Council archive · source document
Part 7 of 37 Appendix 5 - Water and Sewer Infrastructure Report MCU12/0208
Very large file (29.5 MB): the whole original can take several minutes to open, especially on a phone. Text is quick to read.
([D)MWH. Noosa on Weyba Water Network Performance Assessment
5 Conclusions
The ’Unitywater Planning Model -
Water’ water network model has been used to assess the potential
impact of the Noosa on Weyba development in the existing DMA inregard to pressure standards at
maximum hour and under fire flwo conditons. The demand from Noosa on Weyba has been applied
based on the following criteria:
Base model set to the Ultimate planning horizon
494 Residential Lots
339 Mixed Use Residential Lots
. 600 m2 of Retail Space
. Total EP = 2416
Maximum Hour demand = 31 LIs
Fire Flow demand = 51 LIs
The assessment of the water supply network under fire flow and maximum hour demands identified the
following:
Under maximum hour demand conditions Unitywater standards of service were met at the
proposed development site and within Noosa Industrial DMA for the three supply options during
the 2038 planning horizon. No augmentation of the existing network is required.
Under fire flow demand conditions Unitywater standards of service were met at the proposed
development site and within Noosa Industrial DMA for the three supply options during the 2038
planning horizon. No augmentation of the existing network is required.
Storage assessment of the Tewantin Reservoir with inclusion of the Noosa on Weyba development was
undertaken. The storage assessment identified the inclusion of the Noosa on Weyba development
brings forward storage deficiency of the Tewantin Reservoir to 2016 when assessed against the DSS
contained in this report. A total storage deficiency of the Tewantin Reservoir of 1.64 ML was identified at
the 2031 plannnig horizon.
Status: Draft 22/06/2012
Project number: Page 9 Our ref: Noosa on Weyba WS Assessment.docx
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Part 7 of 37 Appendix 5 - Water and Sewer Infrastructure Report MCU12/0208Related documentApplication case desk ↗
About this file
- File size
- 29.5 MB (very large file)
- File type
No other editions are linked here.