‘  *    so,   a Jos
            x      ;               ;                         If telephoning or calling please ask for:
        MIN Go¥                                                tne
           ee         i                                       Tracy Arthur (07) 5449 5228
        a         ‘COUNCIL ,                                   Email: [email protected]
            e                                                Your Ref:
                                                                                      >       +    KS
     |                         |                                                 (3        RECEIVED       a
.                                             ’                                                   Cc
                27 June 2007                                                               q   iy   2?
                      "                                                                   {eo                   .
                                                                                   a)      |     ae COUNCIL ©
                                                                                          NOOSA 5 USE
                Robert G Utz & Stephen J Clague                                       0       Ww
                CARE Kidd & Co Designers                                                /           4
 |              PO Box 262                                                               Cu        Ww
                NOOSA HEADS       QLD 4567

            |   Dear Sirs,
                Re:  Application for Operational Works for 18 Weyba Street, Sunshine Beach
                | refer to the above-mentioned application for Operational Works, which was lodged
                with Council on 24 May 2006.  —
                Council received correspondence dated 20 July 2006 indicating that the other
                information requested as part of Council's Information Request dated 21 June 2006,      _
                was to be forwarded upon receipt of the Decision Notice for the Material Change of —        at
                Use approval (06/0138). This Decision Notice was issued on 14 July 2006, andtodate        i;
                Council has not received this outstanding information, which includes further details on’
                the design of soakage pits, existing site and soil conditions to cater for infiltration and ~~ a
                the provision of rainwater tanks.                                                  SS
                In addition, there has been no payment of bonds and coniributions in accordance with          -
                the conditions of the Material Change of Use approval and evidence that Portable Long
                Service Levy has been paid has not been provided.
                Should the above not be received by 18 July 2007, then a Preliminary Approval for the
                above application may be issued. The Preliminary Approval does not grant approval
                for the works to commence. A further application for a Development Permit, together
                with the relevant forms and fees will need to be fodged with Council for assessment.
                You are reminded that these permits, if issued, do not extend the relevant (currency)
                period for any other approval, which may lapse independent of this application.                .
  .             Should you have any queries in relation to this matter, please do not hesitate to contact
                me on the above number.

                Yours faithfully,
                 TruflQ fe                                        .                 .
                Tracy Arthur                          h                          ,
                PLANNING OFFICER                                                   f 3B3PY        cheque

                                                                                             18fn fo?
                                                                                                        te
                                                             NOOSA COUNCIL ABN OF Go& 14:12)
                                                             9 Pelican Street Tewantin PO Box 141 Tewantin Q 4365
                A c:\datawrks\temp\1 660668\document2.doc    Phone: 07 5449 5200   Fax: 07 S47 1062  1
                                                             Email: mailbon@monsa ald one au
Full text of the other 11 sections

Section 2

rg

                                                                                                             4 July 2007
    &)       )       ©                                                                              SCG Ref: 16078(L1)
    CONSULTING ENGINEERS

                               Kidd & Co Designers,
                               PO Box 262
                               Noosa Heads Q 4567

                                Dear Sirs,
                                                        Re: 18 Weyba Street, Sunshine Beach

                               We have reviewed the recent letter from Noosa Shire Council dated 27th of June 2007,
                                regarding the application for Operational Works for the above project. In short, the letter
                               states that there remains additional information required to complete the Operational Works
                               approval.
                               We have reviewed our current Operational Works documentation and in particular our
                               drawing 16078 — OW1, Revision A. This drawing shows details of the information
                                requested by Council and was issued back in September 2006. In particular stormwater
                               soakage pits and the provision of rainwater tanks for re-use. However, in reading through
                               council's decision notice, it became apparent that there was a request to ensure that
                               overflow from water tanks was to be directed to the street. We have therefore revised our
                               current drawing by relocating the water tanks towards the front of the property to enable the
                               overflow to reach the street. We have enclosed copies of the revised drawings, 16078 —
                                OW1, Revision B.
                                Furthermore Council has requested in their recent letter that details be provided for the
                               design characteristics of the soakage pits and the ability of the surrounding soils to cater for
                                infiltration of the stormwater. We can confirm that as the geotechnical engineers for the
                                project, the natural sand is capable of absorbing the proposed stormwater run-off. These
                                soil conditions were confirmed in our site investigation report 16078(S). We have also
                                included a copy of this report for your information. The pits were also designed for a Q100
                                storm event.
                               Trusting the enclosed information is adequate for your client to obtain Operational Works
                                approval. PleaSe do not hesitate to contact the undersigned should further information be
                                required
                               Yours Fait      ,

                                SEAN SHARP-RICHARDSON
                                For and on behalf of
                                SCG CONSULTING ENGINEERS
                              _ Enc.
  ese emsameanmapee nantes
.    Oreo Lae blo)
    LAC CUMS L |                                                               :                                    °
    2 emait@scg-engineers,com
    po box 1661 noosa heads g.4567
    18 duke st sunshine beach q. 4567

                                                                                   STRUCTURAL * CIVIL * GEOTECHNICAL
    DEBUILD PTY LTD TRADING AS ABM 40 098 481 899

Section 3

.  si     ¥
                               :                   —_                           ICE    COP                            |
                                  |                    -                 OFFICE           COPY
.                               |               |                          (cS 1Ro aracned                                  |

     eee                                                                                    |        31 March, 2006
                                ,                                                   SCG Reference:         16078(S)
                             _  Utz + Clague
                                C/- Kidd & Co.                                                                      .
  ,     ae                      P O Box 262                 .
                                NOOSA HEADS QLD 4567                           .                                     oe

  ’        0                    SOIL TEST & FOOTING REPORT: 18 Weyba Street, Sunshine Beach                              ,
  oe                  |         4.0  * INTRODUCTION:                                 |                       |
    !      /  .                 This company has performed a site classification in accordance with AS 2870-1996 and      .    ;
            ‘                   made recommendations based upon the classification for a building to be constructed —
a                           .   at the above site. This report does not include an assessment of Slope Stability, -
                  .             Landslide Risk, or specifications for*damp proofing, termite protection, moisture
    oe                          barriers, tie down, bracing or structural member sizing.
7         oo            -       This report relates only to the above property and proposed construction as described |
  e             “               below:                                                                           .  ‘
  -                    po           "="    Proposed Construction ©                   Residential Duplex
              SO                          ee external Walls... os             ;          Block / Timber
   .                                = intemalWalls.                    |      [Timber
                              oO   Passes... Ground Floor                               Slab on Ground
                                    he Building Platfom:.            =. |     [Cut Pad
         -                         [o.oo Blockwork Articulation         |    | _s«sRequired @        centres -    |
                           ”     This report must be read and considered as a whole. All of our recommendations,
                                 foundation sections and appendices must be read, considered and followed by all-
        .                        people involved in this project to ensure adequate long term performance of the footing
         -.               +      system and the structure it supports.  If you are unsure of any of the requirements
          BT               ,     herein, you must seek clarification from this office.     ,     .
                     |           2.0     SITE CLASSIFICATION:           |                             oe                .
 *.                  .           After considering the results of our field investigation performed on 24/3/2006 we have.
           ;                     classified this site as:                                                           .

          .    |                                              ’     ~. Class P/S

        CCL Aen                          .                     ;
  ‘     f 07 5447 2634                       ‘
        e emailascg-engineers.com                                 /
        feraRerey Mich MrT heads q.4567                                                    Se                 :
    .   Yet Cased ar ulata elaine: ae                          .                                .            ‘
                                                                                     STRUCTURAL * CIVIL «GEOTECHNICAL
.       Pls teehee Se ee se cid                                                        /             .                     .

Section 4

The classification has been calculated from test work performed on the soil profile encountered on the
            day of our fieldwork and consideration .of AS2870-1996. The ‘P’ Classification relates to the loose sands
            encountered in the upper profile of our test sites. Any disturbance of the soil profile, may result in a
            change to the classification. The attached design, has allowed for the influence of the earthworks
            described in section 5.0 below.

            3.0     SITE DESCRIPTION:
;           The construction area has a gradient in the order of 4%.
            Vegetation on the construction area (and nearby surrounds) consists of grasses and scattered trees.
            The existing surface drainage is fair and sub-surface drainage is good.

            4.0     FINDINGS:
            The soil profiles encountered are shown on the attached log sections.
            No water table was encountered during our testing program.
            The sandy soils encountered are susceptible to collapse when unconfined. This may effect excavations
            and result in additional earthworks and increased concrete volumes. For further information please refer
            to the attached critical line diagram.
            The samples classified on site were assessed as having low to negligible plasticity, therefore laboratory
            testing was considered unnecessary.
            We have assessed the expected differential movement of the soil profiles encountered to be the
            equivalent of a site with a Ys of less than 20mm.
            For buildings within the scope of AS 2870-1996, safe bearing is available at 300mm into the MEDIUM
            DENSE SAND. This strata is shown shaded on the attached logs

      ‘     5.0     SITE PREPARATION DETAILS:
            We recommend scraping this site free of all organic material and debris, then cutting the construction
            area to form a level pad. There must be no fill placed beneath the foot-print of the building. The
         ’  prepared construction pad must be entirely on cut natural ground. A small surface spoon drain with a
            suitable outflow should be excavated at the base of the cut. Any fill placed outside the foot-print should be
            clean material from the cut, laid out in 150mm (maximum) layers and tracked rolled with the excavator
            (six passes in each direction). Cut batters of 1 to 2 (vertical to horizontal) and fill batters of 1 to 3 will be
            stable providing ail fill is compacted as above and exposed banks are protected against erosion.
            Where a retaining wall is required, a cut batter of 1 to 2 (vertical to horizontal) in the sand profile taken
            from the base of the proposed walt should be excavated. These earthworks must incorporate shallow
            surface spoon drains at the base and along the high side of the cut. Drains must have an efficient outflow
            down-slope and clear of the construction area. The exposed face should also be protected against the
             potential for stormwater erosion. Should these recommendations be un-achievable the builder should       -
            seek guidance from this office on temporary shoring, benching or other suitable techniques.
            Areas where existing structures or trees are removed shail be backfilled with engineer approved fill
             materia! compacted in accordance with AS2870-1996, or alternative measures to be provided by the
             engineer.

Section 5

. ‘a     ff                                                          .

              Any loose or soft material uncovered in the site preparation shall be removed and replaced with approved
              fill material compacted in accordance with AS2870-1996, or alternative measures to be provided by the
              engineer.
              Site drainage during construction is important. Stormwater run-off should be diverted away from any
              foundation excavations and not be able to pond within 5.0m of the building footprint. Temporary spoon
              drains or other practical methods should be used.
              We recommend using a footing system as per the attached plans and details on the prepared
              construction pad.
              Where site drainage and landscaping does not conform to the specifications of AS 2870-1996 and CSIRO
              information Service Sheet BTF 18 (2003) significant damage to the building can be expected. A single
              copy of this document is issued with the original issue of this report. Please consult your builder or
              contact this office to obtain a copy.

              6.0    FOOTING AND SLAB SPECIFICATIONS:
              Footing Details:                                                                        .
             Alt footings must be founded a minimum of 300mm into MEDIUM DENSE SAND (shaded on the attached
              log sections). Dimensions and reinforcement requirements are detailed in the following footing plan and
              cross-sections.
              Where the founding tevel is deep or is covered by the introduction of fill the footings are to be increased in
              depth to reach the level. Alternatively the footings can be supported on backhoe dug or drilled piers
              founded at or below the founding level. Refer to this office for details.
              Drilled Piers Supporting the Footings:                               ,
              Where the MEDIUM DENSE SAND is deep or to be covered by fill the footings can be supported on
              350mm diameter drilted piers founded at a minimum of 300mm into the MEDIUM DENSE SAND.
             Aiternatively the footings can be founded on steel screw piers. The piers are to be designed and installed
              by a specialist contractor to achieve the loads nominated on the structural plans.
              Drilled Piers Supporting the Slab:
      .       Slab piers are required where there is more than 300mm of uncontrolled fill beneath the slab. They are to
              be founded at a minimum of 300mm into the MEDIUM DENSE SAND. Special attention must be paid to
              the extra thickening and reinforcement required over each pier as detailed in the attached plan and
             details.                                                               ;
              Where drilled piers supporting columns or posts are not poured with the slab they must be connected to
              the slab in the following manner:
              «  4x N12 bars must be anchored 500mm into the drilled pier and be bent 300mm horizontally into the
                 footing or slab as required.
              ¢  Where a column penetrates a beam or footing 3x N12 bars must be bent around the column to lap the
                 trench mesh by 500mm both sides.

              SCG CONSULTING ENGINEERS                           3                                   SCG Ref: 16078(S)

Section 6

Driited Pier Reinforcement:
                             Pier Depth mm                           Slab Piers
                               up to 1500
                               1500-2500          2xN12bars
                               2500-4000          4xN12bars          2xN12bars
                               4000-6000          6xN12 bars         4xN12bars

     Floor Slab Details:
.    We recommend reinforcing the floor slab as shown with SL82 slab fabric and the thickenings as
     specified.
     Where the foundation level of these thickenings is below prepared pad level, it may be advantageous to
     excavate them at the same time as the perimeter footing.
     Where the beams intersect the perimeter footing, their base must be graded down to the footing base
     level, 3 x N12 bars must be cogged into the footing, and lapped 500 with the beams trench mesh. Refer
     to the attached details.
     A levelling layer under the floor slab is to comprise of granular material compacted in 150mm layers.
     Either well graded sand or crusher dust can be used.
     An approved polyethylene damp proof membrane of 0.2mm (min.) thickness is to be placed over the
     levelling layer. Laps are to be a minimum of 200mm and be taped. All service penetrations and punctures
     are to be fully taped. The membrane is to be extended down the inside face of the perimeter footings.
     Where rock is encountered within the slab area and encroaches within the slab depth it should be
     excavated to a level which enables placement of a 100mm (min.) layer of granular material under the
     slab.
     Notes:
     All building dimensions are to be obtained from the approved pians. The builder must ensure that the final
     pier placement meets all the requirements of this report (both written specifications and cross-sections).
     All excavations must be totally free of all loose material and debris before pouring. They must be cleaned
     out so that the concrete is poured onto undisturbed ground. Tamping and/or watering loose material is
     not acceptable.
     We strongly recommend footing excavations be inspected by a qualified person with appropriate
     experience to confirm the founding material and level is as nominated herein.
      Similarly all preparations should be inspected prior to the pouring of concrete by a qualified
      person with appropriate experience to confirm that the workmanship and construction conforms
      with the details and recommendations contained herein.
      Tiled Areas:
      In areas where ceramic floor tiles or brittle coverings alike are required we recommend increasing the
      size of the slab mesh by one grade. Use flexible adhesives when affixing tiles and delay the laying for as
      long as possible (at least 3 months, preferably 6 months) after the slab is poured.

      $CG CONSULTING ENGINEERS                         4                                  SCG Ref: 16078(S)

Section 7

Reinforcement:
                Reinforcement is to comply with the following :
                a) Concrete cover around the reinforcement must be 40mm to unprotected ground, 40mm to external
                exposure, 30mm to the membrane in contact with the ground, and 20mm to the internal surface. The
                slab fabric shall be placed towards the top of the slab within the zone defined by these limits.   We
                recommend 30mm top cover.
                b) Slab fabric must be lapped by one full panel of fabric so that the two outermost transverse wires of one
-               sheet overlap two outermost transverse wires of the sheet being lapped. Slab fabric is to be supported on
                 bar chairs placed at 800mm ctrs.                       -
                 ¢) Trench mesh must have ail cross wires cut flush with the outer main wires. Trench mesh in slab and
                 edge beams must be overlapped by the width of the fabric at “T” & “L” intersections. Trench mesh must
                 be spliced, where necessary, by a !ap of 500mm.
                 d) Pre-Fabricated footing cages or reinforcing bars at “T” & “L” intersections are to have a Y12 comer
                 lapping bar top and bottom and lapped 500mm with adjacent bars.
                 e) The minimum fap length of reinforcing bar is to be 500mm or 25 bar diameters, whichever greater.
                 7.0    ARTICULATION REQUIREMENTS:
                 The specifications in this report have been specifically formulated for articulated masonry construction.
                 This usually results tower construction costs. All masonry walis must have full height articulation at a
                 maximum spacing of 8 meters. The articulation joint must separate the masonry from footing to eaves
                 fevel at this spacing. Masonry must be supported on each side of the joint in an approved manner to
                 retain its structural integrity. :                                                       ;
                 Where used, internal masonry walis should be articulated in accordance with the masonry manufacturers
                requirements for the width and type of unit used. In no instance should the spacing exceed 4.0m and
                 articulation should always be provided at an abutment with an external wall.
                 If articulation of masonry is found to be unacceptable, the footing system will require re-designing.
                 in addition to joints in masonry, articulation is achieved wherever a 40mm (min) separation in masonry
                 from footings to eaves is achieved. For example, where timber panels are used above and / or below
                 doors and windows.
               _ Where it is necessary to construct construction joints to meet the articulation requirements, they can be
                  placed in places of limited visibility. For example behind downpipes. Internal masonry walls should be
                  articulated where they abut the perimeter walls.
                  The designer of the building must also ensure that articulation is established:           .
                  1,     Adjacent to a change in floor level which exceeds 400 mm.
                 2.      if any proposed extension abuts any existing structure, full height articulation must be established
                         where the new masonry joins the old.
                 3.      Where a masonry wall transgresses from one footing type to another - e.g. from a perimeter
                         footing to a continuous footing.
                  If the building has any masonry arches we must be contacted for further advice.
                  Methods of articulation are well documented in “Technical Note 61” by the Cement & Concrete
                  Association.

                  $CG CONSULTING ENGINEERS                          5                                  SCG Ref: 16078(S)

Section 8

:              8.0     LIMITATIONS: |
               Field Testing Limitations       The soil profiles reported in our Log Section should be representative of
               the soil conditions over this site. In some cases soil conditions may change dramatically over short
               distances, therefore exploration programs may not locate all variations. If site excavations reveal soil
               conditions that are different from those shown in the attached log sections we must be immediately
                notified. Changes to the site classification and/or footing design may be necessary.
                Previous Excavations The recommendations contained in this report have not taken into consideration
               the long term effects of any previous, current or potential subsurface excavation mining or potential slope
                instability problems. {f a slope stability assessment is required for this allotment we can arrange for this to
                be done, but that type of report is beyond the scope of our commission and fees in this report.
                Client Supplied Information In writing this report we have considered all the information supplied to us
                by the client. Should the client or his agent have omitted to supply us with relevant information our report
                may be irrelevant and / or inappropriate. We do not take responsibility for the consequences in such
                cases and we will make an additional charge if as a result, more testing or re-writing of the report is
                necessaly.
                General Recommendations for Builders/Owners:          :
                Underground Services      —__ Where structures are built over uncontrolled fill, services will need to be
                supported so that settlement of this fill does not cause them damage or cause incorrect alignment.
                ‘Plumbing       Arrange plumbing fixtures so that the slab and beam penetrations are kept to a minimum
                and where necessary sleeved to allow for movement with 40mm thick closed cell polythene or similar
                material. Where the penetration is within 150mm of the base of a beam or footing, the depth of this
                footing element should be deepened by approximately twice the diameter of the penetration. All plumbing
                and drainage must comply with the requirements of the Nationa! Plumbing and Drainage Cade.
                Drainage        The ground surrounding the building site must be graded and drained so that water is
                shed away from the house area in all directions. Particular attention should be given to ail drainage and
                plumbing trenches so that they do not introduce water to the foundation soil, and destabilise the footings.
                Correct drainage is an essential part of our recommendations and design.     If the site is not prepared
                correctly, excessive soit moisture may accumulate in some areas, which may lead to wall and/or floor
                 movements. Roof water should be diverted away for the building as soon as the roof is installed. Where
                 building delays occur, temporary downpipes may be necessary.
                 Bracing for Wind Forces        Untess noted, we do not detail slab thickenings or pad footings to
     .           conform to wind bracing. Where a bracing wall is to be bolted to a slab, 40mm bottom concrete cover
                 attained for a radius of 150mm is required around the bolts unless noted by other consultants.
                 inspections:
                 We require 24 hours notice if you require engineers site inspections. Inspections can be booked between
                 8.30am and 4.30pm Monday to Friday by telephoning 07 5447 5544.
                 Site Classification: The site classification is calculated in accordance with the “AS2870-1996 Residential
                 slabs and footings-Construction” and relates to the estimation of Ys, “The characteristic surface
                 movement” within reactive soil profiles. The limits used for this classification are as follows;
                                           Predicted Surface Movement
                                        (Ys=<s2omm SSs*~—C~d SS SSSigt
                                         PYs=>20-40mm TM                           Moderate
                                         r¥s=>40-7omm SSC TH                     CHigh
                                          Problem sites                     P      Problem

                  $CG CONSULTING ENGINEERS                          6                                   SCG Ref: 16078(S)

Section 9

a          ‘Foundation Maintenance and Owners Responsibilities
               Trees and dense shrubs must be kept well away from the building. In alt types of soil conditions, if an
                automatic watering system irrigates within 2.5 meters of a footing, instability problems may occur. Water
               should not be allowed to pond on the ground near the building.
               Definitions:
                Controlled Fill - Man placed soil which has sufficient bearing to support a structure according to AS
                2870-1996. Fill certified at Level 1 according to AS 3798 is controiled fill.          ..
  ;             Partially Controlled - Man placed soil which appears to have been compacted under controlled
                conditions, but as the time of preparing this report, no compaction certificate suitable for compliance to
               -Level 1 of AS 3798-1996 had been presented.     CO
               ‘Uncontrolled Fill — Man placed soil (overlying the natural soils) which is not adequate to support a
               ‘normally loaded footing or floor slab.
      oO       ‘Unexcavatable Rock — Strong material including shaley material and strongly cemented sand or gravel
                that does not soften in water or collapse under the combination of loading and wetting.  Material that
  .             cannot readily be excavated by a backhoe may be taken to be rock.
                Excavatable Rock — A rock-like material which does not shrink or sweil with changes in soil moisture, but
                is readily excavatable with a conventional backhoe.    .     -
                Load Bearing Wall - in our design work a load bearing wall is defined as any wall imposing on the
  .             footing a service load greater than 10kN/m. A load bearing wall will normally be supported by a slab
           ,    thickening or footing in our slab designs.
                Natural (Strata) — Refers to soil that is neither fill or imported material but one that is in its original
                undisturbed state and position.                           ot
                Gravel - Coarse soil particles, larger than sand size, but less than 60mm in diameter.
 .              Cobbles - Rocks greater than 60mm in diameter but less than 600mm in diameter.                                .
                Boulders — Rocks larger than 600mm in diameter.
      te       ‘NOTE : The information contained herein has been compiled following our field and laboratory
                testing, accepted engineering theory and discussions with, and information supplied by our
                client, whom is noted at the head of this report. We offer no warranty for the use of this report by
                other parties without prior written consent from this office.

  .             forandonbehalf
-         _     $CG CONSULTING ENGINEERS

                SCG CONSULTING ENGINEERS                  .       7                                   SCG Ref: 16078(S)  ;

Section 10

ag, me    .

                   SCG CONSULTING ENGINEERS                          LOG SECTIONS        Ref No.16078
                 Depth         TEST SITE No 1          P | Depth          TEST SITE No 2          P
                                Silty Sand SM        [4] 100 |             Silty Sand SM        | 1 |
                           Fine Grained ,PaleGrey [1 | 200 |          FineGrained,PaleGrey      [1 |
                             Roots , Moist , Loose.  | 1 [ 300 |        Roots , Moist , Loose.
               | 400 _|
               | 500_|                              [1 | 500_|
                                Silty Sand SM                              Silty Sand SM
                           Fine Grained ,PaleGrey [1 | 800 |          Fine Grained , Pale Grey
                900 |       (White), Moist, Loose. [1 | 900 |          (White) , Moist , Loose.
                 1000                                       1000                                rt]
                 4100                                       1100                                rt |
                 1200                  ,                    1200
                  1300                                      1300
                  1400                               | + | 1400 |
               | 1500 |      Becoming Med Dense      {1 | 1500          Becoming Med Dense
               | 41600 |       End Hand Auger        | 1 | 1600           End Hand Auger        | 2 |
                  4700                               | 2 | 1700                                 zn
                  1800                               | 2 | 1800                                 3
               | 1900 _|                             | 2 | 1900
               | 2000                                | 3 | 2000 _|                              | 4 |
               | 2100 |                              | 3 | 2100 |                               | 4 |
                 2200                                       2200                                 5 |
               | 2300 _|                             | 4 | 2300 |                               |S
                  2400                               | 5} 2400 |
               | 2500 |                               | 7 | 2500 _|
                  2600                               | 7 | 2600_|
                  2700                                      2700
                  2800                                      2800
               | 2900 |                              | 7 | 2900 |
               | 3000 |                             [7 | 3000_|
                  3100                               |   |  3100                                |  |
                    SPEATREPEIE STORER SR EE REOE RSI RE CIEE OS SEUSS See REIS bet teeo tment tater nae een tne Sate eee eked pea iettreser poset Brae
                    Depth = mm below ground level.                                                iN
                    P = blows per 100mm penetration with an approved 9kg penetrometer.            5:
                    Notation such as (SP) refers to the soil description to Table A1 AS1726 ‘Guide to the description i
                    identification and classification of soils’.                                  f
                    Solid lines represent sharp interface between different soil types. Dotted lines represent i
                    gradation form one soil type to another.                                      3
                   Abbreviations used                                                             i
                    UTP - unable to penetrate, Bec. ~ becoming, N.S.L. — Natural Surface Level    E
                    Med. — medium, MW - Moderately weathered                                      ti
                    EW - extremely weathered, Plast. - Plasticity                                 :
     .              No recovery means unable to extract samples from the base of the bore hole because the soil Bs
                    will not bind in the auger head.                                              i
                    The colour of the soil is often abbreviated, for example Gy = grey Or = orange. z
            .       (Ls=?.?%) Indicates sample location and Linear Shrinkage result.              :
                    The footings must be dug into or supported on piers dug into the shaded material. &
             $CG CONSULTING ENGINEERS                     8                                SCG Ref: 16078(S)

Section 11

wid,  . age                                ,                                      fRevson [Oesetpion                                  |
                                         "som       "en                            fT                   OCC
                                          3                                i       pf
                                              1  —_—— — — —_—_  7         ;           .
                                 §                                |
                                                                  |
                                 |                                |            |
                                 2                                |      BH 2
                                BE                                            ee:
                                                                  |           e
                                      co        ~—__---lt-—-,                                                                 .
                                      k                                    l
                                      |               -_-—                 |
                                      |                                    {
                                      ]                                    |                   .
                                 iy                                  po      dil                                              .
                                    |       |                        |       |
                                    |       |                                |                                                 .
                                    |   - J :                        L =     |  3                                                      ;
                                        |                                |      8               ‘
                                e|      |ige®                      wyal}]       -
                                a)      |1°3e                      Seei])     |.                                               |
                                8                                  33
                                *|      |                                |      |
                                 rm     L—              ,            ca      “|
                                        l                                |

                            |                                  ee
                                    \                                |        |

                                                 |                            |
                                                                     PMO
                                 9
         ,                       9                                                                       .

                                 3               5            of           2               4
             SITE PLAN                            :
                             WEYBA STREET                      .
                                                                                        (Property Boundaries are diagramatic only)
                                                                                      DeSUILD 17A
              vegetation |       Grosses                                                      CONSULTING         ENGINEERS         (G39
                 *                Grasses      _|                                     SCG sirwetural - elsil - geotechnical
               Vegetation                                                                                    +               .     Ea
                     BH2                                                              ABN 40 098 481 899
                @-          Borehole location.                                         48 DUKE STREET SUNSHINE BEACH QLD.4567
                                                                                       Ph (07) 5447 5544          Fax (07) 5447 2634

                            measured as a percentage gradient from
                            high ground to low ground.                                 Project   8 Weyba at ch
                                                                                    3              unshine      Bea
         DO NOT DIMENSION OFF THIS DIAGRAM. =                                       #  pate:   March 2006 rg No. 16078-S|
                                                                        .           3                                                .

Section 12

JA Schematic added, water tanks added 43.09.06
                                                    EXISTING STRUCTURE /OWELUING                                                                                                                                                                                                                                                                                                                               [e._ [WATER TANKS RAGED —_————_—*aaarar,
                                                                                                                                                                                                                                                    PROPOSED BASEMENT                                     SPRAYED RC FACING TO                                                                                  ET
                                                    ALLOTMENTS                                                                                                                                                                                      ENVELOPE.                                             EXCAVATED FACE TO
                     Tj               Yj             THE BULDER/CONTRACTOR                                                                                                   azar         TD mt}                                                                        RP BOUNDARY                       DETAIL.                    +700
                                   Y                 RELEVANT LEVELS FRR TO                                                                                                     CREATE BUNOING IN   [                                                           — ee                                         n+ ences ceverene-----5
                                                    SHALL CONFI ALL                                                                                                                                             gu                          Gua           NN aa                                                          ED          7.718          ETE)
                                       LZ,                                                                                                                                      TEMPORARY HARDSTAND   l /                                                      per ase. ae he  UNIT t                nner    weep eros 7=            5                                .
                                                                                                                                                                                                                                                       creo
                           ad level                                                                                                                                             FOR DIVERISION INTO                                                           vis                                            ¢              “ie    ’
                      W     ay, F      J                    Ths FOOTNG wsTHOUT                                                                                                  SILT FENCES.                                                           le    yo Ue   s  ma    GARAGE                 ',                       le      “|                       \      8
                                                                                                                                                                                                                                                             ao.      ’  A                Lae weeneenee— de...                Yor
                                                                                                                                                                                                                                                       ly,              4                            7
  THS FOOTING {S FOUNDED                                    ABOVE CRITICAL DEPTH                                                                                                                                                                                       s A    FFL 49.850
  BELOW CRITICAL DEPTH                                       UME AND IS UNSTABLE                                                                                      us      Wi                   Ks   Faq Tm                                         V“               Agecrapapr crass
                                                                                                                                                                                                                                                                       coe        7           ¢
  UNE AND [S STABLE.                   a                                                                                                                                         a                                                                           “os         7   ’      s ,  e  r   /   ’                    coos                                         Fr
                                                                                                                                                                              GY                                                                       ia               /   ¢   /       ’   ¢  ’   ,
                                                                                                                                                                                                                                                                                          /   /   7   s  ’
                                                        |                                                                                                                                                                                                             ?    EXISTING HOUSE TO BE                                      nt                                                                         THE COMPRACTON 15 70 STALL APPROMED SAT CTENBON FEACES:
      PIERS OR UNDERPINNING Fi                               UNE OF PROP                                                                       20-40mm AGGREGATE                                                                                       ! o           c sy 4                      rennet                                                                s                                    SPMES AND PROOR TD COMMEMUNG ANY EAIHODNKS. THE FENCE 5 7 BC
                                                        | EXCAVATION EXCAVATION                                                                HARD STAND OVERLAY                                                                                              “os   // .DEMOUSHED ¢                                                                                                            900(#) GEO-FABRIC SRT CONSTRUCTED MONG THE LOWEST BOUNDARY AND
                                                8                                                                                                                                                                                                        a                                                                                                                                           FOED       QQUNEARES TD DEURE Fu STOMEER ENTRAPEDW'
      BELOW THE CRITICAL DEPTH UNE                           OR        NCH,                                                                   FOR DEUIVERY'S DURING           Z                                          Porro ary                          Coe      Cos                       eprtas                                 a                                                        BURED 300 INTO STABLE ~ PUNT FRC RTO PE ALLOTMENT MAS) CAO TORIES THE
           S€ MEDED TO       T                                                                                                                       CONSTRUCTION.                                                       te                            Vy              cous                                                                                                                                     FENCE AnD SHALL NOT ENTER MEGHECUEIES
      @NY FOOTING THAT IS FOUNDED                                                                                                                                                                                                       foe                                                          Ir                              at                                                                         WHE Se OF SUE BUNS DP COUR PROTECTED RSG. THE
     ABOVE THE CRITICAL DEPTH LINE                st A=                                                                                                               ne                                                 boy                           way                                    oy     Words     ,  os  Yq                                                                                        FENCE MUST ROWAN DY PLACE (AM. SUCH TE THAT AORSHED
                                              MO                                                                                                                                                                                        4, or4                  fos                                         f= meg                                                                                              HOSLAPG Sl) ORAWAGL MEASURES ANE SESTALLED
                                                                                                                                                                                                                                                            bv    os
                                                                                                                                                                                                                                       “oe                       coe                          fi     ly                                                                                                         Pete
                                                  TH DETAL AL50 APPUES 70 EXISTING FOUNDATIONS.                                                                                                                          Ie           aL A          wire       a “                             vt                                 CnC nee ee ene                                                                we 1 =n
                                                                                                                                                                                                                                    LT NV                               ?
                                                                PROPERTIES.  PRUNG MUST                           BUMDER TO MAINTAIN STABILITY                                                                          1s                                                     f      ’                                               4
                                                   BE INSTALLED HERE DUSTING FOOTINGS MLL BE                      OF ALL NEIGHBOURING STRUCTURES,            SS Bok in Kerb                        & 1                                    7}        GARAGE     pect diet ie attic                    to                                                                                                         EI mer
                                                  rounoeD ABOVE ANY EXCAVATION CRITICAL DEPTH                     REFER CRITICAL DEPTH LINE                   Weare May                            z|                   Vv              eo          FFL 49,850  |                                    1                                                                                          $200{L) 50 Sq. HOWE SPRES, ee
                                                                                                                                                                RL 51-61                                                1)’                                     tan wee iene --- nnn ne eee eee anne Ve                                                                                                         mH
                                                                                                                  FOR GUIDANCE. ALLOW FOR SPRAYED                     148    sue                   &!                                fw                                                              c-— |     -+-         wneud                      yh                                        —               Ye
                                                                                                                        Te FACING TO EXPOSED CUT                                                                                 =a                                                                         wee nao - =a ene
                                                                                                                  BATTERS 10 PROTECT AGAINST SCOUR.                                                                                                  See            Bcuae               nie                                        22909 ee                       nm                                            Ws
                                                                                                                  SL72 WESH Ml                                                                                                                     OG
                                                                                                                                                                                                                         ee        ee a  ee    ee                                  see
                                                                                                                                                                                                                                                                                                                                    w7.719
                                                                                                                                                                                                                                                                        RP BOUNDARY
                                                                                                                                                                                                                                                                                                          SPRAYED RC FACING TO
                                                                                                                                                                                                                                                                                                          EXCAVATED FACE TO
                           Wet tooled                    125 Thick                                                                                                                                                                                                                                        DETAH.                                                                                               TYPICAL SECTION ~ SILT FENCE
                                      \                  driveway slab.                                                                                                                                                                                                  SITE_PLAN                                                                                                                              Scale 1; 200
                        contro} joint.                                                                                                                                sim    nn
                                                                                                                                                                                                                                                                         Seale 1:    200
                                                                                                                                                                          meu

                     Cut every 2nd                    SL72 mesh                                                                                                                 FIMSHED SITE DRAINAGE IN                                        1.5x4.5x1,0m{D)
                                                                                                                                                                                ACCORDANCE WITH HYDRAULICS
                    wire along {ine                   middie                                                                                                                    DOCUMENTATION,                      BLOCK RETAINING WALL        STORMWATER SOAKAGE PIT
                           of joint.                                                                                                                                  up     Sand                                                               TO DETAIL.
                                                                                                                                                                                          “2-0                                                                          RP BOUNDARY                          4700
                                                                                                                                                                                                                                                                                                             37.79                                  a7
                                                                                                                                                                                     1 ORFLOR                                                   ann nnnn enna nee-- ee eed                wanna nanan ree eee
                                                                                                                                                                                                     |  |  (wm)  |          LDS)       S                                       UNIT 4                       wenn eee nen n naan nn                                a |                                           g 1 $182 Mesh
                                                                                                                                                                                                          ee           IJ   ee                                                GARAGE      henna nena eee.                                                             i                                         zp middle
                                                                                                                                                                                                                                                                              FFL 49.850
                                                                                                                                                                      8                                  he
                                                                                                                                                                                                     \°                    (65)                                         gal                                                                                                                                     | wo ee
                                                                                                                                                                                                                                                                                                                                                                                                                =>---_-
                                                                                                                                                                                              at.          Tithe                                                                                                                                                                                                2
                                                                                                                                                                                               (05)                     DRIVEWAY                    }    1s.) GRATED                                                           ROOF DRANAGE 70 BE PIPED                                        a:               ef Reus
                                                                                                                                                                                                                                                                                                                               TO THE ROAD RESERVE VIA
                  ‘Ground Level  Ie                                                                                                                                                            fe   i a    FalLy              UW                                                                                               WATER TANKS & APPROVED                                                           4) SOomm
                      ESS  |  |                                                                                                                                       nn                                                                                                                                                       KERB ADAPTORS.                                               Sow cut and         Compacted
                        =| | <=                                     SPRAYED 25MPa                                                                                                                                 TW                                                    alt                                                                                                                                     RARSIER, SEMI-HOUNTABLE, MOUNTABLE sond bed
                                 [Pane                                                                                                                                                            Td                                     Files                                                              cee                                                                             breakout
                           iif
                            |       li               IN                                                                                                                                                               ld     awl                                                                                              pase en awe ce nese nee e--————— _                            back of kerb        KER® & CHANNEL OR INVERT CROSSING
                           {=I El                                   CONCRETE FACING
                                        pay            c                                                                                                                                                 a                              or                                 UNIT 2                                                                                                                               CROSSOVER DETAIL
                               ||         |    x                    SL72 MESH MIDDLE                                                                                                                                                                te.                   GARAGE
                                         I       x                                                                                                                                                         mj                           wee                               FFL 49.850
                                                                                                                                                                                                                                                               Manan        nnn eee eed
     SATURATE GROUND AQUACENT               =         eat            Exaaed Level                                                                                     26     sus    ‘my ORMFLOF                                                                                                                                                                                                                 (Scale 1:20)
     EXCAVATION FOR A MINIMUM OF              I=                                                                                                                                                                                                mecccenacnnsesencanena=q              pean ynn-n---- n= wee en --nnd                                             a
     24 HOURS PRIOR TO WORKS                  Sil                                                                                    DRIVEWAY CROSS OVER DETAILS                                                                                                                  RP BOUNDARY                                — Fis
     COMMENCING.                                 =|      LD          LEE}                                                            70 BE IN ACCORDANCE WITH                                      (W1} ACTION TANKS SPLITMASTER                oe     ee                                       ee eee                                                                                                          GENERAL:
                                                      | ——          =|   f=                                                          NOOSA SHIRE COUNCIL'S STD                                                                                  1,5x1.5x1.Om(D
                                                                l    TT                                                              DRAWINGS 9005 & 9019.                                         SOL TANKS FOR EACH UNIT.                     STORMWATER SOAKAGE PIT                                                                                                                                          4, Do nol scale from this drawing.
                                                                                                                                                                                                   SUPPLY VIA ROOF DRAINAGE,                    TO DETAIL.
                                                                                                                                                                                                   OVERFLOW 10 KERB & CHAWNEL.                                                                                                                                                                                  2. All dimensions in millimetres
                    Ly               HON    ™~  Con     EL)   CONCRE T           +41             AMEN                                                                 na     um                    PLUMB FOR RE-USE IN WC's AND                                                                                                                                                                                 3. Setting out dimensions are to be obtained from the orchitectural
                                                  LT                                        ty
                                                                                                                                                                         ne esi                    EXTERNAL APPLICATIONS.          SITE PLAN — DRIVEWAY AND DRAINAGE DETAILS                                                                                                                                    drawings.
                                                                                                                                                                                                                                                                                                                                                                                                                4. Any discrepancies between these drowing and the architectural drawings
                                                                                                                                                                                                                                    Scole 1:    200                                                                                                                                                             are to be referred to the engineer immediately.
                                                                                                                                                                                                                                                                                                                                                                                                                5. The builder is responsible for locating all existing services within ond
                                                                                                                                                                                                                                                                                                                                                                                                                adjacent the diatment and shall ensure thot afl new works ore in
                                                                                                                                                                                                                                                                                                                                                                                                                accordance with the attached critical depth line diagram.
                                                                                                                                                                                                                                                                                                                                                                                                                FOOTPATHS AND DRIVEWAYS:
                                                                                                                                                                                                                                                                                                                                                                                                                1. Existing footpaths to be saw cut prior to removal
                                                                                                                                                                                                                                                                                                                                                                                                                2. Crossings ore not designed for commercial vehicles
                                                                                                                                                                                                                                                                                                                                                                                                                3. Concrete driveway to be 125mm thk. excluding ony finished treatments,
                           LEGEND                                                                                                                                                                                                                                                                                                    wo                                                                         eg. stamping
                                                                                                                                                                                                                                                                                                                                      ao                                                                        4. Concrete surfoce toleronce +5.0mm over 3.0m
                                                                                                                                                                                                                                                                                                                                      ao                     a>    a
                         ~                                                                                                                                                                                                                                                                                                           wo                                                                         5. Concrete N25 in accordance with AS 1379 and AS 3600
                                Indicates existing surface contour                                                                                          Surface                                                                                                                                                                                             |                     4                         6. Reinforcement fabric to AS 1304, ploced central slob depth.
49,007                          and   level  to AHD.                                                                                                     pe                 Capped Concrete encased                                                                                                                                                                                                             7. Expansion joints to be 10mm wide wet tooled with every 2nd mesh wire
                                                                                                                                                                            906 backflush point                                                                                                                                                                                                                 cul along pint.
                                                                                                                                                                                                                                                                                                                                                                                                                8. One access point permitted for each allotment.
                                Indicates proposed finished            spot                                                                                    iii                                                                                                                                                                                                                                              9. For curved driveways, maximum grades apply to inside edge of curve
                                surface levels to AHD.                                                                                                         Aull                                                                                                                                                                                                                                             10. All services to be lacoted and protected os required prior to work
                                                                                                                                YY,               LLM                                                                                  Slotted horizontal                                                                                                                                                       commencing
                  x 12.78       Existing surface spot levels.                                                                   10                                                                                                     99 laterals
                                                                                                                                                                                                                                       pipes equally spaced
                                                                                                                                                                                                                                                                                                                                                                                                                Issue:
                      wl        Denotes wet       tooled    joint   to                                                              aS                                                                                                                                                                                                                                                                          ISSUE FOR CONST.
                                                                                                                                        TT |
                                driveway slab,      refer to details.                                                   Flow                                                                                                                                                                                                                                                                                    CEBUILD TA CONSULTING ENGINEERS
                                125 Thk. Driveway slob on compacted                                                 Slatled Agg pipe                                                                                                                                                                                                          ey                                                                SCG structural - civil - geotechnical
                                                                                                                    150 min clearance
                                material, SL72 mesh, top 40 cover,                                                  to base.                        As per plan              20mm clean                             TYPICAL SECTION « A —                                                        cr |             ago            |"                                       aw      GARAGE                        ABN 40 098 481 899
                                200(1#) x 200(D) edge thickening at                                                                                                         aggregate fully                         DETALS                                                                                                                                                    FFL 49.85                         18 DUKE STREET SUNSHINE BEACH QLD.4567
                                un—supported edges, Flexible joint against                                                                                                  encased in
                                brickwork.                                                                                                                                  geofabric,                                                                                                    Refer Driveway                                                                                                        Ph (07) 5447 5544 Fax (07) 5447 2634
                                                                                                                                                                                                                                                                                  Crossover Detail Above
                                                                                                                                                                                                               — Ensure the inflow into the pit is protected with
                  FALL. y      Indicates direction of fall                                                                       STORMWATER SOAKER PIT DETAIL                                                  an approved leaf and sit quord                                                                                                                       Groted
                                to finished driveway surfoce.                                                                                                                                                  ~ The pit MUST be sropped in geofobric cloth os                                                                                                        drain
                                                                                                                                                                                                                ecified
—_—    —si—            —        Indicates    position    of approved       silt                                                                                                                                = The pit should be backflushed on a regular basis                                                                                DRIVEWAY CENTRE PROFILE
                                                                                                                                                                                                               (3 months) to remove any sills or similiar
                                                                                                                                                                                                               thateriols,
                               retension     fence.                                                                                                                                                            — The pit should only be used for the disposal of                                                                                   (V&H    1: 200)
                                                                                                                                                                                                               stormwater,

                                                                                                                                                                                                                                                                                                                                                                                                                /

Used in these records

About this file

File size
702 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

0015CE08.001.pdf · 702 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.