, conclusions or recommendations in this report are based on conditions encountered
and information received at the time of preparing the report and may not be relied upon as site
conditions or operations vary over time.




                                                                                                     ii

Page 3

CO NT E NT S


1             INTRODUCTION ..................................................................................................................... 1
2             SITE DESCRIPTION ............................................................................................................... 1

2.1           Location and Land Use ............................................................................................................ 1

2.2           Lawful Point of Discharge ........................................................................................................ 2

2.3           Upstream Drainage Connection .............................................................................................. 2

2.4           Flooding ................................................................................................................................... 2

3             STORMWATER QUANTITY MANAGEMENT ........................................................................ 2
4             WATER QUALITY MANAGEMENT ....................................................................................... 2

4.1           Operational Phase ................................................................................................................... 2

4.2           Construction Phase ................................................................................................................. 3

4.2.1         Design Objectives .................................................................................................................... 3
4.2.2         Erosion and Sediment Control ................................................................................................. 5
4.2.3         Maintenance and Monitoring Requirements ............................................................................ 6
5             CONCLUSION ......................................................................................................................... 7
6             APPENDICES ..................................................................................................................... A-1

Appendix A – Erosion Hazard Assessment ........................................................................................ A-1

Appendix B – Flood Information Certificate ........................................................................................ B-1

Appendix C – Engineering Plans ........................................................................................................ C-1

Appendix D – Site Survey & Architectural Drawings .......................................................................... D-1


List of Tables

Table 1 – Pollutants Typically Generated During the Construction Phase ............................................. 3

Table 2 – SPP Appendix 2: Part 1 Construction Phase – Stormwater Management Design Objectives
           .............................................................................................................................................. 3
Table 3 – SPP Appendix 2: Part 2 Construction Phase – Stormwater Management Design Objectives
           for Temporary Drainage Works ............................................................................................ 5

Table 4 – SPP Appendix 2: Part 3 Construction Phase – Stormwater Management Design Objectives
           for Emergency Spillways on Temporary Sediment Basins................................................... 5

Table 5 - ESC maintenance requirements. ............................................................................................. 6

List of Figures

Figure 1 – Indicative site location (Nearmaps, 2021) ............................................................................. 1




                                                                                                                                                        iii

Page 4

1         INT RO D UC TIO N


Westera Partners Pty Ltd has been commissioned by Cooper & Small Pty Ltd to prepare a Stormwater
Management Report to accompany a development application to Noosa Council for a proposed
residential development.

The proposal involves the construction of a duplex on an existing lot along with new access driveway
and ground level features. Driveway access will be provided via a single, shared access crossover from
Weyba Road.

This report documents how stormwater runoff will be managed on site in accordance with Noosa
Council’s (NC’s) requirements.

2      SI T E D ES CR I PT IO N


2. 1    Loc at i on an d L and U se

The proposed development site is located at 183 Weyba Road, Noosaville, also known as Lot 8
rp113358. The proposed development area is approximately 607m2 and is currently occupied by a
detached dwelling. The site currently generally falls to the north towards Weyba Road at approximately
1.0% grade.

The site is bound by residential properties to the east and south, a commercial property to the west and
Weyba Road to the north. Refer to Figure 1 for an indicative site location and Appendix C for detailed
site survey information.




                                              SITE




                       Figure 1 – Indicative site location (Noosa Mapping, 2021)



                                                                                                      1

Page 5

2. 2       Law fu l P oint of D is ch ar ge

Under existing site conditions, roofwater runoff from the existing dwelling appears to discharge to the
Weyba Road kerb and channel with runoff from ground level areas discharging towards Weyba Road
as sheet flow.

The proposed lawful point of discharge for the site shall be the Weyba Road kerb and channel in line
with existing conditions. Roofwater runoff from the proposed development shall be collected on site
and directed to the kerb and channel via the construction of new on site drainage. Refer to Appendix B
for further information regarding the proposed stormwater works for the development.

2. 3       Ups tr e am D r ain ag e C onn e ct ion

The development site does not have any upslope, unimproved properties unable to gravity drain to a
lawful point of discharge.

2. 4       Flood ing

The proposed development site is impacted by NC flood overlay mapping for both river flooding and
stormtide sources. The proposed development will need to adequately achieve immunity to these flood
events in accordance with the Noosa Council Flood Overlay Code. The Flood Information Certificate
(refer Appendix B) obtained from Council has identified a Defined Flood Level (DFL) of 2.40m AHD and
an applicable immunity level for habitable rooms of 2.70m AHD (300mm freeboard). The proposed
duplex will need to have a minimum floor level of 2.70m AHD to comply with the Flood Overlay Code
requirements. A reduced floor level of 2.60m AHD is proposed for the garages to assist with driveway
grading.

3      STO R M WAT E R Q UA N TIT Y M AN AG E ME NT


A detailed stormwater quantity analysis of the existing and developed site conditions has not been
undertaken as the proposal is for a residential duplex on an existing residential lot without substantial
change in site impervious fraction as a result of the development.

4      W AT ER Q U AL IT Y M A NAG E M EN T


4. 1       O pe r at io na l Ph a se

The development is not required to meet the Queensland Government’s State Planning Policy (July
2017) as the site does not exceed the 2,500m2 minimum site area. However stormwater quality
management must still be undertaken via the application of best management practices (BMPs) to
ensure no adverse impacts to the downstream environment.

Pollutants typically generated during the operational phase of the development include:

       •    Litter/gross pollutants;

       •    Sediment;

       •    Nutrients (N & P);

       •    Hydrocarbons (oils and grease); and

       •    Heavy metals.
Stormwater quality best management practices may be implemented for the development as follows:

       •    First flush diversion system for roof water diverting the roof water for irrigation purposes

       •    Rainwater storage tanks may be used to collect rainwater for landscape irrigation.

                                                                                                           2

Page 6

Best management practices have been deemed sufficient for the site area and land use. Refer to
Appendix B for the stormwater management drawing.

4. 2       Con st ruc t io n Ph a se

Management of stormwater runoff during construction and the implementation of an erosion & sediment
control program is necessary to avoid impacts to receiving waters from pollutants typically generated
during the construction phase. Typical pollutants are described in Table 1 below:

Table 1 – Pollutants Typically Generated During the Construction Phase

              Pollutant                                            Sources

 Litter (Gross Pollutants)         Paper, construction packaging, food packaging, cement bags.

 Sediment                          Unprotected exposed soils and stockpiles during earthworks and building.

 Hydrocarbons                      Fuel and oil spills, leaks from construction equipment.

 Toxic materials                   Cement slurry, asphalt prime, solvents, cleaning agents, wash waters.

 pH altering substances            Acid sulphate soils, cement slurry and wash waters.

In addition to the degradation of receiving waters, impacts of inadequate erosion and sediment control
downstream from the site include:

       •    traffic safety problems;
       •    blocked drains;

       •    local flooding problems;

       •    aesthetic pollution of drainage paths; and

       •    damage to local ecosystems.
4.2.1 De si gn O bj e ct i v es

Management of stormwater runoff during construction should be undertaken in accordance with
Appendix 2 of the SPP (July 2017). The SPP outlines the design objectives for construction phase
stormwater management. These are presented in Table 2, Table 3 and Table 4.

Table 2 – SPP Appendix 2: Part 1 Construction Phase – Stormwater Management Design Objectives

               Issue             Desired Outcomes




 Drainage Control                1. Manage stormwater flows around or through areas of exposed soil to
                                    avoid contamination.

                                 2. Manage sheet flows in order to avoid or minimise the generation of rill or
                                    gully erosion.

                                 3. Provide stable concentrated flow paths to achieve the construction
                                    phase stormwater management design objectives for temporary
                                    drainage works (part 2).




                                                                                                             3

Page 7

         Issue             Desired Outcomes



                           4. Provide emergency spillways for sediment basins to achieve the
                              construction phase stormwater management design objectives for
                              emergency spillways on temporary sediment basins (part 3).




Erosion Control            1. Stage clearing and construction works to minimise the area of exposed
                              soil at any one time.
                           2. Effectively cover or stabilise exposed soils prior to predicted rainfall.

                           3. Prior to completion of works for the development, and prior to removal
                              of sediment controls, all site surfaces must be effectively stabilised
                              using methods which will achieve effective short-term stabilisation.

Sediment Control           1. Direct runoff from exposed site soils to sediment controls that are
                              appropriate to the extent of disturbance and level of erosion risk.

                           2. All exposed areas greater than 2500 metres must be provided with
                              sediment controls which are designed, implemented and maintained
                              to a standard which would achieve at least 80% of the average annual
                              runoff volume of the contributing catchment treated (i.e. 80%
                              hydrological effectiveness) to 50mg/L Total Suspended Solids (TSS) or
                              less, and pH in the range (6.5–8.5).

Litter, Hydrocarbons and   1. Remove gross pollutants and litter.
other contaminants
                           2. Avoid the release of oil or visible sheen to released waters.

                           3. Dispose of waste containing contaminants at authorised facilities.

Waterway Stability and     1. Where measures are required to meet post-construction waterway
flood flow management         stability objectives, these are either installed prior to land disturbance
                              and are integrated with erosion and sediment controls, or equivalent
                              alternative measures are implemented during construction.

                           2. Earthworks and the implementation of erosion and sediment controls
                              are undertaken in ways which ensure flooding characteristics
                              (including stormwater quantity characteristics) external to the
                              development site are not worsened during construction for all events up
                              to and including the 1 in 100 year ARI (1% AEP).




                                                                                                          4

Page 8

Table 3 – SPP Appendix 2: Part 2 Construction Phase – Stormwater Management Design Objectives
for Temporary Drainage Works

 Temporary Drainage Works                        Anticipated Operation Design Life and Minimum
                                                              Design Storm Event


                                                 <12 Months        12-24 Months         >24 Months

 Drainage Structure                               1 in 2 year       1 in 5 year         1 in 10 year
                                                 ARI/39% AEP       ARI/18% AEP         ARI/10% AEP

 Where located immediately up-slope of an                     1 in 10 year ARI/10% AEP
 occupied property that would be adversely
 affected by the failure or overtopping of the
 structure

 Culvert Crossing                                             1 in 1 year ARI/63% AEP


Table 4 – SPP Appendix 2: Part 3 Construction Phase – Stormwater Management Design Objectives
for Emergency Spillways on Temporary Sediment Basins

            Drainage Structure                   Anticipated Operation Design Life and Minimum
                                                              Design Storm Event


                                                  <3 Months         3-12 Months         >12 Months

 Emergency spillways         on    temporary      1 in 10 year      1 in 20 year        1 in 50 year
 sediment basins                                 ARI/10% AEP        ARI/5% AEP          ARI/2% AEP

Best practice erosion and sediment controls must be installed to minimise the discharge of sediment
laden runoff during construction and to achieve the objectives outlined in Tables 2-4. This is discussed
in the following section.
4.2.2 E ro sio n and Se dim en t Co ntr ol

Management of stormwater runoff during construction is necessary to avoid pollution of downstream
waterways from sediment and gross pollutant loading. Impacts of inadequate erosion and sediment
control downstream from the site include:

    •   traffic safety problems;

    •   blocked drains;

    •   local flooding problems;

    •   aesthetic pollution of drainage paths; and

    •   damage to local ecosystems.
Best practice erosion and sediment controls must be installed to minimise the discharge of sediment
laden runoff during construction. Erosion and sediment control plans shall be developed during detailed
design phase and must be continually maintained and amended as required to minimise environmental
harm.



                                                                                                       5

Page 9

Erosion and sediment control plans are based on three sets of control measures:

    •   drainage control;

    •   erosion control; and
    •   sediment control.

These control measures must be maintained in an effective operational condition. Sediment disposal
from site is to occur to the satisfaction of Noosa Council. Defects in erosion and sediment control
devices, such as sediment fences, are to be inspected and documented. Upon Inspection, the
Contractor is to determine whether the device should be replaced or repaired. Documentation is to
include how the damage was caused and what measures can be implemented to reduce the possibility
of repeat occurrences. Any damage to either permanent or temporary water quality control structures
or devices is to be immediately rectified at the contractor’s expense.
The effectiveness of the erosion and sediment control devices can be monitored by visual audits. All
ESC measures are to be inspected:

    •   at least daily (when work is occurring on site) or weekly (when work is not occurring on site);

    •   within 24 hours of expected rain; and

    •   within 18 hours of a rainfall event (i.e. an event of sufficient intensity and duration to mobilise
        sediment on site).
Drainage paths are to be inspected to ensure the sediment fences are not being bypassed as a result
of soil erosion.

Sediment laden runoff shall be prevented from entering neighbouring properties. This shall be achieved
by landscaping disturbed areas immediately and prior to a rainfall event.

The proposed development has scored a 13 on the IECA erosion hazard assessment with no trigger
score values exceeded (refer Appendix A for details). Further details of proposed on site erosion and
sediment control measures will be required at the detailed design phase of the development.
4.2.3 Ma int en an ce and M o nit o ri ng Re qui r em ent s

Periodic maintenance and monitoring of stormwater devices proposed in this report is crucial to ensure
effective operation and design life.
Inspect field inlet grates, pits and underground pipes for blockage or damage at least 6 monthly or after
significant rainfall event. The filter baskets shall be inspected and maintained preferably by the
manufacturer to avoid damage to units and to ensure adequate cleaning and record keeping. For the
first 12 months routine inspections of filter baskets shall be carried out monthly with routine clean out
at alternate months. Results of the initial 12 months maintenance program shall be used to determine
future maintenance intervals. Refer manufactures maintenance and monitoring methodology for
specific details.

Maintenance of ESC measures must occur in accordance with Table 5.

Table 5 - ESC maintenance requirements.

        ESC Measure                  Maintenance Trigger              Timeframe for Completion
                                                                           of Maintenance

 Sediment basins               When settled sediment exceeds         Within 7 days of the
                               the volume of the sediment            inspection.
                               storage zone


                                                                                                          6

Page 10

 Other ESC measures           The capacity of ESC measures         By the end of the day.
                              falls below 75%.

Sediment accumulation on ESC devices is to be removed and disposed of to the satisfaction of Noosa
Council.

5   CO N CLU S IO N


This SWMP outlines how stormwater runoff from the site will be managed in order to not adversely
impact the receiving environment.
The proposed lawful point of discharge for the development shall be the Weyba Road kerb and channel.
Stormwater detention is not considered to be required as the proposal is for a residential duplex on an
existing lot. Stormwater runoff from the development site will need to be collected on site and directed
to the kerb and channel at the build phase to ensure no adverse impacts to neighbouring properties as
a result of the development.

The development will need to comply with the necessary flood immunity levels in line with the
requirements of the Noosa Flood Overlay Code as outlined on the Flood Information Certificate.

Stormwater treatment should be managed through the implementation of best management practices
on site. Based on the scale of the proposed development, and typical pollutants produced, these
measures are considered adequate.

By implementing the proposed stormwater management system, and providing adequate maintenance,
the downstream environment and neighbouring properties will not experience any adverse deterioration
of water quality as a result of the proposed development.




                                                                                                      7

Page 11

6   AP P E ND IC E S



App end ix A – E ro sio n H az ar d As s es sm en t




                                                      A-1


[OCR of page images]
Us WESTERA
PARTNERS

 

6 APPENDICES

Appendix A — Erosion Hazard Assessment

Page 12

Best Practice Erosion And Sediment Control                                  Erosion Hazard Assessment Form


                               Erosion Hazard Assessment Form
                               Condition                                       Points   Score     Trigger
                                                                                                   value
AVERAGE SLOPE OF DISTURBANCE AREA [1]
•   not more than 3%                                [3%  33H:1V]                 0
•   more than 3% but not more than 5%               [5% = 20H:1V]                 1
                                                                                           1         4
•   more than 5% but not more than 10%              [10% = 10H:1V]                2
•   more than 10% but not more than 15% [15%  6.7H:1V]                           4
•   more than 15%                                                                 6
SOIL CLASSIFICATION GROUP (AS1726) [2]
•   GW, GP, GM, GC                                                                0
•   SW, SP, OL, OH                                                                1        3
•   SM, SC, MH, CH                                                                2
•   ML, CL, or if imported fill is used, or if soils are untested                 3
EMERSON (DISPERSION) CLASS NUMBER [3]
•   Class 4, 6, 7, or 8                                                           0
•   Class 5                                                                       2        4         6
•   Class 3, (default value if soils are untested)                                4
•   Class 1 or 2                                                                  6
DURATION OF SOIL DISTURBANCE [4]
•   not more than 1 month                                                         0
•   more than 1 month but not more than 4 months                                  2        2         6
•   more than 4 months but not more than 6 months                                 4
•   more than 6 months                                                            6
AREA OF DISTURBANCE [5]
•   not more than 1000 m2                                                         0
•   more than 1000 m2 but not more than 5000 m2                                   1        0         4
•   more than 5000 m2 but not more than 1 ha                                      2
•   more than 1 ha but not more than 4 ha                                         4
•   more than 4 ha                                                                6
WATERWAY DISTURBANCE [6]
•   No disturbance to a watercourse, open drain or channel                        0
                                                                                           0         2
•   Involves disturbance to a constructed open drain or channel                   1
•   Involves disturbance to a natural watercourse                                 2
REHABILITATION METHOD [7]
Percentage of area (relative to total disturbance) revegetated by seeding
without light mulching (i.e. worst-case revegetation method).
•   not more than 1%                                                              0        0
•   more than 1% but not more than 5%                                             1
•   more than 5% but not more than 10%                                            2
•   more than 10%                                                                 4
RECEIVING WATERS [8]
•   Saline waters only                                                            0        0
•   Freshwater body (e.g. creek or freshwater lake or river)                      2
SUBSOIL EXPOSURE [9]
•   No subsoil exposure except of service trenches                                0        2
•   Subsoils are likely to be exposed                                             2
EXTERNAL CATCHMENTS [10]
•   No external catchment                                                         0
                                                                                           0
•   External catchment diverted around the soil disturbance                       1
•   External catchment not diverted around the soil disturbance                   2
ROAD CONSTRUCTION [11]
•   No road construction                                                          0        0
•   Involves road construction works                                              2
pH OF SOILS TO BE REVEGETATED [12]
•   more than pH 5.5 but less than pH 8                                           0        1
•   other pH values, or if soils are untested                                     1

                                                                    Total Score [13]      13


IECA (Australasia)                               November 2008                                     Page 1

Page 13

Best Practice Erosion And Sediment Control                        Erosion Hazard Assessment Form


Explanatory notes
Requirements:        Specific issues or actions required by the proponent.
Warnings:            Issues that should be considered by the proponent.
Comments:            General information relating to the topic.


[1]   REQUIREMENTS:
      For sites with an average slope of proposed land disturbance greater than 10%, a
      preliminary ESCP must be submitted to the regulatory authority for approval
      during planning negotiations.

      Proponents must demonstrate that adequate erosion and sediment control
      measures can be implemented on-site to effectively protect downstream
      environmental values.

      If site or financial constraints suggest that it is not reasonable or practicable for
      the prescribed water quality objectives to be achieved for the proposal, then the
      proponent must demonstrate that alternative designs or construction techniques
      (e.g. pole homes, suspended slab) cannot reasonably be implemented on the
      site.

      WARNINGS:
      Steep sites usually require more stringent drainage and erosion controls than
      flatter grade sites.

      COMMENTS:
      The steeper the land, the greater the need for adequate drainage controls to
      prevent soil and mulch from being washed from the site.

[2]   REQUIREMENTS:
      If the actual soil K-factor is known from soil testing, then the Score shall be
      determined from Table 1.

      If a preliminary ESCP is required during planning negotiations, then it must be
      demonstrated that adequate space is available for the construction and operation
      of any major sediment traps, including the provision for any sediment basins and
      their associated embankments and spillways. It must also be demonstrated that
      all reasonable and practicable measures can be taken to divert the maximum
      quantity of sediment-laden runoff (up to the specified design storm) to these
      sediment traps throughout the construction phase and until the contributing
      catchment is adequately stabilised against erosion.

      WARNINGS:
      The higher the point score, the greater the need to protect the soil from raindrop
      impact and thus the greater the need for effective erosion control measures. A
      point score of 2 or greater will require a greater emphasis to be placed on
      revegetation techniques that do not expose the soil to direct rainfall contact
      during vegetation establishment, e.g. turfing and Hydromulching.

      COMMENTS:
      Table 2 provides an indication of soil conditions likely to be associated with a
      particular Soil group based on a statistical analysis of soil testing across NSW.
      This table provides only an initial estimate of the likely soil conditions.



IECA (Australasia)                           November 2008                               Page 2

Page 14

Best Practice Erosion And Sediment Control                               Erosion Hazard Assessment Form


        The left-hand-side of the table provides an indication of the type of sediment
        basin that will be required (Type C, F or D). The right-hand-side of the table
        provides an indication of the likely erodibility of the soil based on the Revised
        Universal Soil Loss Equation (RUSLE) K-factor.

        Table 3 provides some general comments on the erosion potential of the various
        soil groups.

                          Table 1 – Score if soil K-factor is known
                                                RUSLE soil erodibility K-factor
                           K < 0.02             0.02<K<0.04          0.04<K<0.06              K > 0.06
     Score                       0                   1                      2                     3

                      Table 2 – Statistical analysis of NSW soil data [1]

Unified          Likely sediment basin                    Probable soil erodibility K-factor (%) [2]
  Soil             classification (%)
 Class         Dry                   Wet            Low         Moderate           High          Very High
System
             Type C      Type F        Type D     K < 0.02     0.02<K<0.04      0.04<K<0.06       K > 0.06
  GM            30          58             12        12             51              26                 12
  GC            42          33             25        13             71              17                 0
  SW            40          48             12        49             39              12                 0
   SP           53          32             15        76             18               5                 1
  SM            21          67             12        26             48              25                 1
   SC           26          50             24        16             64              18                 2
  ML            5           63             32        4              35              45                 16
   CL           9           51             39        12             56              19                 13
   OL           2           80             18        34             61               5                 1
  MH            12          41             48        15             19              41                 25
  CH            5           44             51        39             43              11                 7
Notes: [1]    Analysis of soil data presented in Landcom (2004).
       [2]    Soil erodibility based on Revised Universal Soil Loss Equation (RUSLE) K-factor.

Unified Soil Classification System (USCS)
GW      Well graded gravels, gravel-sand mixtures, little or no fines
GP      Poorly graded gravels, gravel-sand mixture, little or no fines
GM      Silty gravels, poorly graded gravel-sand-silt mixtures
GC      Clayey gravels, poorly graded gravel-sand-clay mixtures
SW      Well graded sands, gravelly sands, little or no fines
SP      Poorly graded sands, gravelly sands, little or no fines
SM      Silty sands, poorly graded sand-silt mixtures
SC      Clayey sands, poorly graded sand-clay mixtures
ML      Inorganic silts & very fine sands, rock flour, silty or clayey fine sands with slight plasticity
CL      Inorganic clays, low–medium plasticity, gravelly clays, sandy clays, silty clays, lean clays
OL      Organic silts and organic silt-clays of low plasticity
MH      Inorganic silts, micaceous or diatomaceous fine sandy or silty soils, elastic silts
CH      Inorganic clays of high plasticity, fat clays
OH      Organic clays of medium to high plasticity




IECA (Australasia)                                November 2008                                        Page 3

Page 15

Best Practice Erosion And Sediment Control                                       Erosion Hazard Assessment Form



                      Table 3 – Typical properties of various soil groups [1]
   Soil Groups                                           Typical properties [2]
     GW, GP               •    Low erodibility potential.
     GM, GC               •    Low to medium erodibility potential.
                          •    May create turbid runoff if disturbed as a result of the release of silt
                               and clay particles.
      SW, SP              •    Low to medium erodibility potential.
      SM, SC              •    Medium erodibility potential.
                          •    May create turbid runoff if disturbed as a result of the release of silt
                               and clay particles.
      MH, CH              •    Highly variable (low to high) erodibility potential.
                          •    Will generally create turbid runoff if disturbed.
      ML, CL              •    High erodibility potential.
                          •    Tendency to be dispersive.
                          •    May create some turbidity in runoff if disturbed.
Note: [1]       After Soil Services & NSW DLWC (1998).
      [2]       Any soil can represent a high erosion risk if the binding clays or silts are unstable.

Table 4 provides general guidelines on the suitability of various soil groups to various
engineering applications.

      Table 4 – Engineering suitability based on Unified Soil Classification [1]
                                            Embankments
                               USC                                        Fill         Slope        Untreated
Unified Soil Class                        Water           Non
                              Group                                                   stability      roads
                                        retaining        water
                                                       retaining
Well graded gravels            GW       Unsuitable      Excellent      Excellent      Excellent          Average
Poorly graded gravel           GP       Unsuitable      Average        Excellent       Average       Unsuitable
Silty gravels                  GM       Unsuitable      Average          Good          Average           Average
Clayey gravels                 GC        Suitable       Average          Good          Average       Excellent
Well graded sands              SW       Unsuitable      Excellent      Excellent      Excellent          Average
Poorly graded sands            SP       Unsuitable      Average          Good          Average       Unsuitable
Silty sands                    SM       Suitable [2]    Average        Average         Average            Poor
Clayey sands                   SC        Suitable       Average        Average         Average            Good
Inorganic silts                ML       Unsuitable        Poor         Average          Poor         Unsuitable
Inorganic clays                CL       Suitable [2]      Good         Average          Good              Poor
Organic silts                  OL       Unsuitable     Unsuitable        Poor         Unsuitable     Unsuitable
Inorganic silts                MH       Unsuitable        Poor           Poor           Poor         Unsuitable
Inorganic clays                CH       Suitable [2]    Average       Unsuitable       Average       Unsuitable
Organic clays                  OH       Unsuitable     Unsuitable     Unsuitable      Unsuitable     Unsuitable
Highly organic soils           Pt       Unsuitable     Unsuitable     Unsuitable      Unsuitable     Unsuitable
Notes:   [1]      Modified from Hazelton & Murphy (1992)
         [2]      Suitable only after modifications to soil such as compaction and/or erosion protection




IECA (Australasia)                                     November 2008                                         Page 4

Page 16

Best Practice Erosion And Sediment Control                   Erosion Hazard Assessment Form


[3]   If the soils have not been tested for Emerson Class, then adopt a score of 4.

      REQUIREMENTS:
      Works proposed on sites containing Emerson Class 1 or 2 soils have a very high
      pollution potential and must submit a conceptual ESCP to the regulatory authority
      for review and/or approval (as required by the authority) during planning
      negotiations.

      WARNINGS:
      Class 3 and 5 soils disturbed by cut and fill operations or construction traffic are
      highly likely to discolour stormwater (i.e. cause turbid runoff). Chemical
      stabilisation will likely be required if these soils are placed immediately adjacent
      to a retaining wall. Any disturbed Class 1, 2, 3 and 5 soils that are to be
      revegetated must be covered with a non-dispersive topsoil as soon as possible
      (unless otherwise agreed by the regulatory authority).

      Class 1 and 2 soils are highly likely to discolour (pollute) stormwater if exposed to
      rainfall or flowing water. Treatment of these soils with gypsum (or other suitable
      substance) will most likely be required. These soils should not be placed directly
      behind a retaining wall unless it has been adequately treated (stabilised) or
      covered with a non-dispersible soil.

[4]   The duration of disturbance refers to the total duration of soil exposure to rainfall
      up until a time when there is at least 70% coverage of all areas of soil.

      REQUIREMENTS:
      All land developments with an expected soil disturbance period greater than 6
      months must submit a conceptual ESCP to the regulatory authority for review
      and/or approval (as required by the authority) during planning negotiations.

      COMMENTS:
      Construction periods greater than 3 months will generally experience at least
      some significant storm events, independent of the time of year that the
      construction (soil disturbance) occurs.

[5]   REQUIREMENTS:
      Development proposals with an expected soil disturbance in excess of 1ha must
      submit a conceptual ESCP to the regulatory authority for review and/or approval
      (as required by the regulatory authority) during planning negotiations.

      The area of disturbance refers to the total area of soil exposed to rainfall or dust-
      producing winds either as a result of:
        (a) the removal of ground cover vegetation, mulch or sealed surfaces;
        (b) past land management practices;
        (c) natural conditions.

      WARNINGS:
      A Sediment Basin will usually be required if the disturbed area exceeds 0.25ha
      (2500m2) within any sub-catchment (i.e. land flowing to one outlet point).

      COMMENTS:
      For soil disturbances greater than 0.25ha, the revegetation phase should be
      staged to minimise the duration for which soils are exposed to wind, rain and
      concentrated runoff.



IECA (Australasia)                           November 2008                          Page 5

Page 17

Best Practice Erosion And Sediment Control                   Erosion Hazard Assessment Form


[6]   REQUIREMENTS:
      All developments that involve earthworks or construction within a natural
      watercourse (whether that watercourse is in a natural or modified condition) must
      submit a conceptual ESCP to the regulatory authority for review and/or approval
      (as required by the regulatory authority) during planning negotiations.

      Permits and/or licences may be required from the State Government, including
      possible submission of the ESCP to the relevant Government department.

[7]   REQUIREMENTS:
      No areas of soil disturbance shall be left exposed to rainfall or dust-producing
      winds at the end of a development without an adequate degree of protection
      and/or an appropriate action plan for the establishment of at least 70% cover.

      COMMENTS:
      Grass seeding without the application of a light mulch cover is considered the
      least favourable revegetation technique. A light mulch cover is required to
      protect the soil from raindrop impact, excessive temperature fluctuations, and the
      loss of essential soil moisture.

[8]   COMMENTS:
      All receiving waters can be adversely affected by unnatural quantities of
      sediment-laden runoff. Freshwater ecosystems are generally more susceptible to
      ecological harm resulting from the inflow of fine or dispersible clays than saline
      water bodies. The further inland a land disturbance is, the greater the potential
      for the released sediment to cause environmental harm as this sediment travels
      towards the coast.

      For the purpose of this clause it is assumed that all sediment-laden runoff will
      eventually flow into saline waters. Thus, sediment-laden discharges that flow first
      into freshwater are likely to adversely affect both fresh and saline water bodies
      and are therefore considered potentially more damaging to the environment.

      This clause does not imply that sediment-laden runoff will not cause harm to
      saline waters.

[9]   COMMENTS:
      This clause refers to subsoils exposed during the construction phase either as a
      result of past land practices or proposed construction activities. The exposure of
      subsoils resulting from the excavation of minor service trenches should not be
      considered.

[10] WARNINGS:
     The greater the extent of external catchment, the greater the need to divert up-
     slope stormwater runoff around any soil disturbance.

      COMMENTS:
      The ability to separate “clean” (i.e. external catchment) stormwater runoff from
      “dirty” site runoff can have a significant effect on the size, efficiency and cost of
      the temporary drainage, erosion, and sediment control measures.




IECA (Australasia)                           November 2008                          Page 6

Page 18

Best Practice Erosion And Sediment Control                   Erosion Hazard Assessment Form


[11] REQUIREMENTS:
     Permission must be obtained from the owner of a road reserve before placing
     any erosion and sediment control measures within the road reserve.

      WARNINGS:
      Few sediment control techniques work efficiently when placed on a road and/or
      around roadside stormwater inlets. Great care must be taken if sediment control
      measures are located on a public roadway, specifically:
       • safety issues relating to road users;
       • the risk of causing flooding on the road or within private property.

      The construction of roads (whether temporary or permanent) will usually modify
      the flow path of stormwater runoff. This can affect how “dirty” site runoff is
      directed to the sediment control measures.

      COMMENTS:
      “On-road” sediment control devices are at best viewed as secondary or
      supplementary sediment control measures. Only in special cases and/or on very
      small projects (e.g. kerb and channel replacement) might these controls be
      considered as the “primary” sediment control measure.

[12] WARNINGS:
     Soils with a pH less than 5.5 or greater than 8 will usually require treatment in
     order to achieve satisfactory revegetation. Soils with a pH of less than 5
     (whether naturally acidic or in acid sulfate soil areas) may also limit the choice of
     chemical flocculants (e.g. Alum) for use in the flocculation of Sediment Basins.

[13] REQUIREMENTS:
     A preliminary ESCP must be submitted to the local government for approval
     during the planning phase for any development that obtains a total point score of
     17 or greater or when any trigger value is scored or exceeded.




IECA (Australasia)                           November 2008                          Page 7

Page 19

App end ix B – F lood I nf or ma t io n Ce rt ifi ca t e




                                                           C-1


[OCR of page images]
Us WESTERA
PARTNERS

 

Appendix B — Flood Information Certificate

Page 20

Noosa Council documents




            Flood Information Certificate
            This certificate is issued in response to an information request for a property which is located within the
            geographical boundaries of Noosa Council.

            Applicants Name            Adapt Town Planning +                Issue Date                14 July 2021
                                       Development Management
            Applicants                 PO Box 7618                          Property Number
                                                                                                      137114
            Address                    SIPPY DOWNS QLD 4556
                                                                            Property
                                                                                                      Lot 8 RP 113358
                                                                            Description
                                                                            Address                   183 Weyba Rd
                                                                                                      Noosaville Qld 4566
                                                                            Our Reference             Cer21/2699
            Email Address              [email protected]   Issuing Officer           Mark Lewis
                                                                            Your Reference            20210417

            This certificate is issued in response to an enquiry for the above property:

            REGISTERED OWNER/S NAME:                                                                                      MM Mbye
            DEFINED FLOOD LEVEL:                                                                                          2.4m AHD
            DEFINED FLOOD EVENT:                                              1% AEP Under 2100 Climate Change Conditions
            SOURCE OF INFORMATION:                                                 Noosa River Flood Study 2016, WMA Water
            HIGHEST HISTORICAL FLOOD                                        A flood level has not been recorded for this property
            LEVEL:
            LOCATION DESCRIPTION OF
                                                                            A flood level has not been recorded for this property
            RECORDED HISTORICAL EVENT:
            DATE OF HISTORICAL EVENT:                                       A flood level has not been recorded for this property
            FREEBOARD:                                                                                                          0.3m
            APPLICABLE MINIMUM FLOOR
            LEVEL FOR HABITABLE ROOM /
                                                                                  *2.7m AHD (as required by The Noosa Plan)
            AREA:
                                   THIS CERTIFICATE IS VALID FOR 6 MONTHS FROM DATE OF ISSUE.


            *Velocity note:
            The subject property is located in an active water flow area and the velocity of the water is up to approximately
            0.3m/s for the 1% AEP Defined Flood Event.




            www.noosa.qld.gov.au                  [email protected]              T 07 5329 6500
            PO Box 141 Tewantin Qld 4565                                             ABN 97 969 214 121
            Flood Information Certificate (FSCV3-0809)                                                               Page 1 of 3
Document Set ID: 21526047
Version: 2, Version Date: 14/07/2021                                                                           Print Date: 14 July 2021, 2:10 PM

Page 21

Noosa Council documents




            CLIMATE CHANGE
            The advice provided in this certificate is based upon information relating to historically recorded flood events and
            future climate condition. The defined flood event incorporates an allowance for climate change for the 1% AEP at
            year 2100. Climate change projections include increased rainfall intensity, higher mean sea level and more
            extreme weather conditions (e.g. storm surge and tropical cyclones).
            NOTES FOR FLOOD INFORMATION
            1.    The absence of Highest Historical Flood Level information does not imply that the above property is not
                  subject to flooding, simply that Council has no record of this property flooding. Applicants are encouraged to
                  make their own local enquiries.
            2.    In accordance with the Low Density Housing Code, the MINIMUM FLOOR LEVEL is calculated as
                  whichever is greater of either:
                   (a)    300mm freeboard added to the Defined Flood Event for the site; or
                   (b)    500 mm freeboard added to the Highest Historical Flood Level appropriate to the site; or
                   (c)    If the property is intended for use as a Hospital, Aged Residential Care Facility or Emergency
                          Services Facility then the Council should be contacted to determine this level.
            3.    Council advises that if stormwater drainage pipelines/easements exist on the property then no earthworks or
                  building are permitted in the easement.
            4.    All buildings shall conform to the relevant Planning Scheme Code in The Noosa Plan.
            5.    Please be aware of the natural topography in your area. Water runoff which exceeds the capacity of the
                  underground drainage system (if present) and which concentrates in surface depressions and gullies as it
                  flows down a catchment can cause localised flooding and is not identified in this certificate.
            6.    Filling must not cause actionable nuisance in accordance with Queensland Urban Drainage Manual.
            7.    Council advises that if there are openings to basements these openings require a minimum level at least
                  equal to the minimum floor level.
            8.    Please be aware that the reported flood information may vary in the future as new data becomes available.
            9.    Flood Hazard Maps within Council’s planning scheme are indicative only and should not be relied upon as a
                  guide to potential flooding.




            www.noosa.qld.gov.au               [email protected]               T 07 5329 6500
            PO Box 141 Tewantin Qld 4565                                           ABN 97 969 214 121
            Flood Information Certificate (FSCV3-0809)                                                          Page 2 of 3
Document Set ID: 21526047
Version: 2, Version Date: 14/07/2021                                                                       Print Date: 14 July 2021, 2:10 PM

Page 22

Noosa Council documents




            DISCLAIMERS
            Flood information provided by Council should only be used as a guide to the extent of flooding on the property. This
            information may be inaccurate or incomplete and it is recommended that purchasers make their own local enquiries with
            regard to the flooding and drainage history of the site. NO LIABILITY IS ACCEPTED FOR THIS INFORMATION.
            The property information supplied does not represent the highest probable flood level that could occur on this property. A flood
            more severe than the level described above may occur, although such events would be extraordinary.
            The absence of flood information does not imply that the above property is not subject to flooding, simply that Council has no
            flood information for this property flooding.
            If there is a history of flooding or drainage issues, we recommend you seek professional advice on this matter.
            COUNCIL ACCEPTS NO RESPONSIBILITY FOR THE ACCURACY OF THIS INFORMATION
            GLOSSARY OF TERMS
                        Term                                                          Definition
                                           The Australian Height Datum (AHD) is the reference level for defining reduced levels
            AHD                            adopted by the National Mapping Council of Australia. The level of 0.0 m AHD is
                                           approximately mean sea level.
            Defined Flood Level            A water level derived through mathematical modelling of the Defined Flood Event.
                                           Terminology consistent with State Planning Policy (SPP, 2003) which states “Defined Flood
            Defined Flood Event            Event is the flood event adopted by a local government for the management of development
                                           in a particular locality”.
                                           The Annual Exceedance Probability is the likelihood of occurrence of a flood or storm tide
                                           inundation event of a given size or larger in any one year, usually expressed as a
                                           percentage. For example, if an event has an AEP of 1%, it means that there is a 1% risk
            1% AEP                         (i.e. probability of 0.01 or a likelihood of 1 in 100) of this event occurring in any one year. A
                                           1% AEP event should not be interpreted as only occurring once in 100 years.
                                           This flood event is also commonly called the 100 year ARI (Average Recurrence Interval) or
                                           Q100.
                                           Is a reference to the document summarising the results of the anticipated flooding relevant
            Source of Information
                                           to this location.
            Highest Historical Flood
                                           The highest flood water level from all historic events for which Council has records.
            Level
            Location Description of
                                           A description of the site where the Highest Historical Flood Level was recorded.
            Recorded Historical Event
            Date of Historical Event       The date on which the Highest Historical Flood Level occurred.
                                           The minimum floor level calculated in accordance with the Town Plan through the addition
            Minimum Floor Level            of the relevant freeboard to the Defined Flood Level and the Highest Historical Flood Level.
                                           Council requires that the higher of these two levels be used as the minimum floor level.
                                           A factor of safety usually expressed as a height above the adopted Defined Flood Level. A
            Freeboard                      freeboard tends to compensate for factors such as wave action and historical and modelling
                                           uncertainties.
                                           In a residential situation: a living or working area, such as a lounge room, dining room,
            Habitable Room/Area
                                           rumpus room, kitchen, bedroom or workroom.
                                           Where a ‘regulation line’ has been set by Council to define the limit to which development
            Flood Regulation Line
                                           may encroach onto a floodplain, development is undertaken outside such ’regulation line’.
            Rainfall Intensity             The amount of rainfall occurring in a unit of time, usually expressed in millimetres/hour.
                                           A tidal datum; the arithmetic mean of hourly heights of the sea at the tidal station observed
            Mean Sea Level
                                           over a period of time (preferably 19 years). Source: BOM This is approximately 0.0 m AHD
                                           The elevation of water generated by a tropical cyclone above or below the normal
            Storm Surge
                                           astronomical tide.
                                           A tropical cyclone is a low-pressure system which develops in the tropics and is sufficiently
            Tropical Cyclones              intense to produce sustained winds of at least 63 km/h or greater and gusts in excess of 90
                                           km/h near the centre.




            www.noosa.qld.gov.au                   [email protected]                    T 07 5329 6500
            PO Box 141 Tewantin Qld 4565                                                    ABN 97 969 214 121
            Flood Information Certificate (FSCV3-0809)                                                                       Page 3 of 3
Document Set ID: 21526047
Version: 2, Version Date: 14/07/2021                                                                                   Print Date: 14 July 2021, 2:10 PM

Page 23

App end ix C – Eng in e er ing Pl an s




                                         C-1


[OCR of page images]
Us WESTERA
PARTNERS

 

Appendix C —- Engineering Plans

Page 24

                                                                                                                                                                                                                                                                                                           LEGEND




                         WEYBA ROAD




                                                                                                                                                                                     ROOF
                                                                                                                                                                                   CATCHMENT
                                                                                                                                                                                    TO STUB




                                                                                                       STORMWATER MANAGEMENT PLAN




                          DOCUMENT CONTROL   APPROVED                                                                                         SUNSHINE COAST                               GOLD COAST           SURVEYOR                                                                                      DRAWING STATUS
                                                                                                                                     Suite 2, Norval Corporate Centre,                           Level 3
                                                                                                                                                                                                                                                                                                PROJECT
                          DESIGNED                                                                                                         13 Norval Ct, Maroochydore             17 Welch St, Southport
                                                                                                                                    T 07 5391 3777 F 07 5646 5857      T 07 5571 1599 F 07 5571 1330
                          DRAWN                                                                                             E [email protected] E [email protected]                                                                                           LOCATION      DRAWING NUMBER

                          CHECKED                                                      PARTNERS                                                        BRISBANE                     NORTHERN NSW USE FIGURED DIMENSIONS ONLY. DO NOT SCALE, IF A DISCREPANCY ARISES CHECK WITH THE

                          DATE               For and on behalf of                                                                                 Level 2 Limestore,
                                                                                                                                                                                                 PROJECT ENGINEER AND/OR SUPERVISING AUTHORITY. DO NOT WORK FROM REDUCED SCALE
                                                                                                                                                                                                  Suite 24,    DRAWINGS (A1-A3 SIZE PAPER). COPYRIGHT OF ALL DRAWINGS & WORKS EXECUTED FROM     TITLE         SHEET NUMBER     REVISION
                                             WESTERA PARTNERS PTY. LTD.                                                                    33 Longland St, Newstead           11-13 Pearl Street, Kingscliff   THEM IS VESTED IN WESTERA PARTNERS AND USE OF THERE FORE WITHOUT PERMISSION IS
                                                                                                                                   T 07 3852 4333 F 07 3852 4777       T 02 6674 8047 F 02 6674 8049           STRICTLY PROHIBITED! IT IS THE BUILDERS RESPONSIBILITY TO ENSURE ALL WORKS ARE
No.   DATE   REVISIONS    FILE NAME                                       www.westerapartners.com.au   ABN 52 097 417 975        E [email protected]       E [email protected]          CARRIED OUT WITH DUE CARE AND DILIGENCE TO COMPLY WITH THE CONTRACT DOCUMENTS.   CLIENT

Page 25

App end ix D – Si t e Su rv e y & A rc hit ec tu ra l Dr aw ing s




                                                                    D-1


[OCR of page images]
Us WESTERA
PARTNERS

 

Appendix D — Site Survey & Architectural Drawings

Page 26

Skyline Surveyors
Suite 11C
Brightwater Corporate Centre   PHONE
                               07 5493 4877
69 Attenuata Drive
MOUNTAIN CREEK QLD 4557
E: [email protected]
W: www.skysurv.com.au

Page 27

         183 WEYBA RD
                                                                                                                             ISSUE     DATE         DESCRIPTION        PROJECT:                                DRAWING:                        DRAWING NUMBER:              REVISION




     HIVE ARCHITECTURE
                                                                                                                             SD1       08/07/21     CONCEPT DESIGN
                                                                                                                             DD1       25/08/21     DEVELOPED DESIGN   183 WEYBA RD                            COVER PAGE                      A.00.01                        DD1
                                                                                                                                                                       NOOSAVILLE QLD 4566
                                                                                                                                                                                                               SCALE:             DATE:
                                                                                                                                                                       LOT 8 RP 113358
                                                                                                                                                                                                               1:1   @A3
                                                                                                                                                                                                                     NTS          25/08/2021
                                                                                                                                                                       CLIENT:               PROJECT NUMBER:
     w       w       w       .   h   i   v   e   a   r   c   h   i   t   e   c   t   u   r   e   .   c   o   m   .   a   u
                                                                                                                                                                       MBYE                  2115              SCHEMATIC DESIGN
GSPublisherVersion 0.0.100.100
                                                                                                                             NOT FOR CONSTRUCTION                                                                                                                © HIVE Architecture 2020

Page 28

                                                                                                            FLOOR AREAS
                                                                                                            GROUND FLOOR                                  FIRST FLOOR                     GFA                                   SITE COVER                                                LANDSCAPE                                          PRIVATE OPEN SPACE
                                                                                                            Ground Floor:                 59m²            First Floor:        73m²        Ground Floor:          59m²           Site Area:                       606m²                    Landscape area required: 242m2 (40%)               Acess off ground living:     >25m²
                                                                                                            Garage:                       51m²            Balcony:            6m²         First Floor:           73m²           Footprint:                       230m²                    Landscape area provided: 242m2 (40%)
                                                                                                            Total:                        124m²           Total:              83m²        Total:                 132m²          Total:                           38%                      Soft Lansdcape required:   145m²
                                                                                                                                                                                          Plot ratio:            0.43:1                                                                   Soft Lansdcape provided:   145m²


                                                                                                                                                                                                                                                            02




                                                                                                                                                                                                                                                                                                                                                                                                                                                              510
                                                                                                                                                                                                                                                                                                                                                                                                                                                9
                                                                                                                                                                                                                                                                                                                                                                                                                                                         RP136
                                                                                                                                         6,000                                                                                                                                                                                                                                                          6,000




                                                                                                                                                                                                                                                     S-06
                                                                                                                                        setback                                                                                                                                                                                                                                                        setback

                                                                                                                                                  8,000                              90                          6,200                                 90         1,600             90         1,300        90               4,460                  90                                       8,165

                                                                                                        1,200 190         800




                                                                             setback
                                                                              1,500
                                                                                                                                                                                                                                                                                                                                                                                                                  8




                                                                                                                                                          1,500
                                                                                                                                                                                                          BINS               CLOTHESLINE



                                                                                                                                                                                                                                                                                                                                                                                                      RP113358




                                                                                                                                                          90




                                                                                                                                                                                                                                                                                                                                                                                                                                        90
                                                                                                                                                                                                                                                                                                     WIP
                                                                                                                                                                                                                                                                                                                                 2,640


                                                                                                                                                                                                                                                                            bike
                                                                                                                                                                                                                                                                            store




                                                                                                                                                          6,100
                                                                                                                                                                                                                   GARAGE
                                                                                       10,058




                                                                                                                                                                                                                  49.58 m2
                                                                                                                                                                                                                                                                                                                       64.91 m2




                                                                                                                                                                                                                                                                                                                                                                                                                                        8,373
                                                                                                                                                                                                                                                                  PWD




                                                                                                                                                                                                                                                                                                                                                                                                                      POOL
                                                                                                                                                                                                                                                                                                                                                                                                                       5X3
                                                                                                                                                          90
                         R D




                                                                                                                                                          2,183
                         W E Y B A




                                                                                                                                                                                                                                                                                                                                                                                                                                                               510
                                                                                                                                                                                                                                                                                                                                                                                                                                                10
                                                                                                                                                                                                                                                                                                                                                                                                                                                          RP136
                                                                                                                                                          190




                                                                                                                                                                                                                                                                                                                                                                                                                                        190
                                                                                                                                                                         01




                                                                                                                                                                                                                                                                                                                                                                                                                                        03
                                                                                                                                                                                                                                                                                                                                                                                                                      POOL
                                                                                                                                                                                                                                                                                                                                                                                                                       5X3



                                                                                                                                                                                                                                                                  PWD
                                                                                       10,059




                                                                                                                                                                                                                   GARAGE



                                                                                                                                                                                                                                                                            bike
                                                                                                                                                                                                                                                                            store




                                                                                                                                                                                                                                                                                                  WIP




                                                                                                                                                                                                          BINS               CLOTHESLINE
                                                                                 setback
                                                                                  1,500




                                                                                                                                                                                                                                             ISSUE               DATE                    DESCRIPTION                   PROJECT:                                                   DRAWING:                                   DRAWING NUMBER:               REVISION




     HIVE ARCHITECTURE
                                                                                                                                                                                                                                             SD1                 08/07/21                CONCEPT DESIGN
                                                                                                                                                                                                                                             DD1                 25/08/21                DEVELOPED DESIGN              183 WEYBA RD                                               GROUND FLOOR PLAN                          A.01.01                         DD1
                                                                                                                                                                                                                                                                                                                       NOOSAVILLE QLD 4566
                                                                                                                                                                                                                                                                                                                                                                                  SCALE:             DATE:
                                                                                                                                                                                                                                                                                                                       LOT 8 RP 113358
                                                                                                                                                                                                                                                                                                                                                                                  1:100    @A3       25/08/2021
                                                                                                                                                                                                                                                                                                                       CLIENT:                                 PROJECT NUMBER:
     w       w       w          .    h   i   v   e   a   r   c   h   i   t   e    c        t    u   r   e     .   c   o   m     .   a    u
                                                                                                                                                                                                                                                                                                                       MBYE                                    2115               SCHEMATIC DESIGN
GSPublisherVersion 0.0.100.100
                                                                                                                                                                                                                                             NOT FOR CONSTRUCTION                                                                                                                                                                               © HIVE Architecture 2020

Page 29

                                                                                                                                                                                                                                        02
                                                                                                                                                                                                                                         17,395
                                                                                                                                6,000                               3,026                                                                              12,905                                                                           1,464                                        6,000




                                                                                                                                                                                                                                 S-06
                                                                                                                               setback                                                                                                                                                                                                                                              setback


                                                                                                                                6,000             1,035 90                         3,510            90   2,080      90                  3,500                     90                3,500                     90                3,320                 780                            6,000




                                                                                                                                                                                                                                                                                             2,175            90




                                                                                                                                                            1,500
                                                                                     setback




                                                                                                                                          2,013
                                                                                      2,000




                                                                                                                                                                                                                                                                                                                                                            2,000
                                                                                                                                                            90
                                                                                                                                          90




                                                                                                                                                                                                                                                                          FALL 5°




                                                                                                                                                                                                                                                                                                                                                            693
                                                                                                                                          500
                                                                                                                                                                            VOID




                                                                                                                                         90
                                                                                                                                          600
                                                                                                                                                                            SEAT             ROBE




                                                                                                                                                                                                                                                                                                                                                            3,280
                                                                                                                                                                                                           ENS
                                                                                                                                                                                                                                         BED 2                                         BED 3




                                                                                                                                          4,480
                                                                                                                                                   BALC.                             BED 1
                                                                                                                                                  5.97 m2




                                                                                                                                                                                                                                                                                                                                                                        7,963
                                                                                                                                                                                                           WIR




                                                                                                                                                                                                                                                                                                                                                            600
                                                                                                                                                                                                                                                                                                                         VOID




                                                                                                                                                                                                                                                                                                                                                            90
                                                                                                                                                                                                                                                73.22 m2


                                                                                                                                                                                                                                                                                            BATH
                                                                                                                                          90




                                                                                                                                                                                                                                                                                                                                                            3,300
                                                                                                                                                                                                                                                 skylights
                                                                                                                                                                                                                 VOID

                                                                                                                                                                                                                                                                                              skylight




                                                                                                                                                                                                                                                                                                                                                            190


                                                                                                                                                                                                                                                                                                                                                                        190
                                                                                                                                                     01




                                                                                                                                                                                                                 VOID




                                                                                                                                                                                                                                                                                                                                                                                                          03
                                                                                                                                                                                                                                                                                            BATH




                                                                                                                                                                                                                                                                                                                         VOID
                                                                                                                                                                                                           WIR




                                                                                                                                                   BALC.                             BED 1

                                                                                                                                                                                                                                         BED 2                                         BED 3
                                                                                                                                                                                                           ENS




                                                                                                                                                                            SEAT      ROBE




                                                                                                                                                                                                                                                                          FALL 5°
                                                                                                                                                                            VOID
                                                                                     setback
                                                                                      2,000




                                                                                                                                                                                                                         ISSUE              DATE                DESCRIPTION                        PROJECT:                                                    DRAWING:                        DRAWING NUMBER:              REVISION




     HIVE ARCHITECTURE
                                                                                                                                                                                                                         SD1                08/07/21            CONCEPT DESIGN
                                                                                                                                                                                                                         DD1                25/08/21            DEVELOPED DESIGN                   183 WEYBA RD                                                UPPER FLOOR PLAN                A.01.02                        DD1
                                                                                                                                                                                                                                                                                                   NOOSAVILLE QLD 4566
                                                                                                                                                                                                                                                                                                                                                               SCALE:             DATE:
                                                                                                                                                                                                                                                                                                   LOT 8 RP 113358
                                                                                                                                                                                                                                                                                                                                                               1:100    @A3       25/08/2021
                                                                                                                                                                                                                                                                                                   CLIENT:                                PROJECT NUMBER:
     w       w       w       .   h   i   v   e   a   r   c   h   i   t   e   c   t      u      r   e   .   c   o   m   .   a    u
                                                                                                                                                                                                                                                                                                   MBYE                                   2115                 SCHEMATIC DESIGN
GSPublisherVersion 0.0.100.100
                                                                                                                                                                                                                         NOT FOR CONSTRUCTION                                                                                                                                                                    © HIVE Architecture 2020

Page 30

                                                                                                                                                                                   02




                                                                                                                                                                            S-06
                                                                                                                                6,000                                                                                                                                                  6,000
                                                                                                                               setback                                                                                                                                                setback
                                                                                                                                6,000                      3,040                                      14,355                                                                       6,780




                                                                     setback
                                                                      2,000




                                                                                                                                                                                                         FALL 5°
                                                                                                                                             6,960
                                                                                                                                     7,960                FALL 5°




                                                                                                                                                                                          skylights

                                                                                                                                                                                                                         skylight
                                                                                                                                     190




                                                                                                                                                                                                                         skylight
                                                                                                                                                     01




                                                                                                                                                                                          skylights




                                                                                                                                                                                                                                                                                                               03
                                                                                                                                     7,960




                                                                                                                                                          FALL 5°




                                                                                                                                                                                                         FALL 5°
                                                                                                                                             6,960
                                                                     setback
                                                                      2,000




                                                                                                                                                                    ISSUE               DATE          DESCRIPTION           PROJECT:                                DRAWING:                        DRAWING NUMBER:               REVISION




     HIVE ARCHITECTURE
                                                                                                                                                                    SD1                 08/07/21      CONCEPT DESIGN
                                                                                                                                                                    DD1                 25/08/21      DEVELOPED DESIGN      183 WEYBA RD                            ROOF PLAN                       A.01.03                         DD1
                                                                                                                                                                                                                            NOOSAVILLE QLD 4566
                                                                                                                                                                                                                                                                    SCALE:             DATE:
                                                                                                                                                                                                                            LOT 8 RP 113358
                                                                                                                                                                                                                                                                    1:100    @A3       25/08/2021                     1:100 @
                                                                                                                                                                                                                            CLIENT:               PROJECT NUMBER:
     w       w       w       .   h   i   v   e   a   r   c   h   i    t        e   c   t   u   r   e   .   c   o   m   .   a    u
                                                                                                                                                                                                                            MBYE                  2115              SCHEMATIC DESIGN
GSPublisherVersion 0.0.100.100
                                                                                                                                                                    NOT FOR CONSTRUCTION                                                                                                                               © HIVE Architecture 2020

Page 31

                                                                                                            LANDSCAPING

                                                                                                                         Landscape area required: 242m2 (40%)
                                                                                                                         Landscape area provided: 242m2 (40%)
                                                                                                                         Soft Lansdcape required:     145m²
                                                                                                                         Soft Lansdcape provided:     145m²


                                                                                                                                                                                                                             02




                                                                                                                                                                                                                                                                                                                                                                                                           510
                                                                                                                                                                                                                                                                                                                                                                                             9
                                                                                                                                                                                                                                                                                                                                                                                                      RP136
                                                                                                                                          6,000                                                                                                                                                                                                      6,000




                                                                                                                                                                                                                      S-06
                                                                                                                                         setback                                                                                                                                                                                                    setback

                                                                                                                                                   8,000                90          6,200                               90         1,600             90         1,300        90         4,460           90                                8,165

                                                                                                        1,200 190          800




                                                                             setback
                                                                              1,500
                                                                                                                                                                                                                                                                                                                                                               8




                                                                                                                                                           1,500
                                                                                                                                                                             BINS               CLOTHESLINE



                                                                                                                                                                                                                                                                                                                                                   RP113358




                                                                                                                                                           90




                                                                                                                                                                                                                                                                                                                                                                                     90
                                                                                                                                                                                                                                                                      WIP
                                                                                                                                                                                                                                                                                            2,640


                                                                                                                                                                                                                                             bike
                                                                                                                                                                                                                                             store




                                                                                                                                                           6,100
                                                                                                                                                                                     GARAGE
                                                                                       10,058




                                                                                                                                                                                     49.58 m2
                                                                                                                                                                                                                                                                                  64.91 m2




                                                                                                                                                                                                                                                                                                                                                                                     8,373
                                                                                                                                                                                                                                   PWD




                                                                                                                                                                                                                                                                                                                                                                   POOL
                                                                                                                                                                                                                                                                                                                                                                    5X3
                                                                                                                                                           90
                         R D




                                                                                                                                                           2,183
                         W E Y B A




                                                                                                                                                                                                                                                                                                                                                                                                            510
                                                                                                                                                                                                                                                                                                                                                                                             10
                                                                                                                                                                                                                                                                                                                                                                                                       RP136
                                                                                                                                                           190




                                                                                                                                                                                                                                                                                                                                                                                     190
                                                                                                                                                                   01




                                                                                                                                                                                                                                                                                                                                                                                     03
                                                                                                                                                                                                                                                                                                                                                                   POOL
                                                                                                                                                                                                                                                                                                                                                                    5X3



                                                                                                                                                                                                                                   PWD
                                                                                       10,059




                                                                                                                                                                                     GARAGE



                                                                                                                                                                                                                                             bike
                                                                                                                                                                                                                                             store




                                                                                                                                                                                                                                                                   WIP




                                                                                                                                                                             BINS               CLOTHESLINE
                                                                                 setback
                                                                                  1,500




                                                                                                                                                                                                              ISSUE               DATE                    DESCRIPTION             PROJECT:                                     DRAWING:                                   DRAWING NUMBER:               REVISION




     HIVE ARCHITECTURE
                                                                                                                                                                                                              SD1                 08/07/21                CONCEPT DESIGN
                                                                                                                                                                                                              DD1                 25/08/21                DEVELOPED DESIGN        183 WEYBA RD                                 LANDSCAPE AREAS                            A.01.04                         DD1
                                                                                                                                                                                                                                                                                  NOOSAVILLE QLD 4566
                                                                                                                                                                                                                                                                                                                               SCALE:             DATE:
                                                                                                                                                                                                                                                                                  LOT 8 RP 113358
                                                                                                                                                                                                                                                                                                                               1:100    @A3       25/08/2021
                                                                                                                                                                                                                                                                                  CLIENT:                    PROJECT NUMBER:
     w       w       w          .    h   i   v   e   a   r   c   h   i   t   e    c        t    u   r   e    .   c   o     m     .   a    u
                                                                                                                                                                                                                                                                                  MBYE                       2115              SCHEMATIC DESIGN
GSPublisherVersion 0.0.100.100
                                                                                                                                                                                                              NOT FOR CONSTRUCTION                                                                                                                                                           © HIVE Architecture 2020

Page 32

                                                                                                        +8,725
                                                                                                 3 ROOF LEVEL




                                                                                                      +6,025
                                                                                             2 UPPER FLOOR




                                                                                                      +2,700
                                                                                             1 LOWER FLOOR




                                                                                01                                                    NORTH ELEVATION                                                                                                             1:100
                                                 Boundary




                                                                                                                                                                                                                          6,000




                                                                                                 6,000




                                                                                                                                                                                                   WB 01




                    02                                                                                                                 EAST ELEVATION                                                                                                                                       1:100




                                                                                                                                              ISSUE     DATE         DESCRIPTION        PROJECT:                                  DRAWING:                                DRAWING NUMBER:               REVISION




     HIVE ARCHITECTURE
                                                                                                                                              SD1       08/07/21     CONCEPT DESIGN
                                                                                                                                              DD1       25/08/21     DEVELOPED DESIGN   183 WEYBA RD                              ELEVATIONS                              A.04.01                         DD1
                                                                                                                                                                                        NOOSAVILLE QLD 4566
                                                                                                                                                                                                                                  SCALE:             DATE:
                                                                                                                                                                                        LOT 8 RP 113358
                                                                                                                                                                                                                                  1:100    @A3       25/08/2021
                                                                                                                                                                                        CLIENT:               PROJECT NUMBER:
     w       w       w       .   h   i   v   e   a          r   c   h   i   t   e    c   t   u    r   e   .   c   o   m   .   a   u
                                                                                                                                                                                        MBYE                  2115                SCHEMATIC DESIGN
GSPublisherVersion 0.0.100.100
                                                                                                                                              NOT FOR CONSTRUCTION                                                                                                                           © HIVE Architecture 2020

Page 33

                                                                                         +8,725
                                                                                  3 ROOF LEVEL




                                                                                       +6,025
                                                                              2 UPPER FLOOR




                                                                                       +2,700
                                                                              1 LOWER FLOOR




                                         03                                                                                          SOUTH ELEVATION                                                                                                                      1:100




                                                                                                                                                                                                                                                               Boundary
                                                                                  Boundary




                                                                                                                         6,000
                                                                                                                                                                                                                                              6,000




                         04                                                                                                          WEST ELEVATION                                                                                                                               1:100




                                                                                                                                             ISSUE     DATE         DESCRIPTION        PROJECT:                                DRAWING:                                    DRAWING NUMBER:              REVISION




     HIVE ARCHITECTURE
                                                                                                                                             SD1       08/07/21     CONCEPT DESIGN
                                                                                                                                             DD1       25/08/21     DEVELOPED DESIGN   183 WEYBA RD                            ELEVATIONS                                  A.04.02                        DD1
                                                                                                                                                                                       NOOSAVILLE QLD 4566
                                                                                                                                                                                                                               SCALE:             DATE:
                                                                                                                                                                                       LOT 8 RP 113358
                                                                                                                                                                                                                               1:100    @A3       25/08/2021
                                                                                                                                                                                       CLIENT:               PROJECT NUMBER:
     w       w       w       .   h   i   v    e   a   r   c   h   i   t   e   c   t          u   r   e   .   c   o   m   .   a   u
                                                                                                                                                                                       MBYE                  2115              SCHEMATIC DESIGN
GSPublisherVersion 0.0.100.100
                                                                                                                                             NOT FOR CONSTRUCTION                                                                                                                            © HIVE Architecture 2020

Page 34

                                                                                                                             ISSUE     DATE         DESCRIPTION        PROJECT:                                DRAWING:                        DRAWING NUMBER:              REVISION




     HIVE ARCHITECTURE
                                                                                                                             SD1       08/07/21     CONCEPT DESIGN
                                                                                                                             DD1       25/08/21     DEVELOPED DESIGN   183 WEYBA RD                            PERSPECTIVE VIEWS               A.09.01                        DD1
                                                                                                                                                                       NOOSAVILLE QLD 4566
                                                                                                                                                                                                               SCALE:             DATE:
                                                                                                                                                                       LOT 8 RP 113358
                                                                                                                                                                                                               N.T.S.
                                                                                                                                                                                                                  @A3             25/08/2021
                                                                                                                                                                       CLIENT:               PROJECT NUMBER:
     w       w       w       .   h   i   v   e   a   r   c   h   i   t   e   c   t   u   r   e   .   c   o   m   .   a   u
                                                                                                                                                                       MBYE                  2115              SCHEMATIC DESIGN
GSPublisherVersion 0.0.100.100
                                                                                                                             NOT FOR CONSTRUCTION                                                                                                                © HIVE Architecture 2020

Page 35

                                                                                                                             ISSUE     DATE         DESCRIPTION        PROJECT:                                DRAWING:                        DRAWING NUMBER:              REVISION




     HIVE ARCHITECTURE
                                                                                                                             SD1       08/07/21     CONCEPT DESIGN
                                                                                                                             DD1       25/08/21     DEVELOPED DESIGN   183 WEYBA RD                            PERSPECTIVE VIEWS               A.09.02                        DD1
                                                                                                                                                                       NOOSAVILLE QLD 4566
                                                                                                                                                                                                               SCALE:             DATE:
                                                                                                                                                                       LOT 8 RP 113358
                                                                                                                                                                                                               N.T.S.
                                                                                                                                                                                                                  @A3             25/08/2021
                                                                                                                                                                       CLIENT:               PROJECT NUMBER:
     w       w       w       .   h   i   v   e   a   r   c   h   i   t   e   c   t   u   r   e   .   c   o   m   .   a   u
                                                                                                                                                                       MBYE                  2115              SCHEMATIC DESIGN
GSPublisherVersion 0.0.100.100
                                                                                                                             NOT FOR CONSTRUCTION                                                                                                                © HIVE Architecture 2020

Page 36

                                                                                                                             ISSUE     DATE         DESCRIPTION        PROJECT:                                DRAWING:                        DRAWING NUMBER:              REVISION




     HIVE ARCHITECTURE
                                                                                                                             SD1       08/07/21     CONCEPT DESIGN
                                                                                                                             DD1       25/08/21     DEVELOPED DESIGN   183 WEYBA RD                            PERSPECTIVE VIEWS               A.09.03                        DD1
                                                                                                                                                                       NOOSAVILLE QLD 4566
                                                                                                                                                                                                               SCALE:             DATE:
                                                                                                                                                                       LOT 8 RP 113358
                                                                                                                                                                                                                 @A3              25/08/2021
                                                                                                                                                                       CLIENT:               PROJECT NUMBER:
     w       w       w       .   h   i   v   e   a   r   c   h   i   t   e   c   t   u   r   e   .   c   o   m   .   a   u
                                                                                                                                                                       MBYE                  2115              SCHEMATIC DESIGN
GSPublisherVersion 0.0.100.100
                                                                                                                             NOT FOR CONSTRUCTION                                                                                                                © HIVE Architecture 2020

Page 37

                                                                                                                             ISSUE     DATE         DESCRIPTION        PROJECT:                                DRAWING:                        DRAWING NUMBER:              REVISION




     HIVE ARCHITECTURE
                                                                                                                             SD1       08/07/21     CONCEPT DESIGN
                                                                                                                             DD1       25/08/21     DEVELOPED DESIGN   183 WEYBA RD                            PERSPECTIVE VIEWS               A.09.04                        DD1
                                                                                                                                                                       NOOSAVILLE QLD 4566
                                                                                                                                                                                                               SCALE:             DATE:
                                                                                                                                                                       LOT 8 RP 113358
                                                                                                                                                                                                                 @A3              25/08/2021
                                                                                                                                                                       CLIENT:               PROJECT NUMBER:
     w       w       w       .   h   i   v   e   a   r   c   h   i   t   e   c   t   u   r   e   .   c   o   m   .   a   u
                                                                                                                                                                       MBYE                  2115              SCHEMATIC DESIGN
GSPublisherVersion 0.0.100.100
                                                                                                                             NOT FOR CONSTRUCTION                                                                                                                © HIVE Architecture 2020

Page 38

                                                                                                                             ISSUE     DATE         DESCRIPTION        PROJECT:                                DRAWING:                        DRAWING NUMBER:              REVISION




     HIVE ARCHITECTURE
                                                                                                                             SD1       08/07/21     CONCEPT DESIGN
                                                                                                                             DD1       25/08/21     DEVELOPED DESIGN   183 WEYBA RD                            PERSPECTIVE VIEWS               A.09.05                        DD1
                                                                                                                                                                       NOOSAVILLE QLD 4566
                                                                                                                                                                                                               SCALE:             DATE:
                                                                                                                                                                       LOT 8 RP 113358
                                                                                                                                                                                                                 @A3              25/08/2021
                                                                                                                                                                       CLIENT:               PROJECT NUMBER:
     w       w       w       .   h   i   v   e   a   r   c   h   i   t   e   c   t   u   r   e   .   c   o   m   .   a   u
                                                                                                                                                                       MBYE                  2115              SCHEMATIC DESIGN
GSPublisherVersion 0.0.100.100
                                                                                                                             NOT FOR CONSTRUCTION                                                                                                                © HIVE Architecture 2020

Page 39

                                                                                                                             ISSUE     DATE         DESCRIPTION        PROJECT:                                DRAWING:                        DRAWING NUMBER:              REVISION




     HIVE ARCHITECTURE
                                                                                                                             SD1       08/07/21     CONCEPT DESIGN
                                                                                                                             DD1       25/08/21     DEVELOPED DESIGN   183 WEYBA RD                            PERSPECTIVE VIEWS               A.09.06                        DD1
                                                                                                                                                                       NOOSAVILLE QLD 4566
                                                                                                                                                                                                               SCALE:             DATE:
                                                                                                                                                                       LOT 8 RP 113358
                                                                                                                                                                                                                 @A3              25/08/2021
                                                                                                                                                                       CLIENT:               PROJECT NUMBER:
     w       w       w       .   h   i   v   e   a   r   c   h   i   t   e   c   t   u   r   e   .   c   o   m   .   a   u
                                                                                                                                                                       MBYE                  2115              SCHEMATIC DESIGN
GSPublisherVersion 0.0.100.100
                                                                                                                             NOT FOR CONSTRUCTION                                                                                                                © HIVE Architecture 2020

Page 40

                                                                                                                             ISSUE     DATE         DESCRIPTION        PROJECT:                                DRAWING:                        DRAWING NUMBER:              REVISION




     HIVE ARCHITECTURE
                                                                                                                             SD1       08/07/21     CONCEPT DESIGN
                                                                                                                             DD1       25/08/21     DEVELOPED DESIGN   183 WEYBA RD                            PERSPECTIVE VIEWS               A.09.07                        DD1
                                                                                                                                                                       NOOSAVILLE QLD 4566
                                                                                                                                                                                                               SCALE:             DATE:
                                                                                                                                                                       LOT 8 RP 113358
                                                                                                                                                                                                                 @A3              25/08/2021
                                                                                                                                                                       CLIENT:               PROJECT NUMBER:
     w       w       w       .   h   i   v   e   a   r   c   h   i   t   e   c   t   u   r   e   .   c   o   m   .   a   u
                                                                                                                                                                       MBYE                  2115              SCHEMATIC DESIGN
GSPublisherVersion 0.0.100.100
                                                                                                                             NOT FOR CONSTRUCTION                                                                                                                © HIVE Architecture 2020