AS 1428.1—2009 102
B4 DETERMINATION OF LUMINANCE CONTRAST
This Paragraph sets out a method for using the luminous reflectance values to
calculate the required minimum luminance contrast between two adjacent or
contiguous surfaces when the luminous reflectance of the products are known, and
is based on the following equation:
C = 125 (Y 2 − Y 1)/(Y 1 + Y2 + 25) = 30
where
C = luminance contrast
Y 1 = darker surface
Y 2 = lighter surface
The full set of limits is shown in Table B1.
The luminous reflectance of the building elements has to lie above or below the
lines illustrating the minimum and maximum luminous reflectance necessary, as
shown in Figure B1.
TABLE B1
VALUES OF LUMINOUS REFLECTANCE REQUIRED
TO PROVIDE ADEQUATE LUMINANCE CONTRAST
AS A FUNCTION BETWEEN BUILDING ELEMENTS
Minimum luminous Maximum luminous
Luminous
reflectance of a reflectance of a
reflectance of the
possible lighter possible darker
building element
building element building element
95 — 53
90 — 50
85 — 47
80 — 44
75 — 41
70 — 38
65 — 35
60 — 31
55 96 28
50 90 25
45 82 22
40 74 19
35 65 16
30 57 13
25 49 10
20 41 7
15 33 4
10 25 1
© Standards Australia www.standards.org.au