        CONCRETE/FOUNDATION NOTES:
        1.       All concrete shall be 25MPa UNO with 20mm nominal
        maximum aggregate size and 80mm slump to AS3600.
        2.       No on site water to be added to the concrete unless
        approved by the engineer.
        3.       All Concrete to be mechanically vibrated so that the                                                                                                                           Retaining Wall
        concrete is fully compacted U.N.O.                                                                                                                                                      Footings.
        4.       Concrete is to be cured for a minimum of 7 days after
        initial set. The curing method is to be approved by the
        engineer.
        5.       Cover to reinforcement to be 40mm for all steelwork.
        6.       Concrete shall not be poured when the air temperature
        is greater than 38 degrees or less than 5 degrees.




                                                                                                                                                       B2
        7.       Concrete footings and floors to be inspected by the                                                                                                                                 2/N12 Starter Bars
        engineer prior to pouring. The engineer is to be given 24 hrs.                                                                                                                               for 2 Stage Pour.
        notice of such an inspection being required.
        8.       Slab Mesh is to be lapped so as the two outermost
                                                                                                       SL72 MESH                                                    B2

        transverse wires of one sheet overlap the two outermost
                                                                                                      100mm SLAB
        transverse wires of the other sheet.                                                                                A




                                                                                                                                                       B2
        9.       All Reinforcement shall be adequately supported before
                                                                                                                            04
        commencement of concrete pour to ensure cover and
        placement of steel is maintained.
        10.      Controlled Fill shall be clean granular material (free of                                                                       EC
        clay) compacted to 95% standard compaction in layers no                                                                                             B2
        greater than 150mm.
        11.      FOUNDATION MATERIAL: Organic Material, soft spots,
        top soil and any other deleterious material shall be removed
        from footing or slab excavations. Excavations shall then be
        proof rolled and soft spots replaced with controlled fill if under
        slabs or 15Mpa mass concrete if under footings. Site to have a
        nominal bearing capacity of 100kPa and classification not
        greater than 'S'.
                                                                                                  Note; Based on the Sandy Soil Classification there is
        Soil test by ASI Australian Soil Investigations, Report No; 210239(S).                  potential of a cave in during excavation. Shoring may be
        12.   Footings shall be founded below the bottom of existing
                                                                                                   required, to be determined at builders discression.
        or proposed adjoining service trenches. Excavations shall not
        be taken below the bottom of adjoining footings.
        13.    The site shall be graded so that water cannot pond
        against or near the house.
        14.   Care should be taken to control the flora so as to not
        adversely affect the drainage of the site.
        15.    Site Classification "H1/P"




                                                                            No.   Description             Date       ADAM FLANAGAN & SHANE TYE                      APPROVED
AAA Design & Development Pty Ltd                                                                                                                                     Jose David Lesmes Tirado             CONCRETE FOOTING LAYOUT
34/13 Norval Court, MAROOCHYDORE, QLD 4558                                                                           164 Edwards St,
                                                                                                                                                                                                   Project number T081-01
Tel/Fax: (07) 5479 6747
                                                                                                                     SUNSHINE BEACH QLD
Mob:      0422 039 247                                                                                                                                                                             Date         06/12/2021       3497 - 01
                                           design &                                                                                                                                                                  K.A.J
                                                                                                                                                                    BEng, MIEAust, RPEQ 7198       Drawn by
email: [email protected]                                                                                                                                      For & on behalf of AAA
                                                                                                                     PROPOSED DUPLEX                             Design & Development Consulting   Checked by        D.L.T.   Scale @ A3     1:100
Log in to download the original file

Att 4 Earthworks Plans.pdf · 550 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.