Original PDF page 44, section 1. The text section number identifies this passage in the reader.

                                                                                                                                             BARRIER/FENCE TO THE TOP OF RETAINING WALLS
                                                                                                                                             WHERE HIGHER THAN 1.0m.
                                                                                                                                             REFER RETAINING WALL NOTES 10, 11 & 12.
                                                                                                                                             REFER ARCHITECT, CONTACT ENGINEER IF
                                                                                                                                             FURTHER INPUT REQUIRED.                                                      1000

                                                                                                                                                                       FINISHED SURFACE (TOW)

                                                                                                                                                                                                                        STONE CLADDING AS PER
                                                                                                                                                                                     1000 MIN                           ARCHITECTS DETAILS




                                                                                                                                                                                                                                                                           1100 MAX.
                                                                                                                                                                                       %%
                                                                                                                                                                                                                        N12 - 400 HORIZONTAL
                                                                                                                                                                                                                        (N12-200 TO LOWER 800)
                                                                                                                                                                                                                                                                                                 AT 2000mm MAX. SPACING, PROVIDE 600 HIGH x 190 WIDE
                                                                                                                                                                                                60                  FINISHED                                                                     BLOCKWORK BUTTRESSES BETWEEN WALLS, WITH
                                                                                                                                                STARTERS / VERTICAL BARS TO                                                                                                                      N12-400 CRS VERT & HORIZ, TYING WALLS AND
                                                                                                                                                                                                                    SURFACE
                                                                                                                                                BE 60mm FROM SOIL FACE                                                                                                                           STRENGTHENING. ENSURE N12-400 CRS HORIZ HAVE 200
                                                                                                                                                                                                                  (BOW & TOW)
                                                                                                                                                                                                                                                   STONE CLADDING AS PER                         COG INTO EACH WALL.
                                                                                                                                                                                                                  ENSURE                           ARCHITECTS DETAILS
                                                                                                                                                                                                                  ADEQUATE
                                                                                                                                                                                                                  DRAINAGE 60




                                                                                                                                                                                                                                                                           1200 MAX.
                                                                                                                                                                                                                                                  N12 - 400 HORIZONTAL




                                                                                                                                                                              800
                                                                                                                                                                                                                 CLEAN OUT
                                                                                                                                                                                       $$                        BLOCKS                           CLEAN OUT
                                                                                                                                                                                                                                                  BLOCKS                                        STONE CLADDING TO CONCEAL
                                                                                                                                                                                        100                         SL82 MESH                                                                   WALL-FOOTING JOINT




                                                                                                                                                                                       300




                                                                                                                                                                                                                                                                           300
                                                                                                                                                                                                                                                                                         FINISHED SURFACE (BOW)                               GROUND FLOOR FINISHED SURFACE

                                                                                                                                                                                                                                                           SL82 MESH




                                                                                                                                                                                                                                                                           200
                                                                                                                                                                                                                 N12 - 300
                                                                                                                                                                                    SCABBLE




                                                                                                                                                                                                                                                                           300
                                                                                                                                                                                                                 N16 - 400 CRS

                                                                                                                                                                                                                                                                                             N12 - 400 CRS




                                                                                                                                                                                                                                                                           300
                                                                                                                                                                                                                          N12 - 400 CRS
                                                                                                                                                                                                                                                   N12 - 300


                                                                                                                                                                                                                                                  850           300                    N12

                                                                                                                                                                                                                                   2200




                                                                                                                                                                                                                                                                         COMPACTED SUBGRADE                                            WALL TO BE DESIGNED FOR TERRACE
                                                                                                                                                                                                                                                                                                                                       WALL SURCHARGE AND CONSTRUCTED
                                                                                                                                                                                                                                                                                                                                       PRIOR TO TERRACE WALL




                                                                                                                                                                                                                                            ZONE OF INFLUENCE


                                                                                                                                                                                                                                                                                                                                                  GARAGE FINISHED SURFACE



                                                                                      APPROVED WATERPROOFING AND BANDAGE

                                                          30/20.10 CONTROL                    30/20.09 CONTROL
                                                          JOINT BLOCK                         JOINT BLOCK
                                                                                                                                                                                              LEGEND
                                                                                                                                                                                                $$      DENOTES PROVIDE Ø100 AG PIPE SURROUNDED WITH 10mm BLUE METAL, WRAPPED IN GEOFABRIC (BIDIM A14).
                                                                                                                                                                                                        PROVIDE AN OUTLET EACH SIDE THROUGH WALL WITH Ø80 DWV PIPE AS A WEEP HOLE WITH BIDIM A14 GEOFABRIC,
                                                                                                                                                                                                        FIXED WITH STAINLESS STEEL HOSE CLAMPS. ENSURE COVER TO STEEL REINFORCEMENT IS MAINTAINED.
                                       ELASTOMERIC SEALANT EACH SIDE                           CLADDING (WHERE REQUIRED)
                                       OF JOINT. EXPRESS / REFLECT JOINT                     VERTICAL REINFORCEMENT EACH SIDE OF JOINT                                                          %%      FREE DRAINING GRANULAR MATERIAL WRAPPED IN GEOFABRIC (BIDIM A14) AND PLACED IN EXCAVATION BEHIND WALL.
                                       THROUGH ANY WALL CLADDING.                          R12-400 GALV DOWEL BARS (400 LONG)                                                                           APPLY APPROVED BITUMINOUS WATERPROOFING MEMBRANE AND BANDAGE OVER COLD JOINT ONTO FOOTING.
                                                                                           GREASED ONE END                                                                                              ADD CORFLUTE MEMBRANE PROTECTION AS REQUIRED.

                                                          JOINTS TO BE PROVIDED AT 8000 MAXIMUM CENTRES
                                                                                                                                                                                              NOTES                                                                                                                                                                                                                                                         NOOSA COUNCIL
                                                                                                                                                                                              1.     REFER DRAWING 24572-C023 FOR SPECIFICATION NOTES.
                                                                                                                                                                                                                                                                                                                                                                                                                                                            APPROVED PLAN
                                                           VERTICAL CONTROL JOINT                                                                                                             2.     REFER TO THE ARCHITECT OR LANDSCAPE ARCHITECT FOR FINISHES AND WATER PROOFING.                                                                                                                                                                      MCU24//0125, OPW24/0158
                                                                                                                                                                                                                                                                                                                                                                                                                                                             & RAL24/0021
                                                                                                                                                                                                                                                                                                                                                                                                                                                               4 SEP 2025

              COPYRIGHT ©                                                                                           Associated Consultants        Client                                                                                                        Drawn                              Verified            Project                                                             Drawing Title                                                          Scale            Sheet Size
                                                                                                                                                                                                                                                                M.K.P.                             D.R.
              This drawing is subject to
              copyright in accordance with                                                                                                        DEVTEX NOMINEES                                                                                                                                                      73-77 EUMUNDI-NOOSA ROAD                                            RETAINING WALL DETAILS                                                  AS SHOWN            A1
              the agreement between TOD                                                                                                                                                                                                                         Designed                           Verified
              Consulting Pty Ltd (tc) and tc's                                                                                                    PTY LTD                                                                                                       M.K.P.                             D.R.                NOOSAVILLE, QLD 4566                                                SHEET 2                                                                Drawing Number
              client. This drawing shall only
              be used for this specific project.                                                                                                                                                                                                                Approved                           RPEQ No             RP DESCRIPTION  LOTS 1, 2 3, 48, 49 AND 50 ON SP298783                                                                                             24572-C024
              This drawing shall not be used                                                                                                                                                          Noosa: 07 5449 9600       Sunshine Coast: 07 5329 3190    D. REYNOLDS                        9072                LOCAL AUTHORITY NOOSA SHIRE COUNCIL
                                                                                                                                                                                                                                                                                                                       MCU APPROVAL                             HORIZ DATUM MGA DERIVED                    0     10     20     30    40     50      60            Sheet             Revision
              for construction until marked as                                                                                                                                                                   PO Box 61, Noosaville, QLD 4566                Signed
                                                    A    23.01.25   ISSUED FOR APPROVAL                      MKP                                                                                                                                                                                                       ROL APPROVAL                             VERT DATUM RL.13.595 AHD
              'Issued For Construction' in the
              revision description.                Rev    Date      Revision Description                    Drawn
                                                                                                                                                                                                      [email protected]     www.todconsulting.com
                                                                                                                                                                                                                      ABN 39 128 805 336                                                          30.04.25             OPW APPROVAL                             RL DATUM      PSM 53205                        MEASUREMENT BAR - INCREMENTS IN mm                     8 OF 23          A
Document Set ID: 23725764
Version: 1, Version Date: 09/05/2025

Used in these records

About this file

File size
18.4 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Complied Approved Plans - MCU24 0125, OPW24 0158 & RAL24 0021(As Published).pdf · 18.4 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.