Approved Plans - MCU22-0017 · MCU22/0017

Plans and drawings: the text below has words only, no drawings.

Log in to see the plans as drawn
                                                                                                              GENERAL                                                                                                           DIMENSIONS/LEVELS                                                                                                    CONSTRUCTABILITY CONSTRAINTS:
                                                                                                              G1    STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE                                                   L1.       CONSTRUCTION SHALL BE SET OUT USING SURVEY BENCHMARKS PROVIDED BY COUNCIL.                                 CC1. CONSTRUCTABILITY CONSTRAINTS:
                                                                                                                    SPECIFICATION, ARCHITECTURAL, AND OTHER CONSULTANTS' DOCUMENTS.
                                                                                                                                                                                                                                L2. ALL LEVELS AND SETOUT POINTS ARE SHALL BE CONFIRMED ON SITE BY REGISTERED                                             A)   PROTECT ALL EXISTING INFRASTRUCTURE (EG CULVERT CROSSING, PAVEMENTS,
                                                                                                              G2    REFER TO THE ARCHITECTURAL DRAWINGS FOR SETOUT. NO DIMENSIONS SHALL BE                                      SURVEYOR PRIOR TO CONSTRUCTION. ADVISE ANY DISCREPANCY BEFORE PROCEEDING.                                                      FENCING & ELECTRICAL POLES/WIRES) FROM ANY DAMAGE.
                                                                                                                    OBTAINED BY SCALING FROM DRAWINGS.
                                                                                                                                                                                                                                L3.       DIMENSION STANDARDS:                                                                                         B)      ALLOW OF LIKELIHOOD OF FLOW WITHIN THE WATERWAY: EXISTING WATERWAY ARE
                                                                                                              G3    UNLESS OTHERWISE NOTED (UNO), ALL LEVELS ARE IN METRES AND ALL DIMENSIONS ARE IN                                      - REDUCED LEVELS, CHAINAGES AND COORDINATES ARE ALL IN METRES.                                                       FLOODED MULTIPLE TIMES PER YEAR. PROTECT CONSTRUCTION EQUIPMENT AND
                                                                                                                    MILLIMETRES.                                                                                                          - CIVIL DRAWINGS (SKC SERIES): ALL OTHER DIMENSIONS ARE IN METRES (m).                                               WORKS.
                                                                                                                                                                                                                                          - STRUCTURAL DRAWINGS (SKS SERIES): ALL OTHER DIMENSIONS ARE IN MILLIMETRES (mm).
                                                                                                              G4    THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE STABILITY OF THE                                                                                                                                                         CC2. NO WORK TO COMMENCE ON SITE UNTIL:
                                                                                                                    STRUCTURE UNTIL ITS COMPLETION AND SHALL ENSURE THAT NO PART OF THE STRUCTURE                               L4.       ALL LEVELS ARE TO AUSTRALIAN HEIGHT DATUM.                                                                      - OFFICIAL PRE-START MEETING HELD AND PRE-START MEETING MINUTES ISSUED
                                                                                                                    IS OVER-STRESSED BY EXCESSIVE LOADING.                                                                                                                                                                                                - CONTRACTOR'S MANAGEMENT PLANS SUBMITTED (SITE, TRAFFIC, ENVIRONMENT,
                                                                                                                                                                                                                                L5.       DIMENSIONS SHALL NOT BE SCALED FROM DRAWINGS.                                                                   SAFETY) FOR SUPERINTENDENT'S REVIEW.
                                                                                                              G5    ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE CURRENT VERSION
                                                                                                                    OF THE APPLICABLE STANDARD EXCEPT WHERE VARIED BY THE SPECIFICATION AND/OR                                  L6.       DESIGN USES DIGITAL TERRAIN MODEL GENERATED FROM THE SITE SURVEY. SOME                                     DRIVEN PILES:
                                                                                                                    DRAWINGS. APPLICABLE CODES OF PRACTICE INCLUDE BUT ARE NOT LIMITED TO THE                                             ELEMENTS ARE INTERPOLATED AND MAY VARY FROM THE ACTUAL SITE CONDITIONS
                                                                                                                    FOLLOWING:                                                                                                                                                                                                                       P1.       PILES SHALL BE CONSTRUCTED IN ACCORDANCE WITH AS2159.
                                                                                                                    AS 1163        STRUCTURAL STEEL HOLLOW SECTIONS
                                                                                                                    AS 1170        SAA LOADING CODE                                                                             DESIGN CRITERIA
                                                                                                                                                                                                                                                                                                                                                     P2.       CONSTRUCTION CONSTRAINTS: AVOID LOADING EXISTING REVETMENT WALLS.
                                                                                                                    AS 1289        METHODS OF TESTING SOILS FOR ENGINEERING PURPOSES
                                                                                                                    AS 1554        WELDING OF STEEL STRUCTURES                                                                  DC1 THE STRUCTURAL ELEMENTS HAVE BEEN DESIGNED FOR THE FOLLOWING LIVE LOADS
                                                                                                                                                                                                                                                                                                                                                     P3.       DESIGN LOADS: PILES TO ACHIEVE GEOTECHNICAL CAPACITIES (VERTICAL &
                                                                                                                    AS 1664        ALUMINIUM STRUCTURES                                                                             IN ACCORDANCE WITH AS 1170.1: LIVE LOAD REDUCTIONS ARE NOT APPLICABLE.
                                                                                                                                                                                                                                                                                                                                                               HORIZONTAL) SHOWN ON THE DRAWINGS
                                                                                                                    AS 1684        RESIDENTIAL TIMBER-FRAMED CONSTRUCTION                                                           ELEMENT            UDL         CONCENTRATED
                                                                                                                    AS 1720        TIMBER STRUCTURES                                                                                ROOF               0.25 kPa    1.1KN
                                                                                                                                                                                                                                                                                                                                                     P4.       REQUIRED PILE POSITION TOLERANCES:
                                                                                                                    AS 2159        PILING CODE                                                                                      INTERNAL FLOORS    1.5kPa
                                                                                                                    AS 4100        STEEL STRUCTURES                                                                                 DECK               2.0kPa
                                                                                                                                                                                                                                                                                                                                                               PLAN POSITION: +/- 50mm AT UNDERSIDE OF EACH GROUND BEAM.
                                                                                                                    AS 5100        BRIDGE DESIGN                                                                                    THOROUGHFARES      4.0 kPa
                                                                                                                                                                                                                                                                                                                                                               PILE VERTICALITY:
                                                                                                                    BCA            BUILDING CODE OF AUSTRALIA (NATIONAL CONSTRUCTION CODE)                                                                                                                                                                     - WITHIN 4% FOR ALL PILES
                                                                                                                                                                                                                                DC2 WIND LOADS HAVE BEEN DETERMINED IN ACCORDANCE WITH AS 1170.2 BASED ON:
                                                                                                              G6    ANY DISCREPANCY SHALL BE REFERRED TO THE SUPERINTENDENT FOR A DECISION BEFORE                                   IMPORTANCE LEVEL            2
                                                                                                                                                                                                                                                                                                                                                     P5.       PILE TOE LEVELS ON THE DRAWINGS ARE ESTIMATED LEVELS. ACTUAL TOE LEVELS
                                                                                                                    PROCEEDING WITH THE WORK.                                                                                       REGION                      N4
                                                                                                                                                                                                                                                                                                                                                               SHALL BE DETERMINED DURING CONSTRUCTION BY AN RPEQ-CERTIFIED
                                                                                                                                                                                                                                    ULTIMATE WIND SPEED         61 m/s
                                                                                                                                                                                                                                                                                                                                                               GEOTECHNICAL ENGINEER.
                                                                                                              G7  ALL PROPRIETARY PRODUCTS NOT DEEMED TO COMPLY WITH THE BCA SHALL HAVE                                             SERVICEABILITY WIND SPEED   39.0 m/s
                                                                                                                  THIRD-PARTY CERTIFICATION WITH RELEVANT TESTING AND SIGN-OFF BY AN RPEQ ENGINEER.                                 TERRAIN CATEGORY            2
                                                                                                                                                                                                                                                                                                                                                     P6.       DO NOT FOUND PILES HIGHER THAN TOE LEVELS ON DRAWINGS, UNLESS APPROVED BY
                                                                                                                  PROPRIETARY PRODUCTS INCLUDES PREFABRICATED TRUSSES, LIGHT-GAUGE STEEL                                                                                                                                                                       BOTH THE SUPERINTENDENT AND THE GEOTECHNICAL ENGINEER. THE
                                                                                                                  FRAMING, FLOORING PRODUCTS, RECYCLED TIMBER AND PLASTICS, BALUSTRADES, SCREENS, DC3 EARTHQUAKE LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH AS 1170.4 BASED                                                                                SUPERINTENDENT SHALL SEEK ADVICE FROM THE DESIGN ENGINEER AS REQUIRED.
                                                                                                                  SHADE FABRICS, JOINERY, PARTITIONS AND OPERABLE WALLS.                                ON:
                                                                                                                                                                                                        ACCELERATION COEFFICIENT     0.06
                                                                                                              G8 REFER TO ARCHITECTS DRAWINGS FOR DETAILS OF ALL GROOVES, FILLETS, HOBS, DRIP           SITE FACTOR                  1
                                                                                                                  GROOVES AND THE LIKE.                                                                 IMPORTANCE LEVEL             1
                                                                                                                                                                                                        STRUCTURE TYPE
                                                                                                              G9  GIVE AT LEAST 24 HOURS NOTICE OF AN INSPECTION BEING REQUIRED FOR :                   DESIGN CATEGORY              EDC1
                                                                                                                  - PILING
                                                                                                                                                                                                    DC4 FIRE RESISTANCE LEVELS OF STRUCTURAL ELEMENTS HAVE BEEN TAKEN AS FOLLOWS:
                                                                                                                                                                                                                                                                                                                                                                                                                                 APPROVED PLAN
                                                                                                                                                                                                                                                                                                                                                                                                                                    MCU22/0017
                                                                                                                  - JETTY FRAMING (TIMBER)
                                                                                                                  - BRACING AND TIE DOWN                                                                ELEMENT       FRL (mins)

                                                                                                              G10 ALL FABRICATION SHOP DRAWINGS SHALL BE PROVIDED TO THE ENGINEER FOR REVIEW AND
                                                                                                                                                                                                        COLUMNS
                                                                                                                                                                                                        BEAMS
                                                                                                                                                                                                                       -/-/-
                                                                                                                                                                                                                       -/-/-                                                                                                                                                                                                     NOOSA COUNCIL
                                                                                                                  COMMENT IN A3 HARDCOPY OR PDF FORMAT.                                                 WALLS          -/-/-                                                                                                                                                                                                      01 MARCH 2022
  File: C:\- A Projects\00 - Black & More\7882 - 19 The Peninsula Jetty\ 7882- Notes Sheet.dwg




                                                                                                              G11   ABBREVIATIONS (GENERAL):                                                                                    DC5 DETERMINATION OF DESIGN LOADING FOR NON-STRUCTURAL ELEMENTS SUCH AS
                                                                                                                    NTS      NOT TO SCALE                                                                                           CEILING AND CLADDING SYSTEMS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
                                                                                                                    UNO      UNLESS NOTED OTHERWISE
                                                                                                                    NSOE     NOT SHOWN ON ELEVATION                                                                             DC6 FLOOD LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH AS 5100 WITH NOMINAL
                                                                                                                    NSOP     NOT SHOWN ON PLAN                                                                                      FLOOD VELOCITY TO BE CONFIRMED BY HYDRAULIC REQUIREMENTS AS FOLLOWS:
                                                                                                                    TYP      TYPICAL                                                                                                -V100 = 1m/s.
                                                                                                                    (O)      OVER
                                                                                                                    (U)      UNDER                                                                                              TEMPORARY WORKS:
                                                                                                                    CRS      CENTRES
                                                                                                                    NOM      NOMINAL
                                                                                                                                                                                                                                T1.       MAINTAIN THE WORKS IN A SAFE CONDITION. ENSURE STRUCTURES ARE NOT
                                                                                                                    CFW      CONTINUOUS FILLET WELD
                                                                                                                                                                                                                                          OVER-STRESSED AT ANY TIME. TEMPORARY ROAD SURFACES SHALL BE TRAFFICABLE
                                                                                                                                                                                                                                          AT ALL TIMES. POTHOLES ETC SHALL BE MONITORED AND REPAIRED.


                                                                                                                                                                                                                                T2.       CONTRACTOR'S RPEQ TO CERTIFY DESIGN AND CONSTRUCTION FOR TEMPORARY
                                                                                                                                                                                                                                          WORKS: STRUTS, PROPPING, FORMWORK STRIPPING AND PROPPING PROCEDURES, TIE
                                                                                                                                                                                                                                          BACKS, EXCAVATION SHORING, PROTECTION WORKS, DE-WATERING SYSTEMS,
                                                                                                                                                                                                                                          FORMWORK, EARLY LOADING OF STRUCTURES AND THE LIKE.
  Printed: 08 November 2021, 6:28 AM




                                                                                                                                                                                                                                                                                                                                                                                                                                            FOR CONSTRUCTION
                                                                                                                                                                                      R.P. DATA                       © Black & More                                                                           Client                               Project                                                  Drawing Title
                                                                                                                                                                                      LOT:    267                     This document is and shall remain
                                                                                                                                                                                                                                                                           Black & More
                                                                                                                                                                                                                                                                           ABN 19 609 960 232
                                                                                                                                                                                                                                                                                                                          ANDREW HAY           PROPOSED JETTY
                                                                                                                                                                                      RP:     856191                  the property of Black & More.                                                            Address
                                                                                                                                                                                                                                                                                                                          19 THE PENINSULA NOOSA WATERS                                                       GENERAL NOTES - SHEET 1 OF 2
                                                                                                 Revisions




                                                                                                                                                                                                                      This document may only be used                       7 / 28 Sunshine Beach Road,
                                                                                                                                                                                      19 THE PENINSULA NOOSA WATERS                                                        Noosa Heads QLD. 4567
                                                                                                                                                                                                                      for the purposes for which it was
                                                                                                                                                                                                                      commissioned and in accordance                       PO Box 611, Noosa Heads QLD. 4567   Drawn            Drawing        Approved                               Date    12/11/21
                                                                                                                                                                                      Client:                         with the Terms of Engagement for
                                                                                                                                                                                                                                                                           Telephone (07) 5447 4444
                                                                                                                                                                                                                                                                                                                           ST   Check     JB
                                                                                                                                                                                      ANDREW HAY                      the commission. Unauthorised use                                                                                                                                                       Drawing Size Scale (A3 size)     Drg No                Revision
                                                                                                             C1 CONSTRUCTION ISSUE                                                                                                                                                                                                                                                      RPEQ 23058
                                                                                                             No.                         Description       Reviewed Approved   Date
                                                                                                                                                                                                                      of this document in any form
                                                                                                                                                                                                                      whatsoever is prohibited.
                                                                                                                                                                                                                                                                           Email
                                                                                                                                                                                                                                                                           Internet
                                                                                                                                                                                                                                                                                     [email protected]
                                                                                                                                                                                                                                                                                     www.blackm.com
                                                                                                                                                                                                                                                                                                               Designed
                                                                                                                                                                                                                                                                                                                           JB
                                                                                                                                                                                                                                                                                                                                Design
                                                                                                                                                                                                                                                                                                                                Check     SS    Drawing is not to be used for construction unless approved      A3             NOT TO SCALE            7882- S002    C1
                                                                                                 External References:    B&M-JETTY-TITLE-A3_e.dwg
Document Set ID: 21816074
Version: 1, Version Date: 10/02/2022

Used in these records

About this file

File size
3.4 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Approved Plans - MCU22-0017.pdf · 3.4 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.