Introduction

The purpose of this report is to evaluate and design a suitable on-site treatment system and disposal
area in accordance with AS 1547 – 2012, the Queensland Plumbing and Wastewater Code, the
Plumbing and Drainage Act, The Environmental Protection Act & Local Authority requirements.
The report relates exclusively to the above site and the proposed and or existing buildings shown on
the plan only. All measurements and levels shown are as accurate as possible with the information
provided these are to be used for locating the onsite effluent disposal system only.


Site Description

 Weather Conditions                                                       Fine
 Slope                                                                    20%
 Slope Stability                                                           N/a
 Vegetation                                                             Grassed
 Fill                                                                      Nil
 Flooding                                                                  Nil
 Watercourses                                                          Nil nearby
 Site exposure                                                        Sun & wind
 Salinity                                                                  Nil
 Surface condition                                        Nil cracks, seepage or compaction
 Boulders & Rock outcrops                                          Boulders uphill
 Will water from uphill traverse the area                  Yes, diversion mound to prevent
 Water table                                                               Nil

Soil Category (AS1547-2012 Table M1)

 Borehole                        0-0.5m                 0.5-1.0m
 BH5-BH7                          Cat 4                   Cat 5
                              Clay Loams               Light Clays
                            Weakly Structured      Moderately Structured
                              0.12-0.5m/d             0.06-0.12m/d

Recommended Design Irrigation Rate

 Test Result                                                             0.15
 Recommended Design Irrigation Rate                                   3.5mm/day
 Adopted Rate                                                         3/mm/day

Calculations

 Bedrooms                                                               4
 Persons                                                                6
 DIR (mm/day)                                                           3
 Litres per person per day (Tank supply)                               120
 Calculations                                                   6x120=720 /3= 240
 Disposal Area Required                                    240m2 Sub- Surface Irrigation
Log in to download the original file

Site Classification Report.pdf · 5.3 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.