GENERAL NOTES COMPLIANCE NOTES COMPLIANCE NOTES CONTINUED COMPLIANCE NOTES CONTINUED COMPLIANCE NOTES CONTINUED
ALL WORKS TO COMPLY WITH THE BUILDING ACT ALL WORKS MUST EITHER COMPLY WITH THE CLADDING INSULATION LIVEABLE HOUSING (NEW HOMES ONLY)
1975, THE NATIONAL CONSTRUCTION CODE PERFORMANCE SOLUTIONS SET OUT IN THE NCC METAL AND PLASTIC SHEET ROOF AND WALL THERMAL INSULATION TO BE SELECTED AND DWELLING ACCESS TO COMPLY WITH PART 1 OF
(NCC)2022, THE QUEENSLAND DEVELOPMENT 2022 AND STATED BELOW, OR ACHEIVE THE SAME CLADDING TO BE DESIGNED AND INSTALLED IN INSTALLED IN ACCORDANCE WITH AS/NZS 4859, THE LIVEABLE HOUSING DESIGN STANDARD.
CODE, LOCAL AUTHORITY REQUIREMENTS, AND ALL PERFORMANCE REQUIREMENTS THROUGH ACCORDANCE WITH AS/NZS 1562, PART 7.2 OF THE PART 13.2 OF THE ABCB HOUSING PROVISIONS AND DWELLING ENTRY TO COMPLY WITH PART 2 OF THE
RELEVANT AUSTRALIAN STANDARDS. ANY COMPLYING WITH THE DEEMED-TO-SATISFY ABCB HOUSING PROVISIONS, AND MANUFACTURER'S DETAILS AND SPECIFICATIONS. LIVEABLE HOUSING DESIGN STANDARD.
OUTDATED STANDARDS LISTED IN THESE NOTES SOLUTIONS AS DETAILED IN RELEVANT SECTIONS MANUFACTURER'S DETAILS AND SPECIFICATIONS. INTERNAL DOORS AND CORRIDORS TO COMPLY
ARE TO BE TAKEN TO REFER TO THE CURRENT OF THE NCC 2022. METAL DOWNPIPES AND RAINWATER FITTINGS TO HEALTH AND AMENITY WITH PART 3 OF THE LIVEABLE HOUSING DESIGN
EDIDITION. BE MANUFACTURED, SELECTED AND INSTALLED IN INSTALL BUILDING MEMBRANES TO ALL NEW STANDARD.
STRUCTURE ACCORDANCE WITH AS/NZS 2179 AND PART 7.4 OF EXTERNAL WALLS IN ACCORDANCE WITH AS/NZS THE GROUND OR ENTRY LEVEL OF A DWELLING
CHECK ALL DIMENSIONS AND LEVELS ON SITE ALL NEW STRUCTURAL INSTALLATIONS SHOULD BE THE ABCB HOUSING PROVISIONS. UPVC 4200 AND PART 10.8 OF THE ABCB HOUSING MUST HAVE AT LEAST ONE SANITARY
PRIOR TO COMMENCING WORKS. COMPLETE SET IN ACCORDANCE WITH AS/NZS 1170 AND PART 2.2 DOWNPIPES AND RAINWATER FITTINGS TO BE PROVISIONS. COMPARTMENT, WHICH IS TO COMPLY WITH PART
OUT OF THE WORKS AND REPORT AND CLARIFY OF THE ABCB HOUSING PROVISIONS. THE MANUFACTURED, SELECTED AND INSTALLED IN ALL MECHANICAL INSTALLATIONS ARE TO BE IN 4.2 OF THE LIVEABLE HOUSING DESIGN STANDARD,
DISCREPANCIES TO THE DESIGNER PRIOR TO STRUCTURAL INTEGRITY OF THE EXISTING ACCORDANCE WITH AS 1273 AND PART 7.4 OF THE ACCORDANCE WITH AS 1668 AND PART 10.8 OF THE AND PART 6 WHERE RELEVANT.
COMMENCING WORKS. BUILDING TO BE ADEQUATELY MAINTAINED DURING ABCB HOUSING PROVISIONS. ABCB HOUSING PROVISIONS. AT LEAST ONE SHOWER MUST COMPLY WITH PART
CONSTRUCTION. METAL ROOF AND WALL CLADDING TO HAVE SANITARY COMPARTMENTS TO BE CONSTRUCTED 5.2 OF THE LIVEABLE HOUSING DESIGN STANDARD,
FIGURED DIMENSIONS TAKE PRECEDENCE. DO NOT PROTECTIVE COATING APPROPRIATE TO IN ACCORDANCE WITH PART 10.4 OF THE ABCB AND PART 6 WHERE RELEVANT.
SCALE OFF DRAWINGS. SITE WORKS ENVIRONMENT CONDITIONS IN ACCORDANCE WITH HOUSING PROVISIONS.
REFER TO SITE SPECIFIC SOIL REPORTS OR AS 1397 AND PART 7.2 OF THE ABCB HOUSING SUSTAINABLE HOUSING REQUIREMENTS
CHECK SERVICES DRAWINGS INCLUDING CLASSIFY THE SITE IN ACCORDANCE WITH PART 4.2 PROVISIONS. FIRE SAFETY THERMAL PERFORMANCE OF THIS BUILDING CAN
HYDRAULIC, MECHANICAL AND ELECTRICAL FOR OF THE ABCB HOUSING PROVISIONS AND AS 2870. ENSURE MATERIAL COMPATIBILITY BETWEEN SMOKE ALARMS TO BE DESIGNED, INSTALLED AND BE SATISFIED AS PER NCC VOL 2 SPECIFICATION
SET OUT AND SIZING OF SERVICES AND DUCTS NECESSARY EARTHWORKS TO BE UNDERTAKEN IN METALS SUITABLE TO ENVIRONMENT CONDITIONS CERTIFIED IN ACCORDANCE WITH AS 3786 AND 42, BY ACHEIVING A MIN. ENERGY EFFICIENCY
WHERE APPLICABLE. ACCORDANCE WITH PART 3.2 OF THE ABCB IN ACCORDANCE WITH PART 7.2 OF THE ABCB PART 9.5 OF THE ABCB HOUSING PROVISIONS. STAR RATING OF 7 STARS, OR 6.5 IF IT HAS AN
HOUSING PROVISIONS. HOUSING PROVISIONS. SYSTEMS TO BE POWERED FROM CONSUMER OUTDOOR LIVING AREA COMPLYING WITH
COORDINATE ALL CONSULTANT DOCUMENTATION ALL NEW EXTERNAL WORKS TO DIVERT SURFACE MAINS POWER SOURCE AND INTERCONNECTED SPECIFICATION 42 PART C2 , OR BY COMPLYING
AND IDENTIFY AND CLARIFY DISCREPANCIES WITH WATER FROM BUILDINGS AND STRUCTURES TO TIMBER CLADDING TO BE SELECTED AND WHERE THERE IS MORE THAN ONE ALARM. WITH THE FOLLOWING PARTS OF THE ABCB
RELEVANT CONSULTANTS PRIOR TO COMMENCING DISCHARGE POINTS COMPLIANT WITH PART 3.3 OF INSTALLED IN ACCORDANCE WITH PART 7.5 OF THE PORTABLE FIRE EXTINGUISHERS AND BLANKETS HOUSING PROVISIONS—
RELATED WORKS. THE ABCB HOUSING PROVISIONS. ABCB HOUSING PROVISIONS AND TO BE PROVIDED DURING CONSTRUCTION IN PART 13.2, FOR THE BUILDING FABRIC; AND
MANUFACTURER'S SPECIFICATIONS. ACCORDANCE WITH AS 2444. PART 13.3, FOR THE EXTERNAL GLAZING AND
CHECK ONSITE DIMENSIONS PRIOR TO SLABS AND FOOTINGS FIBRE CEMENT BOARD AND SHEET CLADDING AND ELECTRICAL INSTALLATIONS TO BE UNDERTAKEN SHADING; AND
FABRICATION OF WINDOWS, DOORS AND JOINERY. CONCRETE SLABS AND FOOTINGS, INCLUDING LINING TO BE SELECTED AND INSTALLED IN IN ACCORDANCE WITH AS 3000. PART 13.4, FOR BUILDING SEALING; AND
STEEL REINFORCEMENT, TO BE DESIGNED, ACCORDANCE WITH PART 7.5 OF THE ABCB PART 13.5, FOR CEILING FANS.
REFER TO BUILDING APPROVAL FOR SPECIFIC INSTALLED AND CERTIFIED IN ACCORDANCE WITH HOUSING PROVISIONS, AS/NZS 2908, AS/NZS 1859 PLUMBING AND DRAINAGE ENERGY EFFICIENT (E.E.) LIGHTING:
CONDITIONS AND ADDITIONAL REQUIREMENTS. AS 2870 AND SECTION 4.2 OF THE ABCB HOUSING AND MANUFACTURERS SPECIFICATIONS. PLUMBING AND DRAINAGE INSTALLATIONS A MINIMUM OF 80% OF TOTAL FIXED INTERIOR
PROVISIONS. PARTICLEBOARD FLOORING TO BE INSTALLED IN INCLUDING WATER SERVICES, SANITARY DRAINAGE ARTIFICIAL LIGHTING TO THE DWELLING AND
ALL NEW SERVICES TO CONNECT TO EXISTING ON ACCORDANCE WITH AS 1860 AND NCC 2022 H1. AND STORMWATER DRAINAGE TO BE INSTALLED IN ATTACHED GARAGE SHALL BE ENERGY EFFICIENT
SITE UTILITIES. CONFIRM SUITABILITY AND REINFORCED CONCRETE ACCORDANCE WITH AS/NZS 3500 AND PARTS 3.3 LIGHTING TO COMPLY WITH QDC MP4.1.
CAPACITY PRIOR TO COMMENCING WORKS. CONCRETE AND CONCRETE STRUCTURES TO BE GLAZING AND 7.4 OF THE ABCB HOUSING PROVISIONS. TAPWARE:
MANUFACTURED, DESIGNED AND INSTALLED IN GLASS AND GLAZING TO BE SELECTED AND INSTALLATIONS TO ACCOMMODATE FOR ALL SHOWER HEADS AND TAPWARE TO LAUNDRY
ALL PROPIETARY MATERIALS SHALL BE USED AND ACCORDANCE WITH AS 3600. INSTALLED IN ACCORDANCE WITH AS 1288 AND POTENTIAL MOVEMENT OF SOIL. REFER TO SOIL TUBS, KITCHEN SINKS AND
FIXED STRICTLY IN ACOORDANCE WITH PART 8.4 OF THE ABCB HOUSING PROVISIONS. REPORTS FOR CLASSIFICATION. BASINS MUST HAVE A MINIMUM 3-STAR WATER
MANUFACTURER'S WRITTEN INSTRUCTIONS FOR MASONRY WINDOWS AND EXTERNAL GLAZED DOORS ARE TO HOT WATER RETICULATION SHALL BE EFFICIENCY LABELLING AND STANDARDS RATING,
USE UNDER THE CONDITIONS APPLICABLE. PROVIDE DAMP PROOF COURSES AND FLASHINGS BE DESIGNED, MANUFACTURED AND INSTALLED IN TEMPERATURE CONTROLLED TO 50ºC OR BELOW TO COMPLY WITH QDC MP4.1.
TO NEW MASONRY WALL INSTALLATIONS IN ACCORDANCE WITH AS 2047 AND PART 8.2 OF THE TO BATHS SHOWERS AND BASINS IN ACCORDANCE TOILETS:
SURFACE WATER DRAINAGE MUST BE PREVENTED ACCORDANCE WITH AS/NZS 2904, AND PARTS 5.7.4 ABCB HOUSING PROVISIONS. WITH AS 3500. TOILET CISTERNS MUST HAVE DUAL FLUSH
FROM ENTERING THE BUILDING WITH FGL SLOPING AND 12.3 OF THE ABCB HOUSING PROVISIONS. GLAZED PANELS CAPABLE OF BEING MISTAKEN CAPABILITY AND HAVE A MINIMUM 4-STAR WATER
AWAY FROM THE BUILDING AND FINISHED SLAB MASONRY STRUCTURES TO BE DESIGNED AND FOR UNOBSTRUCTED OPENINGS ARE TO BE MADE TERMITE RISK MANAGEMENT EFFICIENCY LABELLING AND STANDARDS RATING
LEVELS. INSTALLED IN ACCORDANCE WITH AS 3700 AND APPARENT WITH PERMANENT DECALS OR VISION TERMITE MANAGEMENT BARRIERS AND TO COMPLY WITH QDC MP4.1.
PART 5 OF THE ABCB HOUSING PROVISIONS. STRIPS TO INDICATE ITS PRESENCE. INSTALLATIONS TO BE DESIGNED AND INSTALLED RAINWATER TANKS:
MASONRY STRUCTURES IN SMALL BUILDINGS TO GARAGE AND LARGE PANEL DOORS TO BE TO AREAS WITHIN PROPOSED WORKS IN A RAINWATER TANK WITH A MINIMUM STORAGE
BE DESIGNED AND INSTALLED IN ACCORDANCE DESIGNED AND INSTALLED IN ACCORDANCE WITH ACCORDANCE WITH AS 3660, AS 2870, AND PART CAPACITY OF 5000 LITRES MUST BE INSTALLED TO
WITH AS 4773 AND PART 5 OF THE ABCB HOUSING AS/NZS 4505 AND PART 2.2 OF THE ABCB HOUSING 3.4 OF THE ABCB HOUSING PROVISIONS. AS 3500 - PLUMBING AND DRAINAGE AND AS
PROVISIONS. PROVISIONS. PER QDC MP4.2 AND LOCAL AUTHORITY
WORKPLACE HEALTH AND SAFETY REQUIREMENTS.
FRAMING WATERPROOFING BUILDER SHALL COMPLY WITH ALL WORKPLACE
TIMBER FRAMED CONSTRUCTION SHOULD BE WET AREAS TO BE WATERPROOFED IN HEALTH AND SAFETY REQUIREMENTS REQUIRED
DESIGNED AND INSTALLED IN ACCORDANCE WITH ACCORDANCE WITH AS 3740 AND PART 10.2 OF THE BY LEGISLATION FOR THE CONSTRUCTION OF THE
AS1684 AND NCC 2022 PART H1D6. ABCB HOUSING PROVISIONS. DWELLING AND SHALL ASSESS ALL WORKPLACE
TIMBER STRUCTURES ARE TO BE DESIGNED IN EXTERNAL WATERPROOFING MEMBRANES TO BE HEALTH AND SAFETY ISSUES BEFORE
ACCORDANCE WITH AS 1720.1 AND NCC 2022 PART DESIGNED AND INSTALLED IN ACCORDANCE WITH COMMENCEMENT OF CONSTRUCTION AND LIAISE
H1D6. NAILPLATE TIMBER ROOF TRUSSES TO AS 4654 AND NCC 2022 PART H2. WITH THE DESIGNER IF NECESSARY TO
MANUFACTURERS DETAILS AND AS 1720.5. AVOID/MINIMISE RISKS DURING CONSTRUCTION.
STAIRWAY AND RAMP CONSTRUCTION
STEEL FRAMED CONSTRUCTION SHOULD BE SLIP RESISTANCE OF LANDINGS, STAIRS AND
DESIGNED AND INSTALLED IN ACCORDANCE WITH RAMPS TO BE IN ACCORDANCE WITH PART 11.2 OF
AS/NZS 4600 AND NCC 2022 PART H1D6. STEEL THE ABCB HOUSING PROVISIONS AND AS 4586.
STRUCTURES TO BE DESIGNED, INSTALLED AND
CERTIFIED IN ACCORDANCE WITH AS 4100 AND NCC
2022 PART H1D6.
PRELIMINARY
PROJECT REV DESCRIPTION DATE
178 COOROY MOUNTAIN ROAD WD1 PRELIMINARY 11/03/2024 NOTES AND LEGENDS
11/03/2024 4:25:20 PM
Drawn: TD Checked: KW REV
CLIENT
STUDIO: 0490 547 760 TY JONES
SCALE
1 : 50 @ A3
DRAWING NUMBER
A001
WD1
LIC: 15256628
CREATED WITH GENIUS AT RATWORKS STUDIOS
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalLog in to download the original file
Very large file: the download may take a few minutes. If you are on mobile data, it is best to wait until you are on Wi-Fi.
Searchable page text hides email addresses. Original files are unchanged and may show email addresses.