EngineeringLetter 151082 5-7-2015 7-32 AM

Attached to the e-mail Mens Shed Building Plans For Approval.

of 4

Page text shows just the words. Original shows the document exactly as it was published.

                                                                                PO BOX 590,
                                                                                ROBINA, QLD 4226.
                                                                                PH: 07 5578 8088
                                                                                FAX: 07 5578 9429


07 May, 2015

To whom it may concern
  The actual usage of the building is not able to be finalised by the engineer. This certification is done
  in accordance with the purchaser of the building's advice of the building's Importance Level. Any
  approving authority should confirm that the Importance Level nominated is appropriate for the
  building's usage.
The structural design of the steel building (as detailed in drawing WSS151082, see index below) for Mens Shed
Pomona to be built at the geographic coordinates of -26.36804 and 152.85349. The address of the site has been
given as School Street POMONA QLD Australia 4568 has been carried out by me using the Multiframe
Structural Engineering Analysis Program.
The design has been done in accordance with the NCC:2015, AS/NZS 4600:2005, AS/NZS 1170.1:2002,
AS/NZS 1170.2:2011, AS 4055:2006, AS 4100:1998, AS 2870:2011 and AS 3600:2009.

Design Criteria: Max Design Wind Speed of 45 m/s. Refer to Design Information Sheet for the 8 cardinal
directions breakdown.
         Drawing Number                             Date                                      Description

         WSS151082 - 2                              07/05/2015                                General Notes
         WSS151082 - 3                              07/05/2015                                Layout
         WSS151082 - 4                              07/05/2015                                Specification Sheet
         WSS151082 - 5                              07/05/2015                                Bracing
         WSS151082 - 6                              07/05/2015                                Concrete Piers
         WSS151082 - 7                              07/05/2015                                Slab Dimensions
         WSS151082 - 8                              07/05/2015                                Connection Details
         WSS151082 - 9                              07/05/2015                                Flashing Fixing Details


Some drawings have multiple pages, eg. "1 of 3".

Signed




R. J. Showers
for and on behalf of
SHOWERS ENGINEERING PTY LTD
(ACN 075 007 144)




      Member Institution of Engineers (Aust.), CPEng (NPER Structural & Civil) Regn. No. 321787
      Registered Professional Engineer (Structural & Civil) - Queensland: Regn. No. 1547
      Registered Professional Engineer (Structural & Civil) - Victoria: Regn. No. EC24162
      Registered Building Designer & Professional Engineer (Structural & Civil) - Tasmania: Regn. No. CC4600H
Log in to download the original file

EngineeringLetter 151082 5-7-2015 7-32 AM.pdf · 204 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

Full text of the other 3 pages

Page 2

                                                                                                             Version 3 – March 2013

      Form 15—Compliance Certificate for building Design or Specification
NOTE                                   This is to be used for the purposes of section 10 of the Building Act 1975 and/or
                                       section 46 of the Building Regulation 2006.

                                       RESTRICTION: A building certifier (class B) can only give a compliance
                                       certificate about whether
                                       building work complies with the BCA or a provision of the QDC. A building
                                       certifier (Class B) can


1. Property descript                   Street address(include no., street, suburb / locality & postcode)
This section need only be
                                       School Street POMONA QLD Australia 4568
completed if details of street
address and property                                                                                       Postcode
description are applicable             Lot & plan        (attach list if necessary)
EG. In the case of
                                       details
(standard/generic) pool
design/shell manufacture and/or        In which local government area is the land situated?
The description must identify all
land the
subject of the application.

The lot & plan details (eg. SP / RP)
are
shown on title documents or a

2. Description of component/s
                                        Steel framed building and foundations as described in drawings referenced
certified
Clearly describe the extent of
work covered by this certificate,       Job# 151082
e.g. all structural aspects of the
steel roof beams.




3. Basis of certification
                                        As per attached letter for Brian Lawson at School Street, POMONA, QLD,
Detail the basis for giving the
certificate and the extent to           Australia, 4568 for job number 151082
which tests, specifications,
rules,
standards, codes of practice and




      LOCAL GOVERNMENT USE ONLY

         Date received                                                     Reference Number/s

Page 3

4. Reference documentation
                                       Covering letter of certification.
Clearly identify any relevant
documentation, e.g. numbered
structural engineering plans.
                                       WSS151082 - 2                             General Notes

                                       WSS151082 - 3                             Layout

                                       WSS151082 - 4                             Specification Sheet

                                       WSS151082 - 5                             Bracing

                                       WSS151082 - 6                             Concrete Piers

                                       WSS151082 - 7                             Slab Dimensions

                                       WSS151082 - 8                             Connection Details

                                       WSS151082 - 9                             Flashing Fixing Details




5. Building certifier reference nu   Building certifier reference number

                                       N/A


6. Competent person details          Name (in full)
A competent person for building
work, means a person who is
                                       Robert James Showers, Director
assessed by the building
                                     Company name      (if applicable)                             Contact person
certifier for the work as
                                       Showers Engineering Pty Ltd
competent to practise in an
                                       (ACN 075007144)                                                Robert Showers
aspect of the building and
specification design, of the         Phone no. business hours                   Mobile no.                           Fax No.
building work because of the
                                       07 55788088                                0407 147 253                        07 55789429
individual's skill, experience and
qualifications in the aspect. The    Email address
competent person must also be
registered or licensed under a         [email protected]
law applying in the State to
practice the aspect.                 Postal address

                                       PO BOX 590, Robina D.C, QLD.
If no relevant law requires the
individual to be licensed or                                                                       Postcode          4226
registered to be able to give the
help, the certifier must assess      Licence or registration number        (if applicable)
the individual as having
                                       RPEQ 1547
appropriate experience,

7. Signature of competent perso
This certificate must be signed
by the individual assessed by        Signature                                                                Date
the building certifier as
                                                                                                                7-5-2015

Page 4

Design Information Sheet
Building Details
                       Item                                                                Design Value
 Building Description                                Portal Design Steel Frame and Steel Clad Building
 Job Reference #                                     WSS151082
 Site Address                                        School Street POMONA QLD 4568
 Building Classification                             Class 10
 Effective Design Height                             3.43 m
                                                     Main Building                        Left Leanto     Right Leanto
 Length                                              12m                                  NA              NA
 Bay Size                                            3 evenly spaced                      NA              NA
 Span                                                8m                                   NA              NA
 Roof Pitch                                          12 degrees                           NA              NA

Pressure Coefficients
                 Item                      Design Value                    Reference
 Internal Pressure coefficient CPI         0, -0.3                 AS/NZS 1170.2 Clause 5.3
 Windward Wall (External Across)           0.7                     AS/NZS 1170.2 Table 5.2 (A)
 Windward Rafter (External Across)         -0.76, -0.31            AS/NZS 1170.2 Table 5.3 (B)
 Leeward Rafter (External Across)          -0.47                   AS/NZS 1170.2 Table 5.3 (C)
 Leeward Wall (External Across)            -0.3                    AS/NZS 1170.2 Table 5.2 (B)
 Side Wall (External Along)                -0.65                   AS/NZS 1170.2 Table 5.2 (C)
 Rafters (External Along)                  -0.9, -0.4              AS/NZS 1170.2 Table 5.3 (A)
 Local Pressures Applied                   Yes                     AS/NZS 1170.2 Table 5.6

Site Classification
                Item                  N          NE            E     SE        S   SW       W      NW
 Wind Region                         B
 Importance level                    2
 Terrain Category                    3           3         3        3      3       3       3       3
 Shielding Multiplier (Ms)           0.9         0.9       1        1      1       1       0.95    0.9
 Topographic Multiplier (Mt)         1           1         1        1      1       1       1       1
 Wind Direction Multiplier (Md)      0.95        0.95      0.95     0.95   0.95    0.95    0.95    0.95
 Design Wind Speed                   45 m/s
 Snowload Factor                     0kPa
 Seismic Factor (Z)                  NA