7550P_32 Masthead Quay_200331 Construction Issue · OPW20/0065

Attached to the e-mail Operational Works Application OPW20/0065 - 32 Masthead Quay, Noosaville.

Plans and drawings: the text below has words only, no drawings.

Log in to see the plans as drawn
                                                                                                                                                GENERAL                                                                                                              DIMENSIONS/LEVELS                                                                                                    CONSTRUCTABILITY CONSTRAINTS:
                                                                                                                                                G1    STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE                                                      L1.        CONSTRUCTION SHALL BE SET OUT USING SURVEY BENCHMARKS PROVIDED BY COUNCIL.                                CC1. CONSTRUCTABILITY CONSTRAINTS:
                                                                                                                                                      SPECIFICATION, ARCHITECTURAL, AND OTHER CONSULTANTS' DOCUMENTS.
                                                                                                                                                                                                                                                                     L2. ALL LEVELS AND SETOUT POINTS ARE SHALL BE CONFIRMED ON SITE BY REGISTERED                                             A)   PROTECT ALL EXISTING INFRASTRUCTURE (EG CULVERT CROSSING, PAVEMENTS,
                                                                                                                                                G2    REFER TO THE ARCHITECTURAL DRAWINGS FOR SETOUT. NO DIMENSIONS SHALL BE                                         SURVEYOR PRIOR TO CONSTRUCTION. ADVISE ANY DISCREPANCY BEFORE PROCEEDING.                                                      FENCING & ELECTRICAL POLES/WIRES) FROM ANY DAMAGE.
                                                                                                                                                      OBTAINED BY SCALING FROM DRAWINGS.
                                                                                                                                                                                                                                                                     L3.       DIMENSION STANDARDS:                                                                                         B)      ALLOW OF LIKELIHOOD OF FLOW WITHIN THE WATERWAY: EXISTING WATERWAY ARE
                                                                                                                                                G3    UNLESS OTHERWISE NOTED (UNO), ALL LEVELS ARE IN METRES AND ALL DIMENSIONS ARE IN                                         - REDUCED LEVELS, CHAINAGES AND COORDINATES ARE ALL IN METRES.                                                       FLOODED MULTIPLE TIMES PER YEAR. PROTECT CONSTRUCTION EQUIPMENT AND
                                                                                                                                                      MILLIMETRES.                                                                                                             - CIVIL DRAWINGS (SKC SERIES): ALL OTHER DIMENSIONS ARE IN METRES (m).                                               WORKS.
                                                                                                                                                                                                                                                                               - STRUCTURAL DRAWINGS (SKS SERIES): ALL OTHER DIMENSIONS ARE IN MILLIMETRES (mm).
                                                                                                                                                G4    THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE STABILITY OF THE                                                                                                                                                            CC2. NO WORK TO COMMENCE ON SITE UNTIL:
                                                                                                                                                      STRUCTURE UNTIL ITS COMPLETION AND SHALL ENSURE THAT NO PART OF THE STRUCTURE                                  L4.        ALL LEVELS ARE TO AUSTRALIAN HEIGHT DATUM.                                                                     - OFFICIAL PRE-START MEETING HELD AND PRE-START MEETING MINUTES ISSUED
                                                                                                                                                      IS OVER-STRESSED BY EXCESSIVE LOADING.                                                                                                                                                                                                   - CONTRACTOR'S MANAGEMENT PLANS SUBMITTED (SITE, TRAFFIC, ENVIRONMENT,
                                                                                                                                                                                                                                                                     L5.       DIMENSIONS SHALL NOT BE SCALED FROM DRAWINGS.                                                                   SAFETY) FOR SUPERINTENDENT'S REVIEW.
                                                                                                                                                G5    ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE CURRENT VERSION
                                                                                                                                                      OF THE APPLICABLE STANDARD EXCEPT WHERE VARIED BY THE SPECIFICATION AND/OR                                     L6.       DESIGN USES DIGITAL TERRAIN MODEL GENERATED FROM THE SITE SURVEY. SOME                                     DRIVEN PILES:
                                                                                                                                                      DRAWINGS. APPLICABLE CODES OF PRACTICE INCLUDE BUT ARE NOT LIMITED TO THE                                                ELEMENTS ARE INTERPOLATED AND MAY VARY FROM THE ACTUAL SITE CONDITIONS
                                                                                                                                                      FOLLOWING:                                                                                                                                                                                                                          P1.       PILES SHALL BE CONSTRUCTED IN ACCORDANCE WITH AS2159.
                                                                                                                                                      AS 1163        STRUCTURAL STEEL HOLLOW SECTIONS
                                                                                                                                                      AS 1170        SAA LOADING CODE                                                                                DESIGN CRITERIA
                                                                                                                                                                                                                                                                                                                                                                                          P2.       CONSTRUCTION CONSTRAINTS: AVOID LOADING EXISTING REVETMENT WALLS.
                                                                                                                                                      AS 1289        METHODS OF TESTING SOILS FOR ENGINEERING PURPOSES
                                                                                                                                                      AS 1554        WELDING OF STEEL STRUCTURES                                                                     DC1 THE STRUCTURAL ELEMENTS HAVE BEEN DESIGNED FOR THE FOLLOWING LIVE LOADS
                                                                                                                                                                                                                                                                                                                                                                                          P3.       DESIGN LOADS: PILES TO ACHIEVE GEOTECHNICAL CAPACITIES (VERTICAL &
                                                                                                                                                      AS 1664        ALUMINIUM STRUCTURES                                                                                IN ACCORDANCE WITH AS 1170.1: LIVE LOAD REDUCTIONS ARE NOT APPLICABLE.
                                                                                                                                                                                                                                                                                                                                                                                                    HORIZONTAL) SHOWN ON THE DRAWINGS
                                                                                                                                                      AS 1684        RESIDENTIAL TIMBER-FRAMED CONSTRUCTION                                                              ELEMENT            UDL         CONCENTRATED
                                                                                                                                                      AS 1720        TIMBER STRUCTURES                                                                                   ROOF               0.25 kPa    1.1KN
                                                                                                                                                                                                                                                                                                                                                                                          P4.       REQUIRED PILE POSITION TOLERANCES:
                                                                                                                                                      AS 2159        PILING CODE                                                                                         INTERNAL FLOORS    1.5kPa
                                                                                                                                                      AS 4100        STEEL STRUCTURES                                                                                    DECK               2.0kPa
                                                                                                                                                                                                                                                                                                                                                                                                    PLAN POSITION: +/- 50mm AT UNDERSIDE OF EACH GROUND BEAM.
                                                                                                                                                      AS 5100        BRIDGE DESIGN                                                                                       THOROUGHFARES      4.0 kPa
                                                                                                                                                                                                                                                                                                                                                                                                    PILE VERTICALITY:
                                                                                                                                                      BCA            BUILDING CODE OF AUSTRALIA (NATIONAL CONSTRUCTION CODE)                                                                                                                                                                        - WITHIN 4% FOR ALL PILES
                                                                                                                                                                                                                                                                     DC2 WIND LOADS HAVE BEEN DETERMINED IN ACCORDANCE WITH AS 1170.2 BASED ON:
                                                                                                                                                G6    ANY DISCREPANCY SHALL BE REFERRED TO THE SUPERINTENDENT FOR A DECISION BEFORE                                      IMPORTANCE LEVEL            2
                                                                                                                                                                                                                                                                                                                                                                                          P5.       PILE TOE LEVELS ON THE DRAWINGS ARE ESTIMATED LEVELS. ACTUAL TOE LEVELS
                                                                                                                                                      PROCEEDING WITH THE WORK.                                                                                          REGION                      N4
                                                                                                                                                                                                                                                                                                                                                                                                    SHALL BE DETERMINED DURING CONSTRUCTION BY AN RPEQ-CERTIFIED
                                                                                                                                                                                                                                                                         ULTIMATE WIND SPEED         61 m/s
                                                                                                                                                                                                                                                                                                                                                                                                    GEOTECHNICAL ENGINEER.
                                                                                                                                                G7  ALL PROPRIETARY PRODUCTS NOT DEEMED TO COMPLY WITH THE BCA SHALL HAVE                                                SERVICEABILITY WIND SPEED   39.0 m/s
                                                                                                                                                    THIRD-PARTY CERTIFICATION WITH RELEVANT TESTING AND SIGN-OFF BY AN RPEQ ENGINEER.                                    TERRAIN CATEGORY            2
                                                                                                                                                                                                                                                                                                                                                                                          P6.       DO NOT FOUND PILES HIGHER THAN TOE LEVELS ON DRAWINGS, UNLESS APPROVED BY
                                                                                                                                                    PROPRIETARY PRODUCTS INCLUDES PREFABRICATED TRUSSES, LIGHT-GAUGE STEEL                                                                                                                                                                          BOTH THE SUPERINTENDENT AND THE GEOTECHNICAL ENGINEER. THE
                                                                                                                                                    FRAMING, FLOORING PRODUCTS, RECYCLED TIMBER AND PLASTICS, BALUSTRADES, SCREENS, DC3 EARTHQUAKE LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH AS 1170.4 BASED                                                                                   SUPERINTENDENT SHALL SEEK ADVICE FROM THE DESIGN ENGINEER AS REQUIRED.
                                                                                                                                                    SHADE FABRICS, JOINERY, PARTITIONS AND OPERABLE WALLS.                                ON:
                                                                                                                                                                                                                                          ACCELERATION COEFFICIENT     0.06
                                                                                                                                                G8 REFER TO ARCHITECTS DRAWINGS FOR DETAILS OF ALL GROOVES, FILLETS, HOBS, DRIP           SITE FACTOR                  1
                                                                                                                                                                                                                                          IMPORTANCE LEVEL             1
File: C:\- Projects\00 - Black & More\0 - 7550 - Noosa Jetty Builders\000 - Archive\7550P - 32 Masthead\ 7550P - Notes Sheet.dwg




                                                                                                                                                    GROOVES AND THE LIKE.
                                                                                                                                                                                                                                          STRUCTURE TYPE
                                                                                                                                                G9  GIVE AT LEAST 24 HOURS NOTICE OF AN INSPECTION BEING REQUIRED FOR :                   DESIGN CATEGORY              EDC1
                                                                                                                                                    - PILING
                                                                                                                                                    - JETTY FRAMING (TIMBER)                                                          DC4 FIRE RESISTANCE LEVELS OF STRUCTURAL ELEMENTS HAVE BEEN TAKEN AS FOLLOWS:
                                                                                                                                                    - BRACING AND TIE DOWN                                                                ELEMENT       FRL (mins)
                                                                                                                                                                                                                                          COLUMNS        -/-/-
                                                                                                                                                G10 ALL FABRICATION SHOP DRAWINGS SHALL BE PROVIDED TO THE ENGINEER FOR REVIEW AND        BEAMS          -/-/-
                                                                                                                                                    COMMENT IN A3 HARDCOPY OR PDF FORMAT.                                                 WALLS          -/-/-

                                                                                                                                                G11   ABBREVIATIONS (GENERAL):                                                                                       DC5 DETERMINATION OF DESIGN LOADING FOR NON-STRUCTURAL ELEMENTS SUCH AS
                                                                                                                                                      NTS      NOT TO SCALE                                                                                              CEILING AND CLADDING SYSTEMS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
                                                                                                                                                      UNO      UNLESS NOTED OTHERWISE
                                                                                                                                                      NSOE     NOT SHOWN ON ELEVATION                                                                                DC6 FLOOD LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH AS 5100 WITH NOMINAL
                                                                                                                                                      NSOP     NOT SHOWN ON PLAN                                                                                         FLOOD VELOCITY TO BE CONFIRMED BY HYDRAULIC REQUIREMENTS AS FOLLOWS:
                                                                                                                                                      TYP      TYPICAL                                                                                                   -V100 = 1m/s.
                                                                                                                                                      (O)      OVER
                                                                                                                                                      (U)      UNDER                                                                                                  TEMPORARY WORKS:
                                                                                                                                                      CRS      CENTRES
                                                                                                                                                      NOM      NOMINAL
                                                                                                                                                                                                                                                                     T1.       MAINTAIN THE WORKS IN A SAFE CONDITION. ENSURE STRUCTURES ARE NOT
                                                                                                                                                      CFW      CONTINUOUS FILLET WELD
                                                                                                                                                                                                                                                                               OVER-STRESSED AT ANY TIME. TEMPORARY ROAD SURFACES SHALL BE TRAFFICABLE
                                                                                                                                                                                                                                                                               AT ALL TIMES. POTHOLES ETC SHALL BE MONITORED AND REPAIRED.


                                                                                                                                                                                                                                                                     T2.       CONTRACTOR'S RPEQ TO CERTIFY DESIGN AND CONSTRUCTION FOR TEMPORARY
                                                                                                                                                                                                                                                                               WORKS: STRUTS, PROPPING, FORMWORK STRIPPING AND PROPPING PROCEDURES, TIE
                                                                                                                                                                                                                                                                               BACKS, EXCAVATION SHORING, PROTECTION WORKS, DE-WATERING SYSTEMS,
                                                                                                                                                                                                                                                                               FORMWORK, EARLY LOADING OF STRUCTURES AND THE LIKE.




                                                                                                                                                                                                                                                                                                                                                                                                                                                                           CONSTRUCTION ISSUE
Printed: 31 March 2020, 6:18 AM




                                                                                                                                                                                                                            NOOSA JETTY BUILDERS           © Black & More                                                                           Client                                      Project                                           Drawing Title
                                                                                                                                                                                                                            JoB No: 1241                   This document is and shall remain
                                                                                                                                                                                                                                                                                                                Black & More
                                                                                                                                                                                                                                                                                                                ABN 19 609 960 232
                                                                                                                                                                                                                                                                                                                                                               NOOSA JETTY BUILDERS   PROPOSED NEW JETTY
                                                                                                                                                                                                                            Address:                       the property of Black & More.                                                            Address
                                                                                                                                                                                                                                                                                                                                                               32 MASTHEAD QUAY, NOOSAVILLE                                                        GENERAL NOTES - SHEET 1 OF 2
                                                                                                                                   Revisions




                                                                                                                                                                                                                                                           This document may only be used                       7 / 28 Sunshine Beach Road,
                                                                                                                                                                                                                            32 MASTHEAD QUAY, NOOSAVILLE                                                        Noosa Heads QLD. 4567
                                                                                                                                                                                                                                                           for the purposes for which it was
                                                                                                                                                                                                                            LOT 618    ON 883864           commissioned and in accordance                       PO Box 611, Noosa Heads QLD. 4567   Drawn            Drawing        Approved                               Date    31/03/20
                                                                                                                                                                                                                            Client:                        with the Terms of Engagement for
                                                                                                                                                                                                                                                                                                                Telephone (07) 5447 4444
                                                                                                                                                                                                                                                                                                                                                                ST   Check     FM
                                                                                                                                                                                                                            BRIAN CHARD                    the commission. Unauthorised use                                                                                                                                                       Drawing Size Scale (A3 size)     Drg No                 Revision
                                                                                                                                               C1 CONSTRUCTION ISSUE                          FM       FM        31/03/20                                                                                                                                                                                                    RPEQ 19951
                                                                                                                                               No.                         Description       Reviewed Approved     Date
                                                                                                                                                                                                                                                           of this document in any form
                                                                                                                                                                                                                                                           whatsoever is prohibited.
                                                                                                                                                                                                                                                                                                                Email
                                                                                                                                                                                                                                                                                                                Internet
                                                                                                                                                                                                                                                                                                                          [email protected]
                                                                                                                                                                                                                                                                                                                          www.blackm.com
                                                                                                                                                                                                                                                                                                                                                    Designed
                                                                                                                                                                                                                                                                                                                                                                FM
                                                                                                                                                                                                                                                                                                                                                                     Design
                                                                                                                                                                                                                                                                                                                                                                     Check     DS    Drawing is not to be used for construction unless approved      A3             NOT TO SCALE            7550P- S002    C1
                                                                                                                                   External References:    B&M-JETTY-TITLE-A3_e.dwg

Used in these records

About this file

File size
1.0 MB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

7550P_32 Masthead Quay_200331 Construction Issue.pdf · 1.0 MB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.