Appendix D- Engineering Assessment
KG STRATEGIC STRATEGIC SOLUTIONS, CREATIVE THINKING Appendix D Engineering Assessment Request for a Change to the Conditions specification within the Decision Notice (Minor Change) 5 Pearl Street & 54 Elm Street, Cooroy 4563 QLD Lot 2 on RP64750 & Lot 2 RP153798 Cooroy Villas PTY LTD (ACN: 86 668 393 182) rgstrategic.com.au
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalLog in to download the original file
The download may take up to a minute.
Full text of the other 41 pages
Page 2
ENGINEERING SERVICES ASSESSMENT
PROPOSED TOWNHOUSE DEVELOPMENT AT
5 PEARL STREET
COOROY
Prepared for
Altum Property Group
Attention: Rob McCready
Document Reference
23098 - ESA/2
Record of Issue:
Issue Status Author Date Checked Date Authorised Date
18 Sep 19 Sep Henry Morgan 20 Sep
0 For Review Rick Cui Darren Yuen
2023 2023 RPEQ 11950 2023
26 Sep 28 Sep Henry Morgan 29 Sep
1 For Approval Rick Cui Darren Yuen
2023 2023 RPEQ 11950 2023
17 Jan 17 Jan Henry Morgan 17 Jan
2 For Approval Rick Cui Winston Boon
2024 2024 RPEQ 11950 2024
This investigation and report has been authorised by Mr Henry Morgan, a Director of Morgan
Consulting Engineers Pty Ltd.
Henry J Morgan RPEQ 11950 Friday, 19 January 2024
D:\JOBS\23-Jobs\23098 - 5 Pearl Street, Cooroy\Civil\Reports\ESA\Current\23098 - ESA - Rev 2.docx
Page 3
23098 - ESA/2
Page 2
Table of Contents
1 INTRODUCTION .......................................................................................... 3
2 EXISTING SITE ............................................................................................ 4
2.1 The Site ......................................................................................... 4
2.2 Surrounding Area .............................................................................. 4
3 PROPOSED DEVELOPMENT .............................................................................. 5
4 CODE ASSESSMENT ...................................................................................... 6
5 ENGINEERING ASSESSMENT ............................................................................. 7
5.1 Earthworks ..................................................................................... 7
5.2 Erosion and Sedimentation Control ......................................................... 7
5.3 Roadworks ...................................................................................... 7
5.4 Sewerage Reticulation........................................................................ 7
5.5 Water Reticulation ............................................................................ 8
5.6 Stormwater .................................................................................... 8
5.7 Electricity and Telecommunications ....................................................... 8
5.8 Gas .............................................................................................. 8
6 CONCLUSION ............................................................................................. 9
Appendix A DETAILED SITE SURVEY ..................................................................... 10
Appendix B PROPOSED DEVELOPMENT PLANS ......................................................... 11
Appendix C NSC CODE ASSESSMENTS.................................................................... 12
Appendix D CONCEPT BULK EARTHWORKS PLAN ...................................................... 13
Appendix E CONCEPT SERVICES PLANS ................................................................. 14
Appendix F DIAL-BEFORE-YOU-DIG PLANS ............................................................. 15
Engineering Services Assessment
Proposed Townhouse Development at 5 Pearl Street, Cooroy
Page 4
23098 - ESA/2
Page 3
1 INTRODUCTION
Morgan Consulting Engineers (MCE) has been engaged to provide an engineering services report to
address the servicing of the Proposed Townhouse Development at 5 Pearl Street, Cooroy.
This report will aim to assess how the site can be serviced by sewerage, water, roadworks, drainage,
electrical/telecommunications and gas infrastructure in accordance with the Noosa Shire Council
(NSC) Planning and Development standards and best practice.
It is noted that this report has been compiled based on information current at the time of report
printing and the recommendations supplied within this report are based solely on the above and
will be subject to full engineering review and detailed design once a Council development approval
has been obtained for this project.
Engineering Services Assessment
Proposed Townhouse Development at 5 Pearl Street, Cooroy
Page 5
23098 - ESA/2
Page 4
2 EXISTING SITE
2.1 The Site
The subject site, comprised of Lot 2 on RP153798 and Lot 2 on RP64750 is approximately 2,274m2
(0.2274ha) in area. The site is currently occupied by two existing residential dwellings, with
associated sheds and garages. Trees and shrubs are scattered throughout the subject site.
The subject site generally slopes from the southwest (with an approximate height of 107.41m AHD)
towards the northeast (with an approximate height of 105.2m AHD). Existing access to the subject
site is currently provided from Pearl Street and Elm Street.
Refer to Figure 2.1 for a Locality Plan and Appendix A for the Detailed Site Survey.
N
Sapphire Street Subject Site
Kauri Street
Elm Street
Pearl Street
Figure 2.1 – Locality Plan of Site and Surrounding Area
2.2 Surrounding Area
The site is located within the limits of the NSC region and is classified as Medium Density Residential
Zone. The site is surrounded by residential properties to the north and east and commercial
properties to the west and south. Cooroy Creek lies further west and Cooroy Train Station lies
further south west.
Engineering Services Assessment
Proposed Townhouse Development at 5 Pearl Street, Cooroy
Page 6
23098 - ESA/2
Page 5
3 PROPOSED DEVELOPMENT
The Proposed Townhouse Development primarily involves:
1. Three buildings containing a mix of two and three-bed units;
2. Carparking spaces for residents and visitors;
3. Vehicular access via Pearl Street, south of the site; and
4. Dedicated landscaping and planting throughout the site.
Refer to Appendix B for the Proposed Development Plans.
Engineering Services Assessment
Proposed Townhouse Development at 5 Pearl Street, Cooroy
Page 7
23098 - ESA/2
Page 6
4 CODE ASSESSMENT
The Proposed Townhouse Development has been assessed against the following NSC Planning
Scheme Codes (Refer to Appendix C):
1. NSC Earthworks Code;
2. NSC Existing Services Code; and
3. NSC Fire services for common private title code.
Engineering Services Assessment
Proposed Townhouse Development at 5 Pearl Street, Cooroy
Page 8
23098 - ESA/2
Page 7
5 ENGINEERING ASSESSMENT
5.1 Earthworks
Initially the subject site will be cleared of the existing structures and vegetation. Preliminary
earthworks will be undertaken to provide level building pads for the proposed development. The
internal driveway and hardstand pavement areas will be graded to suit the proposed finished floor
levels.
Retaining structures along the boundary will be wholly contained within the property and will be
no greater than 1.0 m in height to reduce impact to the visual amenity for surrounding properties.
All temporary batters will be constructed with a maximum batter of 1 in 2 unless otherwise stated
in the Geotechnical Investigation.
The proposed earthworks over the subject site will be carried out under Level 1 geotechnical
supervision and as per AS3798 – 2007 “Guidelines on earthworks for commercial and residential
developments”. All uncontrolled fill will be removed/replaced as per the NSC Earthworks Code.
Refer to Appendix C for the NSC Earthworks Code and Appendix D for the Concept Bulk Earthworks
Plan.
5.2 Erosion and Sedimentation Control
Sediment generated during the construction phase shall be dealt with in accordance with an Erosion
and Sediment Control Plan and kept on site during the construction phase.
Refer to the separate Site Based Stormwater Management Plan (SBSMP) prepared by Morgan
Consulting Engineers for further erosion and sedimentation control details.
5.3 Roadworks
The site will be accessed via a new driveway crossover from Pearl Street. The existing redundant
driveway crossover along Elm Street will be removed with the verge to be reinstated to tie in neatly
to the existing verge profile. The existing redundant driveway crossover along Pearl Street will be
removed and a new driveway crossover with new kerb and channel and verge will be constructed
in accordance with NSC’s policies and standards.
5.4 Sewerage Reticulation
Information obtained from Unitywater’s ArcGIS Mapping database indicates that there is a 225mm
diameter Asbestos Cement sewer main traversing across Lot 2 RP64750 of the subject site from the
eastern boundary to the northern boundary. An existing sewer manhole is located over the
aforementioned main within the centre of the property. There are two existing sewer property
connections currently servicing the site from this main and a sewer property connection servicing
the upstream property on Lot 1 RP153798.
It is proposed to decommission the existing sewer property connections servicing the subject site
and construct a new sewer property connection from the existing manhole to service the proposed
development. The existing property connection servicing the upstream property on Lot 1 SP153798
is proposed to be retained.
It is anticipated that the existing sewer infrastructure has sufficient capacity to service the
proposed development. However, this will be confirmed by Unitywater during detailed design.
Engineering Services Assessment
Proposed Townhouse Development at 5 Pearl Street, Cooroy
Page 9
23098 - ESA/2
Page 8
Refer to Appendix C for the NSC Existing Services Code, Appendix E for the Concept Services Plan,
and Appendix F for the Dial-Before-You-Dig Plans.
5.5 Water Reticulation
Information obtained from Unitywater’s ArcGIS Mapping, there is an existing 300mm diameter
Asbestos Cement water main traversing the northern verge of Pearl Street, south of the site. There
is also an existing 100mm diameter Asbestos Cement water main traversing the eastern verge of
Elm Street, west of the site.
It is proposed to decommission the existing service and meter assembly from Pearl Street and
upgrade the existing service and meter assembly from the water main within Elm Street to service
the proposed development.
There are two fire hydrants currently providing adequate fire hydrant coverage within the vicinity
of the site.
It is anticipated that the existing water infrastructure has sufficient capacity to service the
proposed development. However, this will be confirmed by Unitywater during detailed design.
Refer to Appendix C for the NSC Existing Services Code and NSC Fire services for common private
title code, Appendix E for the Concept Services Plan and Appendix F for the Dial-Before-You-Dig
Plans.
5.6 Stormwater
Refer to the separate Site Based Stormwater Management Plan (SBSMP) prepared by Morgan
Consulting Engineers for considerations to stormwater.
5.7 Electricity and Telecommunications
The site can be serviced by electricity at the following locations:
1. Overhead power lines situated along the southern verge of Pearl Street, south of the site.
2. Overhead power lines situated along the eastern and western verge of Elm Street, west of
the site.
The site can be serviced by telecommunications at the following locations:
1. Underground Telstra cables situated along the northern and southern verge of Pearl Street,
south of the site, and along the eastern verge of Elm Street, west of the site.
2. Underground NBN cables situated along northern and southern verge of Pearl Street, south
of the site, and along the eastern verge of Elm Street, west of the site.
Refer to Appendix F for the Dial-Before-You-Dig Plans.
5.8 Gas
There is no existing gas main within vicinity of the site.
Engineering Services Assessment
Proposed Townhouse Development at 5 Pearl Street, Cooroy
Page 10
23098 - ESA/2
Page 9
6 CONCLUSION
The Proposed Townhouse Development at 5 Pearl Street, Cooroy has been assessed to determine if
the proposed development can be serviced by sewerage, water, drainage and
electrical/telecommunications infrastructure in accordance with the Noosa Shire Council (NSC)
Planning and Development standards and best practice.
Based on all the findings outlined in this report, MCE believes that there are no engineering issues
in relation to this development that would preclude the above development from being approved
by Council.
Engineering Services Assessment
Proposed Townhouse Development at 5 Pearl Street, Cooroy
Page 11
23098 - ESA/2
Page 10
Appendix A
DETAILED SITE SURVEY
Engineering Services Assessment
Proposed Townhouse Development at 5 Pearl Street, Cooroy
Page 12
Skyline Surveyors
Suite 11C
Brightwater Corporate Centre PHONE
07 5493 4877
69 Attenuata Drive
MOUNTAIN CREEK QLD 4557
E: [email protected]
W: www.skysurv.com.au
Page 13
23098 - ESA/2
Page 11
Appendix B
PROPOSED DEVELOPMENT PLANS
Engineering Services Assessment
Proposed Townhouse Development at 5 Pearl Street, Cooroy
Page 14
5 5 g g g 7 g & é | g g
‘ : ( - ( 1
‘ | . 1 ja] Ea I BIO REKENTION
| \ : oof 1g] ‘ Ol
— —— == —— aonnseTRACK kA} bye fi for ret sm
7 fe He Aes t ree
‘ I ra 109m? oA : ia nov oe TERRACE 1 *t
I ita i TERRACE am TERRACE ‘ gi ke TERRACE TERRACE Dn gs oon
Wd | tg | ath : | ees be ce fp he |
I ‘ Uo Tham 1 Fost Va g fp tte
| a 2 { a |
! 5 ep |
a
Ls ‘| da] 2 | -
a } ie =
| C SpE |
“es ' a Ie ot |
| : ' 1 :
uw zt 4 RIGHEN KAICHEN i ‘ s, KITCHEN KITCHEN | as
zl ‘ P 1 = *
w B | ETSI ES ' 5 LISI Lie oF
gli Ld 2 Y :
a Z| \ i y 5 ' . |
j Z|: GARAGE ‘GARAGE BARAGE GARAGE ! | fc GARAGE GARAGE 4,
OLE u01 U02 : U03 ‘U04 : | U05 eel U06.. U07 vos ~
Z ie TYPEO1 TYPE02 TYPE02 "TYPEO2 TYPE02 : i TYPEO2>, TYPE02 TYPEO3
GARAGE i i n \ | ; .
og | 4 ele *
= | a 1a RS
4 | YS \ | a.
t \ ee f 2
sf , | a et
| tae LM vay |S 105m
| _ r 4 RSD =
| { frooo y 2500 _|s00y. yp ‘ 00 ~ ae Ll 1i20_ 1000 J.
| i 7% wy . *, BUILDING 01 *. \ BUILDING 02° ~~ - ---
| d . mop fe 6520 150) sm. 250 so. as0yp sa sa mye LL s +
| / . an <2 eh 2 7 dt
| z ns . 270 . +
| et g zt
| a 3 lg 5 ee
IL- ‘e | + 2 ~
¥ \ hy 2
j oo 4 ey
£ E £ 30.175, E 262°02 £ AY £ £
106.2m
105.6m
4 U09 U10 .
TyPE02 || TYPEO2 1 u12 |
GARAGE GARAGE TYPEQ2 TYPEO2
3 GARAGE ~ GARAGE.
KITCHEN L_ 13] E=4
KITCHEN
106m DEVELOPMENT,
‘eae win) ALTUM
/
'
'
lI ! FLOOR PLAN - LEVEL 1
'
“ t
! Development Approval
ah ; ‘ i . / north scale: 1:100@A1
1250 - 1x 1100L RECYCLING ‘ \ NS ‘ / scale: 1:200 @A3
= 1x 1100L GENERAL WASTE ao : ‘sO ‘ 1 issue: 06
date: 19-12-23
\
Project Number 7283-DA04
exist
TREE
‘PEARL STREET
BUCK BURNEJ/CISON
ARCHITECTURE | LANDSCAPE | INTERIOR | PROJECT MANAGEMENT
01 FLOOR PLAN LEVEL 1
1:100 meee
Page 15
23098 - ESA/2
Page 12
Appendix C
NSC CODE ASSESSMENTS
Engineering Services Assessment
Proposed Townhouse Development at 5 Pearl Street, Cooroy
Page 16
Earthworks Code
Noosa Council Plan July 2020
Performance and Acceptable Outcomes Table
Version: Sept 2020
Performance Outcomes Acceptable Outcomes Solution1 Comments Council Use
Effects of Works
Drainage AO1 RO1
PO1 Filled or excavated areas have a minimum Bulk earthworks will be designed to
Finished surface levels ensure land is gradient of 0.5% and drain to Council’s prevent ponding on site and on
free draining stormwater infrastructure where available, neighbouring land. All stormwater
or where stormwater infrastructure is not surface runoff and subsoil flows will
available, toward the street be directed to the lawful point of
discharge. Refer NSC Water
Quality and Drainage Code.
Hydraulics No acceptable outcome provided. RO2
PO2 The existing drainage
Change to the levels on site do not have characteristics of the site and
an adverse impact on the flooding and surrounding area has been
drainage characteristics off-site. considered. The proposal ensures
that surrounding properties and
downstream stormwater
infrastructure and waterways are
not adversely impacted by the
proposed development.
Geotechnical considerations AO3.1 RO3.1
PO3 Filling works are undertaken in accordance All filling will be undertaken in
Earthworks do not result in geotechnical with Council’s Planning Scheme Policy accordance with Council’s PSP6 –
instability on-site or to nearby premises. PSP6 Engineering design standards - Engineering Design Standards –
roads, drainage and earthworks. Roads and Drainage & Earthworks.
All excavation will be undertaken
with no adverse impact on
neighbouring properties or
surrounding infrastructure.
AO3.2 RO3.2
Where the filling is for residential, The proposal complies. Refer to
commercial or industrial purposes the RO3.1
works comply with Australian Standard -
Guidelines for earthworks on commercial
1
Solution: Acceptable Solution Page 1 of 5
A/S Alternative Solution D:\JOBS\23-Jobs\23098 - 5 Pearl Street, Cooroy\Civil\Reports\ESA\Working\Appendices\NSC Earthworks Code 2020.docx
N/A Not applicable to this proposal Job: 23098
Rev: 0
Site Address: 5 Pearl Street, Cooroy 22/09/2023
Page 17
Earthworks Code
Noosa Council Plan July 2020
Performance and Acceptable Outcomes Table
Version: Sept 2020
Performance Outcomes Acceptable Outcomes Solution1 Comments Council Use
& residential development.
Local amenity AO4.1 RO4.1
PO4 The following measures are implemented Water trucks shall be used to
Undertaking earthworks does not – minimise dust emissions. An
adversely impact on the amenity of the (a) regular water spraying of exposed Erosion and Sedimentation Control
local area by way of dust, noise or visual areas to suppress dust; Plan shall be prepared (prior to
amenity. (b) provision of dust stabilised or sealed commencement of construction).
internal roads;
(c) protective covering of exposed areas All disturbed areas will be stabilised
that are left for more than 2 weeks; should they be exposed for more
and than 2 weeks.
(d) unless a development permit provides
otherwise, disturbed areas are
revegetated using species identified
in Council's Planning Scheme Policy
PSP2 Landscaping.
AO4.2 RO4.2
Earthworks are undertaken only during the Filling and earthworks will only be
hours of 7:00am to 6:00pm, Monday to undertaken between the hours
Friday and 7:00am to 3:00pm on Saturday. nominated in AO4.2.
No work is undertaken on Sunday or
public holidays.
Vegetative waste AO5.1 RO5.1
PO5 Cleared vegetation is transported off-site Any vegetated waste encountered
Vegetation cleared from a development for disposal in an approved green waste will be dealt with in accordance with
site is disposed of in an environmentally disposal facility. the acceptable outcomes of PO5.
responsible manner. AO5.2 RO5.2
Cleared vegetation is mulched on-site and The proposal complies. Refer to
reused for landscaping of the finished RO5.1.
development.
AO5.3 RO5.3
Cleared vegetation is disposed of for the The proposal complies. Refer to
purpose of firewood RO5.1.
AO5.4 RO5.4
Disposal of vegetative waste by burning off The proposal complies. Refer to
1
Solution: Acceptable Solution Page 2 of 5
A/S Alternative Solution D:\JOBS\23-Jobs\23098 - 5 Pearl Street, Cooroy\Civil\Reports\ESA\Working\Appendices\NSC Earthworks Code 2020.docx
N/A Not applicable to this proposal Job: 23098
Rev: 0
Site Address: 5 Pearl Street, Cooroy 22/09/2023
Page 18
Earthworks Code
Noosa Council Plan July 2020
Performance and Acceptable Outcomes Table
Version: Sept 2020
Performance Outcomes Acceptable Outcomes Solution1 Comments Council Use
is avoided. RO5.1.
Managing contamination risk AO6.1 RO6.1
PO6 Fill material is solid clean earth, free of All fill imported to site will be free of
Materials used as fill are suitable for putrescible or refuse material, vegetation, contaminants.
development and future acid sulfate soils, building or construction
use of the land and filling or excavation material or other material or contaminants.
works do not result in
the contamination of land.
AO6.2
The site is not on the contaminated land
RO6.2
A search will be undertaken by
register. others to verify whether the
development fails on land listed on
the contaminated land register.
Haulage activity and amenity No acceptable outcome provided. RO7
PO7 Haul routes from trucks used to
Haulage of material to and from a site transport fill/spoil and material to
ensures— and from the site will only use major
(a) minimal disturbance to neighbouring road route to the site, haul trucks
properties and properties along the will use minor roads with the
haulage route; and shortest, most direct route that will
(b) Council’s road infrastructure including have the least amount of
pavements is not adversely affected. environmental impact. This will be
clearly documented in the
Construction Management Plan.
Extent of earthworks AO8 RO8
PO8 All earthworks, including cut and fill All earthworks will be contained
The layout of the development provides batters, retaining walls and the like are within the subject site. Any minor
adequate, clearly defined and easily contained within the subject site. earthworks undertaken external to
accessible— the site will only be undertaken
(a) on-site vehicle parking and after all approvals and/or consent is
manoeuvring areas; and obtained from Council and
(b) loading and manoeuvring areas for neighbouring property owners.
delivery and service vehicles.
Sloping sites AO9 RO9
PO9 Cut or fill is less than 1.5 metres in depth The proposal complies.
On sloping sites development follows the relative to the natural ground level.
natural landform wherever practical and
1
Solution: Acceptable Solution Page 3 of 5
A/S Alternative Solution D:\JOBS\23-Jobs\23098 - 5 Pearl Street, Cooroy\Civil\Reports\ESA\Working\Appendices\NSC Earthworks Code 2020.docx
N/A Not applicable to this proposal Job: 23098
Rev: 0
Site Address: 5 Pearl Street, Cooroy 22/09/2023
Page 19
Earthworks Code
Noosa Council Plan July 2020
Performance and Acceptable Outcomes Table
Version: Sept 2020
Performance Outcomes Acceptable Outcomes Solution1 Comments Council Use
excavation or filling is minimal.
Infrastructure protection No acceptable outcome provided. RO10
PO10 Prior to construction the contractor
Earthworks and vehicular access do not will confirm the correct locations of
adversely impact on the capacity,
operations and maintenance of existing
all existing services whether
indicated or not on the plans. The
infrastructure construction of the proposed
development will ensure the
protection of all existing services or
public utilities.
Environmental protection No acceptable outcome provided. RO11
PO11 An Erosion and Sediment Control
Earthworks minimise any adverse impact Plan shall be prepared (prior to
upon groundwater, watercourses, commencement of construction)
drainage lines, wetlands, and native and maintained for the
vegetation management of the sediment laden
stormwater runoff during the
construction phase in accordance
with Council’s PSP6 – Engineering
Design Standards – Roads and
Drainage & Earthworks.
Dams AO12.1
PO12 Where the site is in the Rural zone—
Dam location and construction does not (a) the land has a slope of less than 25% N/A
impact upon neighbouring properties or (1:4);
road reserves, in terms of— (b) the earthworks including cut and fill
(a) hydrology; batters and retaining walls are setback
(b) alteration of existing overland flow a minimum of 50 metres from the
paths and patterns; property boundary; and
(c) landslide or failure of dam wall; and (c) the size of the lot is greater than 5
(d) effluent disposal areas hectares.
AO12.2
Where the site is in the Rural residential
zone or the Rural zone and the lot is less
than 5 hectares:
(a) the land has a slope of less than 1:6;
1
Solution: Acceptable Solution Page 4 of 5
A/S Alternative Solution D:\JOBS\23-Jobs\23098 - 5 Pearl Street, Cooroy\Civil\Reports\ESA\Working\Appendices\NSC Earthworks Code 2020.docx
N/A Not applicable to this proposal Job: 23098
Rev: 0
Site Address: 5 Pearl Street, Cooroy 22/09/2023
Page 20
Earthworks Code
Noosa Council Plan July 2020
Performance and Acceptable Outcomes Table
Version: Sept 2020
Performance Outcomes Acceptable Outcomes Solution1 Comments Council Use
(b) the earthworks including cut and fill N/A
batters and retaining walls are setback
a minimum of 20 metres from the
property boundary; and
(c) the dam work involves less than
500m³ of material.
AO12.3
For all other zones— N/A
No acceptable outcome provided.
1
Solution: Acceptable Solution Page 5 of 5
A/S Alternative Solution D:\JOBS\23-Jobs\23098 - 5 Pearl Street, Cooroy\Civil\Reports\ESA\Working\Appendices\NSC Earthworks Code 2020.docx
N/A Not applicable to this proposal Job: 23098
Rev: 0
Site Address: 5 Pearl Street, Cooroy 22/09/2023
Page 21
Existing Services Code
Noosa Council Plan July 2020
Performance and Acceptable Outcomes Table
Version: Sept 2020
Performance Outcomes Acceptable Outcomes Solution1 Comments Council Use
Setbacks, Easements and Maintenance
PO1 No acceptable outcome provided. RO1
Development near a stormwater drain, All buildings and structures will be
overland flow path or associated located outside of the zone of
structure does not – influence and building piers and
(a) Adversely affect the function of the footings will be extended below the
service; zone of influence for all existing and
(b) Place an additional load on the proposed underground stormwater
service; and services.
(c) Unduly increase future maintenance
costs.
PO2 AO2.1
Maintenance access is to be provided to For trunk infrastructure, a registered
all stormwater drains, overland flow easement in favour of Council is created N/A
paths and associated structures. over all underground infrastructure located
in private property.
AO2.2
The width of the easement required is in
accordance with Council’s Planning
Scheme Policy PSP6 Engineering Design N/A
Standards – Roads, drainage and
earthworks.
AO2.3
The easement is centred over the N/A
centreline of the infrastructure.
1
Solution: Acceptable Solution Page 1 of 1
A/S Alternative Solution D:\JOBS\23-Jobs\23098 - 5 Pearl Street, Cooroy\Civil\Reports\ESA\Working\Appendices\NSC Existing Services Code 2020.docx
N/A Not applicable to this proposal Job: 23098
Rev: 0
Site Address: 5 Pearl Street, Cooroy 22/09/2023
Page 22
Fire services for common private title code
Noosa Council Plan July 2020
Performance and Acceptable Outcomes Table
Version: Sept 2020
Performance Outcomes Acceptable Outcomes Solution1 Comments Council Use
Installation of hydrant AO1.1 RO1.1
PO1 Fire hydrant placement and technical requirements The proposal complies. Two
Fire hydrants are installed and located to for residential streets and common access ways fire hydrants are located
enable QFES vehicles to access water
safely, effectively and efficiently.
within common private title are in accordance with:
Australian Standard (AS) 2419.1 – 2005 Fire
within close proximity of the
site.
hydrant installations; and QFES: Fire Hydrant and
vehicle access guidelines for residential, commercial
and industrial lots.
AO1.2
Fire hydrant placement and technical requirements
for commercial and industrial streets and access
ways within streets serving commercial properties,
such as factories, warehouses and offices, are in
accordance with: Australian Standard (AS) 2419.1 –
2005 Fire hydrant installations; and QFES: Fire
Hydrant and vehicle access guidelines for
residential, commercial and industrial lots N/A
Editor’s Note— Design and technical requirements
for infrastructure from third party providers are to be
in addition to, and integrated where possible, into
the overall design, built form and landscaping
requirements for the development.
PO2 No acceptable outcome provided.
Road widths and construction within the
development are adequate for QFES
vehicles to gain access to a safe working
area close to buildings and near water
supplies whether or not on-street parking N/A
spaces are occupied.
Editor’s Note—Roads should be
designed and constructed in
accordance with Road Planning and
Design manual- 2nd edition.
1
Solution: Acceptable Solution Page 1 of 1
A/S Alternative Solution D:\JOBS\23-Jobs\23098 - 5 Pearl Street, Cooroy\Civil\Reports\ESA\Working\Appendices\NSC Fire services for common private title Code 2020.docx
N/A Not applicable to this proposal Job: 23098
Rev: 0
Site Address: 5 Pearl Street, Cooroy 22/09/2023
Page 23
23098 - ESA/2
Page 13
Appendix D
CONCEPT BULK EARTHWORKS PLAN
Engineering Services Assessment
Proposed Townhouse Development at 5 Pearl Street, Cooroy
Page 24
P: (07) 3369 8411
F: (07) 3369 1893
E : [email protected]
© Morgan Consulting Engineers
This drawing is not to be copied,
retai ned or used without the
permission of the copyright holder.
1 GREAT GEORGE STREET
PADDINGTON Q LD 4 0 6 4
Page 25
P: (07) 3369 8411
F: (07) 3369 1893
E : [email protected]
© Morgan Consulting Engineers
This drawing is not to be copied,
retai ned or used without the
permission of the copyright holder.
1 GREAT GEORGE STREET
PADDINGTON Q LD 4 0 6 4
Page 26
23098 - ESA/2
Page 14
Appendix E
CONCEPT SERVICES PLANS
Engineering Services Assessment
Proposed Townhouse Development at 5 Pearl Street, Cooroy
Page 27
P: (07) 3369 8411
F: (07) 3369 1893
E : [email protected]
© Morgan Consulting Engineers
This drawing is not to be copied,
retai ned or used without the
permission of the copyright holder.
1 GREAT GEORGE STREET
PADDINGTON Q LD 4 0 6 4
Page 28
23098 - ESA/2
Page 15
Appendix F
DIAL-BEFORE-YOU-DIG PLANS
Engineering Services Assessment
Proposed Townhouse Development at 5 Pearl Street, Cooroy
Page 29
Paper size A3 Map has been designed to be reproduced in colour All underground cables shall be treated as being energised. Where a cable is located that is not represented on the ENERGEX BYDA map, then ENERGEX shall be contacted immediately. For Emergency Situations please call 13 19 62 SOGOU: ’ 7 7 ri *< e. P2066763 | * - | -7 a ° a ° a ° 7 -—$— e 7 ° 7 e 7 7 ¢ 7 ¢ 7 P87351-A P2096764 P768369 RY energex BYDA Sequence: 225352172 Date: 01/06/2023 Scale: 1:500 Tile No: 1 For a full list of Map Symbols, please refer to the supplied BYDA Symbology Legend page AS5488 Category “D” Plan N s DISCLAIMER: While reasonable measures have been taken to ensure the accuracy of the information contained in this plan response, neither Energex nor PelicanCorp shall have any liability whatsoever in relation to any loss, damage, cost or expense arising from the use of this plan response or the information contained in it or the completeness or accuracy of such information. Use of such information is This output provides details of the ENERGEX electrical network. As variations map exist no responsibility is incurred by ENERGEX for the accuracy or completeness of the information provided. Exact positions of cables and electrical connectivity should be confirmed on site subject to and constitutes acceptance of these terms. Plans generated 01/06/2023 by Pelicancorp TicketAccess Software | www.pelicancorp.com Energex - Response Plan.docx (13 Mar 2023)
Page 30
Paper size A3 Map has been designed to be reproduced in colour All underground cables shall be treated as being energised. Where a cable is located that is not represented on the ENERGEX BYDA map, then ENERGEX shall be contacted immediately. For Emergency Situations please call 13 19 62 SOGOU: i ee P90167-A } I RY energex ree BYDA Sequence: 225352172 Date: 01/06/2023 Scale: 1:500 Tile No: 2 | For a full list of Map Se | en Sar | Symbols, please refer to the supplied i ee BYDA Symbology Legend page AS5488 Category “D” Plan N s DISCLAIMER: While reasonable measures have been taken to ensure the accuracy of the information contained in this plan response, neither Energex nor PelicanCorp shall have any liability whatsoever in relation to any loss, damage, cost or expense arising from the use of this plan response or the information contained in it or the i completeness or accuracy of such — information. Use of such information is This output provides details of the ENERGEX electrical network. As variations map exist no responsibility is incurred by ENERGEX for the accuracy or completeness of the information provided. Exact positions of cables and electrical connectivity should be confirmed on site subject to and constitutes acceptance of these terms. Plans generated 01/06/2023 by Pelicancorp TicketAccess Software | www.pelicancorp.com Energex - Response Plan.docx (13 Mar 2023)
Page 31
Paper size A3 Map has been designed to be reproduced in colour
All underground cables shall be treated as being energised. Where a cable is located that is
not represented on the ENERGEX BYDA map, then ENERGEX shall be contacted immediately.
For Emergency Situations
please call 13 19 62
Ios
P2066758
P768367-A
X768368
P30$733
P7694-C
+C
SOC8 31 ¥
RIF
energex
BYDA
Sequence: 225352172
Date: 01/06/2023
Scale: 1:500
Tile No: 3
For a full list of Map
Symbols, please
refer to the supplied
BYDA Symbology
Legend page
AS5488 Category “D” Plan
N
s
DISCLAIMER: While reasonable
measures have been taken to ensure the
accuracy of the information contained in
this plan response, neither Energex nor
PelicanCorp shall have any liability
whatsoever in relation to any loss,
damage, cost or expense arising from
the use of this plan response or the
information contained in it or the
completeness or accuracy of such
information. Use of such information is
This output provides details of the ENERGEX electrical network. As variations map exist no responsibility is incurred by ENERGEX for the
accuracy or completeness of the information provided. Exact positions of cables and electrical connectivity should be confirmed on site.
subject to and constitutes acceptance of
these terms.
Plans generated 01/06/2023 by Pelicancorp TicketAccess Software | www.pelicancorp.com
Energex - Response Plan.docx (13 Mar 2023)
Page 32
Paper size A3 Map has been designed to be reproduced in colour All underground cables shall be treated as being energised. Where a cable is located that is not represented on the ENERGEX BYDA map, then ENERGEX shall be contacted immediately. For Emergency Situations please call 13 19 62 OU é" | Ox [ a Sse —_—— oo" - ees . X7695-C ' P83450-A ty , a / as =] rea iD energex BYDA Sequence: 225352172 Date: 01/06/2023 Scale: 1:500 Tile No: 4 For a full list of Map Symbols, please refer to the supplied BYDA Symbology Legend page AS5488 Category “D” Plan N s DISCLAIMER: While reasonable measures have been taken to ensure the accuracy of the information contained in this plan response, neither Energex nor PelicanCorp shall have any liability whatsoever in relation to any loss, damage, cost or expense arising from the use of this plan response or the information contained in it or the completeness or accuracy of such information. Use of such information is P7696-C This output provides details of the ENERGEX electrical network. As variations map exist no responsibility is incurred by ENERGEX for the accuracy or completeness of the information provided. Exact positions of cables and electrical connectivity should be confirmed on site. subject to and constitutes acceptance of these terms. Plans generated 01/06/2023 by Pelicancorp TicketAccess Software | www.pelicancorp.com Energex - Response Plan.docx (13 Mar 2023)
Page 33
All underground cables shall be treated as being energised. Where a cable is located that is Paper size A3 Map has been designed to be reproduced in colour not represented on the ENERGEX BYDA map, then ENERGEX shall be contacted immediately. os For Emergency Situations please call 13 19 62 Ios P2066753/, AN _b768366-A o. 1529 oe : P19175$—_(-) P191754 02 © . lal &) P301528-A \ ,P308052 (x) P7705-D P60216-A SYD energex BYDA Sequence: 225352172 Date: 01/06/2023 Scale: 1:500 Tile No: 5 For a full list of Map Symbols, please refer to the supplied BYDA Symbology Legend page AS5488 Category “D” Plan N s DISCLAIMER: While reasonable measures have been taken to ensure the accuracy of the information contained in this plan response, neither Energex nor PelicanCorp shall have any liability whatsoever in relation to any loss, damage, cost or expense arising from the use of this plan response or the information contained in it or the completeness or accuracy of such This output provides details of the ENERGEX electrical network. As variations map exist no responsibility is incurred by ENERGEX for the accuracy or completeness of the information provided. Exact positions of cables and electrical connectivity should be confirmed on site. information. Use of such information is subject to and constitutes acceptance of these terms. Plans generated 01/06/2023 by Pelicancorp TicketAccess Software | www.pelicancorp.com Energex - Response Plan.docx (13 Mar 2023)
Page 34
Paper size A3 Map has been designed to be reproduced in colour For Emergency Situations please call 13 19 62 All underground cables shall be treated as being energised. Where a cable is located that is not represented on the ENERGEX BYDA map, then ENERGEX shall be contacted immediately. P7703-C [an P7702-B P757857 P757858 Seas P7699-B oo P7701-C Sequence: 225352172 Date: 01/06/2023 Scale: 1:500 Tile No: 6 SSF SWZ energex BYDA For a full list of Map Symbols, please refer to the supplied BYDA Symbology Legend page AS5488 Category “D” Plan N s DISCLAIMER: While reasonable measures have been taken to ensure the accuracy of the information contained in this plan response, neither Energex nor PelicanCorp shall have any liability whatsoever in relation to any loss, damage, cost or expense arising from the use of this plan response or the information contained in it or the completeness or accuracy of such information. Use of such information is subject to and constitutes acceptance of these terms. This output provides details of the ENERGEX electrical network. As variations map exist no responsibility is incurred by ENERGEX for the accuracy or completeness of the information provided. Exact positions of cables and electrical connectivity should be confirmed on site. Energex - Response Plan.docx (13 Mar 2023) Plans generated 01/06/2023 by Pelicancorp TicketAccess Software | www.pelicancorp.com
Page 35
rad 1 pease | o : 5 Ss : red Ses | 10.6 = | a¥ 2 ° z 1 P20-18, 0m wile 7. ty 1 P35-1.34 oy () a : 4 © b } 3 | yee P5160 75 z py 8) x Pet a 4 | | g aa} a] i fee. fb PEAR: Ba | SAPPHIRE sy 26. ay z P2e.. 1 P50-7-23, en Emergency Contacts You must immediately report any damage to the nbn™ network that you are/become aware of telephone - 1800 626 329. . Notification may be by
Page 36
TY
ae NOOSA
59
nN
yous ee ze
Sequence No: 225352170
Job No: 34328300
Location: 5 Pearl Street, Cooroy, QLD 4563
12
YQ
3
z
a
Q ea
%
PPhire Sp
a ae
-_ —.
~,
~N
*
XN
*
N
‘ 16
|,
So
So. Sh.
5
Plans generated 01 Jun 2023 by Pelicancorp TicketAccess Software | www.pelicancorp.com
\
|
17
BEFORE
YOU DIG
www dyda.com.au
Legend
Stormwater Chamber
@ Manhole
@ Pit
A Water Quality
A Structures
Stormwater Pipe
~~ Pipe
Allotment
ec Culvert
— — TeleComm Networks
—— Open Drain
=~ © Flood Alert Station Pipe
=== | eachate Rising Main
Water Quality
Easement
Covenant
Scale: 1:1000
\ Expires: 29 Jun 2023
DISCLAIMER: While reasonable
measures have been taken to ensure the
accuracy of the information contained in
this plan response, neither Noosa
Council nor PelicanCorp shall have any
liability whatsoever in relation to any
loss, damage, cost or expense arising
from the use of this plan response or the
information contained in it or the
completeness or accuracy of such
information. Use of such information is
subject to and constitutes acceptance of
these terms.
AU.Noosa C (QLD) - Response Plan.docx (22 Mar 2023)
Page 37
ws PA Comet 11 1A 13 Tile No: Plans generated 01 Jun 2023 by Pelicancorp TicketAccess Software | www.pelicancorp.com ¢ 7 ¢ 7 Coorgy Connection Road / 4’ 4’ —— , Sequence No: 225352170 Job No: 34328300 Location: 5 Pearl Street, Cooroy, QLD 4563 52 5 / 7 | 45 I) 7 Legend 1 Stormwater Chamber ! @ Manhole ' & Pearl Street / @ Pit e- j A Water Quality ’ A Structures ot ; Stormwater Pipe 48 x —— Pipe oO 5 Allotment § ace Culvert 5 ua a — — TeleComm Networks —— Open Drain =~ © Flood Alert Station Pipe 6 8 12 4 fe B 7 @ of ee 7 16 7 yy === | eachate Rising Main Pearl Lane ° 7 Water Quality + - Easement Covenant , Scale: 1:1000 \ Expires: 29 Jun 2023 DISCLAIMER: While reasonable measures have been taken to ensure the accuracy of the information contained in this plan response, neither Noosa Council nor PelicanCorp shall have any liability whatsoever in relation to any loss, damage, cost or expense arising from the use of this plan response or the information contained in it or the completeness or accuracy of such information. Use of such information is subject to and constitutes acceptance of Cooroy,- Noosa Road Diamong Street 2 4 6 6 6 1D 14] these terms. AU.Noosa C (QLD) - Response Plan.docx (22 Mar 2023)
Page 38
MAPLE ST WARNING: This document is confidential and may also be privileged. Confidentiality nor privilege is not waived or destroyed by virtue of it being transmitted to an incorrect addressee. Unauthorised use of the contents is therefore strictly prohibited. Any information contained in this document that has been extracted from our records is believed to be accurate, but no responsibility is assumed for any error or omission. Optus Plans and information supplied are valid for 30 days from the date of issue. If this timeline has elapsed, please raise a new enquiry. Sequence Number: 225352171 Date Generated: 01 Jun 2023 For all Optus DBYD plan enquiries — Email: [email protected] YOU DIG For urgent onsite assistance contact 1800 505 777 pallet detect Optus Limited ACN 052 833 208 . Plans generated 01 Jun 2023 by Pelicancorp TicketAccess Software | www.pelicancorp.com
Page 39
:
. Sequence No: 225352173 VOU DIG
: Job No: 34328300 www.1100.com.au
Networks ' Location: 5 Pearl Street, Cooroy, QLD 4563 The Essential First Step.
21
28
8
& 30
Vv
7 Vv
s&s
¢ 32
Ss
os 25
<
36 eine?
ow
13
1
\ 9
+ 38 7
5
2 3
18% 40 ‘
\“
\ kL Roe 35
COOROY SHOW GROUND 1 o 31 ow 3
| £ 31
7 s 29
2 | 44
27
' 25
/ 23
10
‘ 46
/ 2
808 12 48 38
9 36
50
14 oe 34
M, 32
APL L 16 << 30
9
7 16 52 28
° 18 26 ce’ 20
41 yi 22
| 20 pw? 24
43 26
EMEp 22 54 3
ALD ST 1/2 DI 25 7 \* x
. AMOND sr pe
. ww
Tile No:4 w
Legend | Scale: 1:2500 DISCLAIMER: While reasonable measures have been taken to ensure the accuracy of the information
N Cable contained in this plan response, neither Visionstream or PelicanCorp shall have any liability whatsoever in
relation to any loss, damage, cost or expense arising from the use of this plan response or the information
A contained in it or the completeness or accuracy of such information. Use of such information is subject to and
constitutes acceptance of these terms.
Plans generated 01/06/2023 by Pelicancorp TicketAccess Software | www.pelicancorp.com AU.Visionstream - Response Plan.docx (29 Nov 2018)
Page 40
2 Cable Plan %
“<o ut
—P35 0.5
OC|10mm]
2xOC[ 6mm]
P5010.0
OC[ 4mm]
OC[16mm]
OC[10mm]
Cl 4mm TOU7802
Cl23mm] (5)
, P5010.0
OC[ 4mm]
SE1-SE12
SHOP1-SHOP10">~
U1-U8
Mc 1.0
OC[10mm]
3xOC[23mm]
E80 15.5
OU tum]
7S
3 P20 30.0
3 OC|13mm] se
3 a Ng
Report Damage: https://service.telstra.com.au/customer/general/forms/report-damage-to-telstra-equipment Seq uence Number: 2253521 76
Ph - 13 22 03
Email - [email protected] -cCj . ;
Planned Services - ph 1800 653 935 (AEST bus hrs only) General Enquiries CAUTION: Fibre optic and/ or major network present
TELSTRA LIMITED ACN. 086 174 781 in plot area. Please read the Duty of Care and
contact Telstra Plan Services should you require
Generated On 01/06/2023 14:45:27 any assistance.
The above plan must be viewed in conjunction with the Mains Cable Plan on the following page
WARNING
Telstra plans and location information conform to Quality Level "D" of the Australian Standard AS 5488-Classification of Subsurface Utility Information.
As such, Telstra supplied location information is indicative only.Spatial accuracy is not applicable to Quality Level D.
Refer to AS 5488 for further details. The exact position of Telstra assets can only be validated by physically exposing it.
Telstra does not warrant or hold out that its plans are accurate and accepts no responsibility for any inaccuracy.
Further on site investigation is required to validate the exact location of Telstra plant prior to commencing construction work.
A Certified Locating Organisation is an essential part of the process to validate the exact location of Telstra assets and to ensure the asset is protected during construction works.
See the Steps- Telstra Duty of Care that was provided in the email response.
Page 1 of 2
Page 41
UNITYWATER BYDA MAP
Sequence Number: 225352175
Job Number: 34328300
Printed On: 1/06/2023
Emergency Situations
Call Unitywater:
1300 086 489
This information on this plan is valid
for 30 days from "Printed On" date.
Legend
Sewer Gravity Main
Trunk Main
i | Extent of Unitywater Area
Water
Water Pump Station Reticulation Main
™ Water Service Overflow Main
%* ~~ Water Valve === Sewer Pipe (Abandoned)
S P. Mai
-———— Water Pipe (Abandoned) ewer Pressure Main
Pressure Sewer
@ = = Water Hydrant
Rising Main
[Water Fitting
Vacuum Main
Water Main
; Pressure Sewer Service
———— Trunk Main
Sewer Service
Reticulation Main
Recycled Water
%* ~~ Recycled Water Valve
Sewer
3]
Recycled Water Pump Station
Sewer Pump Station
© Sewer Manhole
@ = Recycled Water Hydrant
= Sewer Valve
[Recycled Water Fitting
[Sewer Fitting
Recycled Water
“—="=" Pipe (Abandoned)
Recycled Water Main
Map Tile: 1
Scale: 1:1000 N
(If printed at 100%
on A3 size paper)
Before You Dig Australia
Geospatial Information Systems
Ground Floor, 33 King St
Caboolture QLD 4510
Inquiries: 1300 O Unity (1300 086 489)
Email: [email protected]
Disclaimer
These Maps are supplied under the following conditions:-
Mapping details are supplied from information contained in Unitywater’s
records which may have been furnished to Unitywater by other persons.
Unitywater gives no warranty or guarantee of any kind, expressed,
implied, or statutory, to the correctness or accuracy of the map details
or the degree of compliance with any standards in this matter. Persons
making decisions with financial or legal implications must not rely upon
the map details shown on this plan for the purpose of determining
whether any particular facts or circumstances exist and Unitywater
(and its officers and agents) expressly disclaim responsibility for any
loss or damage suffered as a result of placing reliance upon this information.
ozoLvd2
3RP56236
Ss
>
\
\
2SP221081
13
3SP327330
11
Sei A 1SP221081
301CP827089
98MCH810557
ELM STREET
M)
¢ 1RP 155843
48
ae
|
44SP 196689
44-46
=
ps
\
|
-
|
1
|
18C5606 |
| |
3
a
o
51056013
50056013
Oo
49C56013
17C5606
6 8
PEARL LAN
3C5606 4C5606
5 7
16C5606 |
Nh
48056013
10
—
12
5CP889589
15C5606
-
|
— 5C5606 —o—_,n
9 7sP179868 |!
79109240.
oa
47056013
|
|
4
oe
37056013
14C5606
12
|
1
38056013
=a
8C5606 15
69C56013
8CP889587
9C5606
17 |
Page 42
a Ci STRATEGIC STRATEGIC SOLUTIONS, CREATIVE THINKING rgstrategic.com.au