RFI - D - Civil Engineering Response
Indicative Garage Level Drainage Site Drainage is typically developed in coordination with other consultants where their input is required in detailed design phase. The above calculations are provided to demonstrate that there are suitable ways of managing any major storm surface flows around that building without impacting on the neighbouring properties or incurring local flooding inside the proposed dwellings. Final design coordination of this can be conditioned for certification by a hydraulic designer or RPEQ engineer as part of a Decision Notice. ISSUES 14 An existing Unitywater sewer main runs across the site adjacent to the rear boundary and the proposed works have the potential to impact on the sewer main and its ongoing maintenance. The submitted material does not demonstrate how the proposed development achieves The Existing Services - Specific Outcomes O1 and O2 Information Required: Provide written approval for the proposed works from Unitywater RESPONSE The position of the buildings with respect to the Unitywater sewer main along the rear boundary are addressed under the Queensland Development Code QDCMP1.4 (Dec 2013). The QDC is applied to a development in accordance with the Qld Building Act 1975 and Building Regulation. The provisions of the QDC are currently met as demonstrated by the below excerpt from the architectural drawings, highlighting the distance from the sewer to the building. It is acknowledged that the swimming pools may need to be shifted to comply with the QDC, 2008 – Margit Cres, Sunrise Beach 6 CL/cl
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalSearchable page text hides email addresses. Original files are unchanged and may show email addresses.