Bushfire Constraint Assessment – Peer Review
BlueCare, Sunrise Beach
Bushfire
Mitigation LandGraphics 2009 2016 Requirements Comment
Measures
Fire hydrants reticulated water supply reticulated water supply
and relevant Australian and fire hydrants in
Standard accordance with AS 2419
Agree with 2009 recommendation
Gas and Electricity Comply with AS1596 No specific requirements (and electrical lines are to be located
underground)
Construction requirements
Construct buildings to
Building Construction based on BAL – calculated BALs must be recalculated – target to
Level 1 and 2 per
Standards using Method 2 detailed in be no greater than BAL-29.
AS3959-1999
AS3959-2009
Street Numbering Clear and easily
No specific requirements Agree with 2009 recommendation
and Identification identifiable
No specific requirements
Internal Roads 2 wheel drive (no cul-de-sacs for lot Agree with 2009 recommendation
reconfigurations)
First Aid Fire Fighting Install fire hose reels No specific requirements Agree with 2009 recommendation
No specific requirements –
Prepare Evacuation
Evacuation Plan but required by Decision Evacuation Plan must be prepared
Plan
Notice.
Consider requirements
Landscaping No specific requirements Agree with 2009 recommendation
of APZ
Maintenance Regular maintenance No specific requirements Agree with 2009 recommendation
PR132938; Final / October 2016 Page 11