AS 1428.1—2009 86
15.6 Circulation spaces in accessible sanitary facilities
The circulation spaces in accessible sanitary facilities shall be in accordance with
Clause 15.2.8 and Figures 43 to 47 and 50. The following also apply:
(a) Circulation spaces, including door circulation spaces, may be overlapped.
(b) With the following exceptions, fixtures shall not encroach into circulation
spaces:
A1 (i) The washbasin may encroach into the WC circulation space in
accordance with Figure 43 and 50.
A1
(ii) ‘deleted’
(iii) The washbasin may encroach into the circulation space of the door in
accordance with Figures 51(A) and 51(B).
NOTE: An example of an overlapping circulation space in a sanitary
compartment is shown in Figure 52.
Clearances beneath the washbasin shall be in accordance with Clause 15.3 and
door circulation spaces shall be in accordance with Clause 13.3 modified in
accordance with Item (b)(ii) or (b)(iii) of this Clause, if appropriate.
A1
DIMENSIONS IN MILLIMETRES
FIGURE 50 SANITARY COMPARTMENT SHOWING OVERLAP OF WASHBASIN
FIXTURE INTO SHOWER CIRCULATION SPACE
© Standards Australia www.standards.org.au