Attachment 1 - Noise Report ANV
Attached to the e-mail Response to Submissions, Accoustic Report, Amended Proposal Plans, Ext to Decision Period - MCU17/0073.
Thus the noise criteria for staff and student noise radiating from the building do not apply when it is used for
educational purposes.
The Environmental Protection (Noise) Policy sets acoustic quality objectives for residential and other uses.
The external acoustic objective for a dwelling is 50dB(A) for day and evening periods. These can be used to
set upper limits for plant noise criteria developed using the Environmental Protection Act.
The church air conditioning plant is only expected to operate during the day and evening periods. Given the
plant may be used on weekdays and weekends, the noise assessment is based on the criteria that apply
during this period.
Using the measured rating background levels, the project criteria are presented in Table 2.
Table 2 Plant Noise Criteria dB(A)
Day Evening
Criteria Source
7am – 6pm 6pm – 10pm
DEHP EP Act & EPP Noise 48 43
Noise criteria for people on the Friendship Terrace can be assessed using the EPAct Section 440W approach.
Given the noise is not continuously present the levels should also be compared against the existing ambient
levels. Proposed criteria are presented in Table 3.
Table 3 Friendship Terrace Noise Criteria dB(A)
Day Evening
Criteria Source
7am – 6pm 6pm – 10pm
DEHP EP Act & EPP Noise 48 43
Existing Ambient Leq 53 45
NOISE ASSESSMENT
The proposed church alterations include the following:
worship centre;
offices and amenities;
covered friendship terrace; and
meeting room and amenities (lower level).
The floor plans for the church alterations are shown in Figures 3 and 4.
Acoustics Noise Vibration 5 0145 GSL Church Alterations Rpt 02