Unearthed Geotechnical P/L ABN 78 808 074 271 Site Investigation Report O20-212 Lot 4 RP905954. #26 Little Springs Lane Lake Macdonald Noosa Council September 2020 For all geotechnical requirements Unearthed Geotechnical P/L mobile 0417 132 300 PO Box 1204 [email protected] Gympie Q 4570
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalSearchable page text hides email addresses. Original files are unchanged and may show email addresses.
Full text of the other 9 pages
Page 2
INTRODUCTION Unearthed Geotechnical P/L was commissioned to undertake a Site Investigation in the Noosa Council at Lot 4 on RP905954 (26) Little Springs Lane, Lake Macdonald. (GPS coordinates 26°21°54"s, 152°55’58"e), for the proposed house and shed on this vacant 7132 square-metre allotment. Our site investigation fieldwork was performed on 2/09/2020 after generally fine weather in the course of the preceding weeks. This report does not include an assessment of slope stability or landslide risk. The standards and references used in compiling or referred to in this report are, The Queensland Building & Construction Commission, AS 1289-2014 Methods of testing soils for engineering purposes, AS 2870-2011 Residential Slabs and Footings, AS 3798-2007 Guidelines earthworks commercial & residential developments, AS 1726-2017 Geotechnical Site Investigations. COPYRIGHT ™: Copyright in the whole and every part of the drawings, specifications and other documents provided by Unearthed Geotechnical P/L remain the property of the Unearthed Geotechnical P/L. Upon receipt of full payment for our service the client is licensed to use the drawings, specifications and other documents for the work/s for which they were commissioned. They shall not be used for any other work except by agreement with Unearthed Geotechnical P/L. Unearthed Geotechnical P/L. 4 Site Investigation Report 020-212
Page 3
SITE INVESTIGATION As with all site investigations we assume that the fundamental principles of good construction will not be overlooked, and will be carried out with the consistent application of ‘best practice’ techniques across the site and at each stage as these factors are of great consequence. The fieldwork undertaken for our site investigation included the following; detailed subsoil investigation recording characteristics and limitations, a comprehensive site assessment to record topography, geography and geology, soil observation boreholes (75-100 mm dia. Jarret style hand augers), penetrometer testing with 9kg Dynamic Cone Penetrometer (DCP), classification and testing of hand collected soil samples, and the collation and evaluation of the results from the above studies. Be Be Ge He Ge (The test locations were not professionally surveyed and should be considered approximate) (All fieldwork performed in accordance with the relevant Australian Standards and Codes) (All boreholes backfilled in accordance with Occupational Health and Safety regulations) FIELD TEST LIMITATIONS The soil profiles reported should generally be representative of the soil conditions across this site. In some cases soil conditions can change dramatically, and can change over short distances. If site works reveal soil conditions that are different from those shown in the attached data, the evaluator must be informed immediately as changes may be necessary. CLIENT SUPPLIED INFORMATION This site investigation and classification has been undertaken in accordance with AS 2870 ‘Residential Slabs and Footings’. The Queensland Building & Construction Commission's (QBCC) ‘Rectification of Building Work Policy' has a requirement for the following information to be supplied to us, and that we consider this information in determining the site classification. This information includes, but is not limited to; Property description and site address, Evidence to ensure site is correct (e.g. Survey Plan, Registered Plan, etc), Survey plan delineating contours, trees, existing developments, etc, Land searches, including such information as flood lines, easements, covenants, underground services and infrastructure, etc, Any previous geotechnical work, e.g. original contour survey, and the limits of prior subdivisional or developmental cutting and filling, service lines etc. & The known extent of further developmental or construction earthworks Be Se He He 9 In this instance and at the time of our commission, we have considered the information supplied to us by the client. Should the client or his agent have omitted to supply us with the QBCC required information or supplied us with incorrect information our assessment may be irrelevant and/or inappropriate. However, should this information become available we would be pleased to amend our report accordingly, if, and as necessary. We do not take responsibility for the consequences in such cases and may incur additional costs if as a result; more testing or re-writing is necessary. Unearthed Geotechnical P/L. 2 Site Investigation Report 020-212
Page 4
FINDINGS All the field information and test results collected during our site investigation and detailed in this report, including any site plans, log and data sheets together form the basis of our recommendations. The soil profile encountered during our investigations, and as reported, was reasonably and acceptably consistent across the proposed development, and within our expectations from regional experience and correlation with The Qld Dept of Mines/Energy Geology Sheet 9445/1999 (Gympie), which describes the geology as Late Triassic-Jurassic, Duckinwilla Group, Myrtle Creek Sandstone. The proposed site is on a partially exposed 15-20% southeastern slope with neighbouring vegetation consisting of grasses and trees. We recorded approximately 15 medium to large trees within, or adjacent to, the proposed site, that are likely to be removed. The landform was recorded as natural and partially disturbed. Slope configuration across the proposed site is determined to be linear planar. Slope stability problems were not evident during our investigations. The susceptibility to flooding from groundwater is low and site drainage was recorded as poor. No water table was encountered on the day of our site investigation. However, during and for some time after periods of seasonal, heavy or extended rainfall water seepage on the sand/clay interface may cause a loss of bearing capacity at this level. Seepage may also cause collapse of excavations, which may increase concrete volumes significantly above those normally anticipated. Cobbles and/or boulders in soil profiles are sometimes common and unfortunately we cannot predict their size or frequency. It has also been our experience that these floaters can be extremely difficult to excavate with conventional equipment. However, experience in this area has shown that beneath any floaters the soil grades into stable weathered rock at relatively shallow depths. The resistance of the soil encountered was tested with an approved 9kg Dynamic Cone Penetrometer and the results recorded at the appropriate levels on the attached log sections. Existing Services. We were not informed of any existing service line excavations and no existing service line excavations were identified within or immediately adjacent to the proposed house site. Unearthed Geotechnical P/L. 3 Site Investigation Report 020-212
Page 5
The soil samples hand collected and classified from the proposed house site were assessed as having low to negligible plasticity, therefore laboratory testing was considered unnecessary. The expected surface movement (Ys), due to seasonal moisture changes in the soil encountered, is as follows Ys Value = 0-20mm Predicted Surface Movement Class Ys=>20-—< 40mm M Ys=>40-< 60 mm Hl Ys=>60—-< 75 mm H2 Ys=>75 mm E Problem sites P Note: Our assessment does not consider the effect of the presence of trees within or adjacent to the building site, nor the removal of trees prior to or after construction, nor the growth of trees too close to the footings. The proximity of trees and their effect on joundations should be considered when determining specific engineering assessments, and for foundation/footing design. Appendix B of AS 2870-2011 indicates that to reduce, but not eliminate, the possibility of damage to the footings, trees should be restricted to the following distance from the building (where rows or groups of trees are present the distance nominated below must be increased, and similarly the Ys Value listed above may need to be increased) : 75% of the mature tree height, for class “M” sites, 100% of the mature tree height, for class “H 1” sites, and 150% of the mature tree height, for class “E” sites. Note: This classification above has been derived from test work performed on the soil profile encountered on the day of our fieldwork. Any further filling of the site or excavation into the soil profile, may result in a different classification. Temporary Excavations. Where temporary excavations are performed for footing or services up to 600mm deep, natural soils may have minor or no stability problems, however deeper excavations have a possibility of collapse more readily and shoring of vertical excavation may be required. Where an existing excavation has been filled with uncontrolled fill, all locations above a line 30 degrees for sands and 45 degrees for clays above the horizontal may be unstable and may not support any structure — see attached critical depth line diagram. Unearthed Geotechnical P/L. 4 Site Investigation Report 020-212
Page 6
LEGEND
Investigation Code
GP — Poorly graded gravels, little or no fines
GC — Clayey gravels
SP — Poorly graded sands, little or no fines
SC — Clayey sands
OL - Organic silts and organic silty clays
CI - Inorganic clays of medium plasticity
CH - Inorganic clays of high plasticity OH - Organic clays medium/high plasticity
Pt — Peat and other highly organic material Ls — Linear Shrinkage %
Note The stratifications identified on our log sheets are representative of the approximate boundary
between soil types and the transition may be gradual and vary over the site.
Soil descripti 1 the Geotechni
GW — Well graded gravels, little or no fines
GM - Silty gravels
SW — Well graded sands, little or no fines
SM - Silty sands
ML - Inorganic silts and very fine sands
CL ~ Inorganic clays of low plasticity
ion:
Dk - Dark, Lt— Light, Gy- Grey, Rd- Red, Br—Brown, Or-— Orange, Mott - Mottled.
LP, MP, HP - Low, Medium, High Plasticity. SW - Slightly Weathered Rock.
P (p) — blows/100 mm approved penetrometer DW - Distinctly Weathered Rock.
UTP — Unable to penetrate EW - Extremely Weathered Rock.
aring cap: Is
Soft (S) — 25 to 50 kPa
Very Stiff (VSt) — 200 to 400 kPa
Firm (F) — 50 to 100 kPa
Hard (H) — 400+ kPa
Very soft (Vs) —<25 kPa
Stiff (St)— 100 to 200 kPa
SPT “N” value Relative Density (%)
Density
Very Loose (VL)
Loose (L)
Medium Dense (MD)
Dense (D)
Very Dense (VD)
Boulder
Cobble
Gravel
Sand
Clay
Looks and feels dry, c!
Moist
Wet
soils are normally hard,
Feel cool, darkened in colour, no free water on hands when remoulding.
Soils are weak, free water can occur; granular soils bind together, clay softened.
<4
4-10
10 ~30
30-50
> 50
Coarse
Medium
Fine
Coarse
Medium
Fine
or friable.
<15
15-35
35-65
65-85
> 85
> 200
63 — 200
20 - 63
2-20
0.6 —2.0
0.2—0.6
0.075 — 0.2
0.002 — 0.075
< 0.002
Unearthed Geotechnical P/L.
5 Site Investigation Report 020-212
Page 7
Ground/pad level This footing Is founded above the critical depth unstable line and is deemed to be unstable. +O ey, stable eu, Pliers must be excavated to below the critical depth line to provide stability to “7 > these footings. This footing is founded below critical line and Is stable 30 degrees oN, (45 for clay) ~ Horizontal Any proposed or existing excavation. The builder must ensure all excavations are discovered and the footing and slab Is secured below the critical line accordingly. This should Include a search of all council & other records for as constructed plans to establish excavation depths & widths. “ Critical Depth line measured from deepest, point of the excavation nearest the footing. Critical Depth Line ~ In the case of a buried pipe the invert level is usually above and away from the nearest comer of the excavation. Unearthed Geotechnical P/L. Site Investigation Report 020-212
Page 8
Lot 4 (#26) LITTLE SPRINGS LANE, LAKE MACDONALD.
020-212
EB
mely Weathered Rock Lenses) |__| 800
Silty Sand SP_ 1 [| 100 { 1
yBrown) _—«—s'‘|-« 3-:«[ 200 | 4 -
J _ Moist & Medium Dense___| _4 [300 | 5
_. Clayey Sand SC confer Sf 400 | 7 |
(Orange Brown Grey Mottled) 10 | 500 9
_... Moist & Dense | 12, | 600 | 11 |
Silty Sand SP
(Grey Brown) _
___Clayey Sand SC _
"(Orange Brown Grey Mottled)
900
UTP Hand Auger _ | Im
__ (Extremely Weathered Rock EW) {1100
1200
75-100 mm Jarret style Hand Auge
2/09/2020
100
200
300
400
500
600
700
800
“Moist & Friable_
900
_UTP Hand Auger
im
1100
1200
75-100 mm Jarret style Hand Augers.
Pp = blows/100mm - 9kg Dynamic Cone Penetrometer.
UTP = Unable to penetrate.
Note - All field information and test results collected during our site investigation and detailed in the
accompanying report, including any site plans, log and data sheets are only to be used for the purposes of this
report. No third party use of any part of this information is authorised without specific or written consent.
Page 9
BH2 BOREHOLE LOCATION AND NUMBER 20m é LOCATION AND ASPECT OF PHOTO 1:1000(@a4) a Owner/ClienvAgent - ANTHONY MCDONOUGH 0407 493 611 LOT 4 RP905954 (#26) LITTLE SPRINGS LANE, LAKE MACDONALD. Noosa Council. 020-212. Do not scale. Site Drainage - Poor. Vegetation - Grasses & Trees. Slope - 15-20% Vertical:Horizontal \.AJ TRELOAR (Copyright) Unearthed Geotechnical P/l.. PO Box 1204 Gympie 4570 [email protected] 0417 132 300 2i09/2020 _)