Hydraulic Modelling Fee Request                    2                                      ~,.., Cardno      Shaping the Future
UnityWater




Water Supply Demand and Sewage Flow Projections


An adopted design criteria based on the 2012 South East Queensland (SEQ) Planning Guidelines was
adopted for this development. Utilising the adopted peaking factors, detailed in Table 2, the water supply
demands were calculated for the proposed development. Table 3 details the projected water supply
demands.


Table 2 SEQ Planning Guidelines Design Criteria


                                                                              Additional Flow
                             Base Flow Unit         Peaking Factors
                                                                                requirements




  .
     Water Supply

     -
                          -,-AD = 280LlEP/d            4 x PH:AD
                                                                                   ..

                                                                                   -
                                                                                  ...   .
                                                                                           ..




AD   Average Day
     -




PH   -
         Peak Hour


Table 3 Water Supply Demands for the Proposed Development




Options

The service development, the three options have been developed.


     >      Option 1: This option involves the delivery of the full supply to the development from a connection to
            the existing trunk mains along Eenie Creek Road to the boundary of the site via a proposed 300mm
            trunk main.
     >      Option 2: This option involves splitting the site and utilising two connection locations. One
            connection delivering supply to the development would be via a connection to the existing trunk
            mains along Eenie Creek Road to the boundary of the site via a proposed 300mm trunk main. A
            second connection (200mm)to the existing mains along Lake Entrance Boulevard is also proposed
            to service the western lots. The supply sources would not be linked internally.
     >      Option 2: This option utilising two connection locations. One connection would be via a connection
            to the existing trunk mains along Eenie Creek Road to the boundary of the site via a proposed
            300mm trunk main with a 200mm connection to the existing mains along Lake Entrance Boulevard.
            The supply sources would be linked internally.




Scope Of Work

Cardno require the analysis of the Noosa water supply network to confirm the capacity of the network. As a
minimum Cardno would require the available pressures at the proposed connection locations for both a
maximum day and fire fighting scenarios for each option.




7501-19                                                                                       www.cardno.com

Used in these records

About this file

File size
29.5 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Part 7 of 37 Appendix 5 - Water and Sewer Infrastructure Report MCU12_0208.pdf · 29.5 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.