Approved Plans MCU20-0020
Plans and drawings: the text below has words only, no drawings.
APPROVAL RELATES TO INSTALLATION
OF 4 X 20 METRE HIGH LIGHT TOWERS ON
FIELD 5 ONLY
R55
.00
0
0
00
00
0.0
3.
5
R4
R
CRICKET FIELDS
3.8
0
VEGETATION CLEARING AS REQUIRED Approximate location of MSB
0
and Pole Top transformer.
BIORETENTION SWALE Electrician to calculate
prospective fault current level
0
80
for switchgear specification
3.
FIELD INLET
5.400
6.00
R30.0
6.000
R30.000
5.40
6.000
0
5.400
0
00
Locate existing 100mm conduit
3.000
and extend to pit located at
LP12. Remove pit in this area R1
and re-use if in good condition 0.
00
3.00
0
0.500
Underground conduit to connect
4.000
0
8.000
into the existing electrical pit if
0
00
located outside of 5M run off
0.00
0.500
5.000
4.0
8.000
0
R10
0.00
R10
1X 50MM HD ELECTRICAL CONDUIT.
BOLLARD
ELECTRICAL PIT
00
LP12 - EX CCT
3.0
Install new 35mm XLPE cables and 6 core 240v control
cable into new light pole base. Multi-core cables to control SCOREBOARD TO BE
lights at 50% and 100% light output.. Refer to Empyrean
lighting design version 9 for detailed RELOCATED AS PART
OF DETAIL DESIGN
1X 50MM HD ELECTRICAL CONDUIT.
LP11 - EX CCT
Terminate already installed cables into new light pole
base. Use existing multicore cables to control lights at
50% and 100% light output.. Refer to Empyrean
HEAVY DUTY VEHICLE CROSSING
lighting design version 9 for detailed design
FIELD 5
0
100.00
5.000
6.000
5.400
0
100.00
5.400
BIORETENTION RETAINING WALL AS PART
68.000 3.000
SWALE 3.000 OF DETAIL DESIGN
5.000
2.000 68.000
DWG E03
SERVICE ROAD
5.000 EXISTING LIGHT POLES -
FIELD INLET INSTALL 1X 410W LED FLOOD
3.000 TO EACH POLE FOR CASUAL 5.000
1.500 LIGHTING
3.000
5.000 2.500
LP10 - EX CCT 1X 50MM HD ELECTRICAL CONDUIT.
Install new 35mm XLPE cables and 6 core 240v control
cable into new light pole base. Multi-core cables to control
lights at 50% and 100% light output.. Refer to Empyrean
lighting design version 9 for detailed
R50.000
LP9 - EX CCT
Terminate already installed cables into new light pole
base. Use existing multicore cables to control lights at
50% and 100% light output.. Refer to Empyrean
lighting design version 9 for detailed design
8.000
5.000
8.000
5.000
R50.000 6.000
7.000
3.000
0.500 RUGBY LEAGUE FIELDS
3.000
70.000
3.000
3.500
0.500
2.000
7.000
01 11.02.20 PRELIMINARY DESIGN CH MG
LP8 - EX CCT 3.000
4.000
Relocate existing 16sqMM 2 phase feeds from 3.000 00 09.01.20 PRELIMINARY CH MG
timber light poles into the new galvanised light
0.500 7.000
poles. Place the pole in location the avoid electrical
50.000
joins. Refer to Empyrean lighting design version 9
for detailed design 3.000 Rev Date Description By Chk
70.000
The concepts and information contained in this document are the copyright of M2 Electrical
LP7 - CCT4
Provide new 2 phase 10sqmm SDI Pty Ltd. Use or copying of the document in whole or in part without the written permission of
7.000
cables from TDB2 to light pole. Refer to M2 Electrical Pty Ltd constitutes an infringement of copyright.
Empyrean lighting design version 9 for
detailed design LP4 - EX CCT
3.000 Do not scale drawings. If in doubt, ask!
Relocate existing 16sqMM 2 phase feeds from 3.000
50.000
timber light poles into the new galvanised light
poles. Place the pole in location the avoid 1.000
FIELD 3&4
electrical joins. Refer to Empyrean lighting design
version 9 for detailed design
3.000
TDB2
FIELD 1&2
LP3 - CCT2
Provide new 2 phase 10sqmm SDI
cables from TDB1 to light pole.
Refer to Empyrean lighting design
version 9 for detailed design
DWG E02
3.000
TDB2 TDB1
1X 50MM HD ELECTRICAL CONDUIT.
Decomission existing switchboard and provide a new
Conduit to rise up post in undercover
suitable enclosure to control Field 3 and 4 lighting.
area and follow roof structure to TDB1 6/94 Delta Street, Geebung QLD 4034
Relocate to undercover area and extend submains
PO Box 105, Virginia BC QLD 4014
DWG E01
3.000
cables, LP6 and LP8 cables to new location. Provide
new conduits and cabling to LP5 and LP7 ELECTRICAL PIT
T (07) 3265 4315
1X 50MM HD ELECTRICAL CONDUIT. W www.m2electrical.com.au
0.500
1.500 Lic: 84667
50.000
1X 50MM HD ELECTRICAL CONDUIT.
LP6 - EX CCT
3.000
Relocate existing 16sqMM 2 phase feeds from timber light
poles into the new galvanised light poles. Place the pole in
Client
ELECTRICAL PIT
location the avoid electrical joins. Refer to Empyrean
lighting design version 9 for detailed design
LP5 - CCT3
Provide new 2 phase 10sqmm SDI
Project Name
R9
cables from TDB2 to light pole.
Refer to Empyrean lighting design
.00
0 version 9 for detailed design NOOSA DISTRICT
.00
0
R9
SPORTS COMPLEX
50.000
1.500
3.500
6.000 LP2 - EX CCT
Relocate existing 16sqMM 2 phase feeds from 1X 50MM HD ELECTRICAL CONDUIT.
0.500 timber light poles into the new galvanised light
3.500 poles. Place the pole in location the avoid
- 3.500 electrical joins. Refer to Empyrean lighting
2.100 design version 9 for detailed design
Title
R5
6.000
ELECTRICAL SERVICES
.00
NOOSA COUNCIL LP1 - CCT1
0
0 0 Provide new 2 phase 10sqmm SDI
5.0
R cables from TDB1 to light pole.
Refer to Empyrean lighting design SITE PLAN
4.000
APPROVED PLAN
version 9 for detailed design
3.000
R150.000
CROSSING FACILITY
MCU20/0020 4 JUN 2020
Discipline Status
4.000
As annotated by Council
R1
3.000
SPEED CONTROL DEVICE
ELECTRICAL SERVICES PRELIMINARY
2.5
00
6.000
Designed By Checked By Approved By
MG MG MG
Project No. Drawn By Scale at A1
3.000
- CH NTS
00 Drawing No. Revision
2.5
R1
E00 01
Document Set ID: 21143014
21102680
Version: 1, Version Date: 09/06/2020
16/03/2020
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 2 pages
Page 2
R30.0
6.000
-
NOOSA COUNCIL
00
APPROVED PLAN Locate existing 100mm conduit
MCU20/0020 4 JUN 2020 and extend to pit located at
LP12. Remove pit in this area
As annotated by Council and re-use if in good condition
0.500
Underground conduit to connect
4.000
8.000
into the existing electrical pit if
located outside of 5M run off
APPROVAL RELATES TO INSTALLATION
OF 4 X 20 METRE HIGH LIGHT TOWERS
1X 50MM HD ELECTRICAL CONDUIT. ON FIELD 5 ONLY
ELECTRICAL PIT
LP12 - EX CCT
Install new 35mm XLPE cables and 6 core 240v control
cable into new light pole base. Multi-core cables to control
lights at 50% and 100% light output.. Refer to Empyrean
lighting design version 9 for detailed
1X 50MM HD ELECTRICAL CONDUIT.
LP11 - EX CCT
Terminate already installed cables into new light pole
base. Use existing multicore cables to control lights at
50% and 100% light output.. Refer to Empyrean
lighting design version 9 for detailed design
0
100.00
5.000
6.000
5.400
5.400
68.000
3.000
SERVICE ROAD
5.000
1.500 3.000
5.000 01 11.02.20 PRELIMINARY DESIGN CH MG
00 09.01.20 PRELIMINARY CH MG
Rev Date Description By Chk
The concepts and information contained in this document are the copyright of M2 Electrical
Pty Ltd. Use or copying of the document in whole or in part without the written permission of
LP10 - EX CCT 1X 50MM HD ELECTRICAL CONDUIT. M2 Electrical Pty Ltd constitutes an infringement of copyright.
Do not scale drawings. If in doubt, ask!
Install new 35mm XLPE cables and 6 core 240v control
cable into new light pole base. Multi-core cables to control
lights at 50% and 100% light output.. Refer to Empyrean
lighting design version 9 for detailed
6/94 Delta Street, Geebung QLD 4034
R50.000 PO Box 105, Virginia BC QLD 4014
T (07) 3265 4315
W www.m2electrical.com.au
Lic: 84667
LP9 - EX CCT
Client
Terminate already installed cables into new light pole
base. Use existing multicore cables to control lights at Project Name
50% and 100% light output.. Refer to Empyrean NOOSA DISTRICT
lighting design version 9 for detailed design SPORTS COMPLEX
Title
ELECTRICAL SERVICES
8.000
FIELD 5
5.000
Discipline Status
ELECTRICAL SERVICES PRELIMINARY
Designed By Checked By Approved By
R50.000 6.000 MG MG MG
7.000 Project No.
-
Drawn By
CH
Scale at A1
1:250
0.500 RUGBY LEAGUE FIELDS Drawing No. Revision
3.000 E03 01
Document Set ID: 21143014
21102680
70.000
Version: 1, Version Date: 09/06/2020
16/03/2020
Page 3
MCU20/0020 4 JUN 2020
APPROVED PLAN