Skip to the record
Accept no imitations.

Original source · versioned page text

A6578-20-P05 [A] Roadworks Concrete Details

From the archive Alta Engineering Drawings.zip (folder Engineering Drawings). File date in the archive: 2021-03-05 05:31.

of 1

Page text shows just the words. Original shows the document exactly as it was published.

             REINFORCED CONCRETE NOTES:                                                                                                     TESTING:
             GENERALLY, CONCRETE SHALL BE IN ACCORDANCE WITH AUSTRALIAN STANDARD                                                            ALL CONCRETE TESTING IS TO BE CARRIED OUT BY A NATA REGISTERED LABORATORY,                                                                                                                CONCRETE ACCESS DRIVEWAY DETAILS
             SPECIFICATIONS                                                                                                                 IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF AS 1012.
             AS 3600-1994            "SAA CONCRETE STRUCTURES CODE".                                                                        THE FOLLOWING TESTING SCHEDULE IS TO BE ADOPTED IN ADDITION TO THE REQUIREMENTS
                                                                                                                                                                                                                                                                                                                                          180mm CONCRETE SLAB (Fc=32MPa)
             IN ADDITION TO THE ABOVE CODE THE FOLLOWING AUSTRALIAN STANDARD                                                                OF THE MANUFACTURER'S QUALITY ASSURANCE PROGRAM :
                                                                                                                                                                                                                                                                                                                                          (SL82 MESH WITH 50 TOP COVER) on 200mm CEMENT TREATED SUB
             SPECIFICATIONS AND CODES OR THEIR LATEST REVISION SHALL APPLY:                                                      ·          A MINIMUM OF ONE TEST (3 CYLINDERS) TO BE TAKEN FROM EACH ELEMENT CAST ON ANY
                                                                                                                                                                                                                                                                                                                                          BASE on COMPACTED SUBGRADE (100% STANDARD COMPACTION)
             AS 1012 PTS 1-19        METHODS FOR THE TESTING OF CONCRETE (METRIC UNITS)                                                     GIVEN DAY (EG. COLUMNS, FOOTINGS, ETC)
                                                                                                                                                                                                                                                                                                                                          EXACT PAVEMENT DEPTHS TO BE DETERMINED BY GEOTECHNICAL
             AS 3583.1,2,3,8         METHODS OF TEST FOR SUPPLEMENTARY CEMENTITIOUS                                              ·          A MINIMUM OF ONE TEST (3 CYLINDERS) TO BE TAKEN FROM EACH CONCRETE STRENGTH                                                                                                                   ENGINEER.
                                     MATERIALS FOR USE WITH PORTLAND CEMENT                                                                 GRADE CAST ON ANY GIVEN DAY.
             AS 3582.1               SUPPLEMENTARY CEMENTITIOUS MATERIALS FOR USE                                                ·          A MINIMUM OF ONE TEST (3 CYLINDERS) TO BE TAKEN FROM EACH 5OM³ OR PART
                                             WITH PORTLAND CEMENT- FLY ASH                                                                  THEREOF CAST ON A GIVEN DAY FOR EACH STRENGTH GRADE.
             AS 1141                 METHODS FOR SAMPLING AND TESTING AGGREGATES                                                            ALL SAMPLES ARE TO BE TAKEN FROM THE AGITATOR, ON SITE.                                                                                                                                                                     NOTE:
             AS 1302                 STEEL REINFORCING BARS FOR CONCRETE                                                                    IF WATER IS ADDED ON SITE, WITH THE ENGINEER'S PERMISSION, SAMPLES FOR TESTING                                                                                                                       REFER TO LANDSCAPE ARCHITECT'S PLANS FOR CONCRETE
             AS 1303                 HARD DRAWN STEEL REINFORCING WIRE FOR CONCRETE                                                         SHALL BE TAKEN AFTER THE ADDITION OF WATER.                                                                                                                                                          FINISH / COLOURS. IF EXPOSED AGGREGATE IS SPECIFIED
             AS 1304                 HARD DRAWN STEEL WIRE REINFORCING FABRIC FOR                                                                                                                                                                                                                                                                THEN THE CONTRACTOR MUST SUPPLY SAMPLES OF
                                                                                                                                                                                                                                                                                                                                                 AGGREGATE SIZE AND COLOUR FOR APPROVAL PRIOR TO
                                     CONCRETE
                                                                                                                                                                                                                                                                                                                                                 PLACEMENT OF ANY CONCRETE PAVEMENT.
             AS 3972                 PORTLAND AND BLENDED CEMENTS
             AS 1379                 READY-MIXED CONCRETE (METRIC UNITS)                                                                    CURING:
             AS 2758                 CONCRETE AGGREGATES                                                                                    ALL CONCRETE IS TO BE CURED BY AN APPROVED METHOD FOR A MINIMUM OF 28 DAYS AFTER
             AS 1478, 1479           CODE OF PRACTICE FOR USE OF CHEMICAL ADMIXTURES IN                                                     FINISHING.
                                     CONCRETE
                                                                                                                                            CURING METHOD IS TO BE APPROVED BY THE ENGINEER PRIOR TO CONCRETE PLACEMENT AND
             AS 3610                 FORMWORK FOR CONCRETE                                                                                                                                                                                                                                                                                                                        TOOL FINISH CONCRETE
                                                                                                                                            SHALL GENERALLY CONSIST OF ONE OR A COMBINATION OF THE FOLLOWING METHODS :                                                                                                                             CUT EVERY SECOND               BREAK SLAB FULL DEPTH
                     SUPPLY:                                                                                                     ·          CONTINUOUS WATER PONDING.                                                                                                                                                                              WIRE OF MESH                   WHILE STILL "GREEN"
         ·           ALL CONCRETE IS TO BE SUPPLIED BY A LICENSED READY MIXED CONCRETE MANUFACTURER.                             ·          COMPLETE ENCASEMENT IN A WATERPROOF FILM (EG. POLYTHENE).
         ·           NO ON SITE BATCHING IS ACCEPTABLE.                                                                          ·          APPLICATION OF AN APPROVED CURING COMPOUND.
         ·           MANUFACTURERS MUST HAVE AN APPROVED AND CERTIFIED QUALITY ASSURANCE PROGRAM




                                                                                                                                                                                                                                                                                                                                                 180
                     IN PLACE AND BE APPROVED BY THE ENGINEER PRIOR TO SUPPLY OF ANY CONCRETE.
         ·           ALL MATERIALS, STORAGE, BATCHING, ETC TO CONFORM TO THE REQUIREMENTS
                     OF THE RELEVANT AUSTRALIAN STANDARDS.                                                                                                                                                                                                                                                                                                                                                      200mm CTB
         ·           ALL CONCRETE TO BE NORMAL-CLASS IN ACCORDANCE WITH AS 3600 UNLESS NOTED OTHERWISE.
         ·           ALL CONCRETE SHALL HAVE A SHRINKAGE STRAIN NOT EXCEEDING 600 MICROSTRAIN.                                                                                                                                                                                                                                                                                           200 UM VISQUEEN
         ·           ALL CONCRETE IS SPECIFIED BY 28 DAY COMPRESSIVE STRENGTH UNLESS NOTED OTHERWISE.
         ·           ALL REINFORCEMENT TO BE SUPPLIED BY A REGISTERED MANUFACTURER WITH AN APPROVED AND
                     CERTIFIED QUALITY ASSURANCE PROGRAM IN PLACE. ALL REINFORCEMENT IS TO COMPLY WITH THE                                                                                                                                                                                                                                                  BOLSTER JOINT (BJ)
                     REQUIREMENTS OF AS 1302, AS 1303 AND AS 1304 AS APPLICABLE.                                                                                                                                                                                                                                                                                              N.T.S.
         ·           ALL REINFORCEMENT IS TO BE DELIVERED TO SITE FREE FROM OIL, GREASE OR OTHER SURFACE
                     COATINGS WHICH MAY IMPAIR BOND TO CONCRETE.
         ·           ALL REINFORCEMENT TO BE 500 MPA MINIMUM YIELD UNLESS NOTED OTHERWISE.

                     FORMWORK:
         ·           ALL CONCRETE OTHER THAN CAST AGAINST GROUND, SHALL BE PLACED AGAINST TIMBER, PLYWOOD                                                                                                                                                                                                                                                DOWEL SOCKETS TO
                                                                                                                                                                                                                                                                                                                                                         MANUFACTURERS SPEC.           R16 GALVANISED DOWELS
                     OR STEEL FORMS.
                                                                                                                                                                                                                                                                                                                                                         OR EQUAL                      (600 LONG) AT 450 CTS
         ·           ALL FORMWORK SHALL COMPLY WITH THE REQUIREMENTS OF AS 15O9 AND AS 151O.
         ·           REFER ARCHITECT'S DRAWINGS FOR REQUIRED FORMWORK CLASS WHERE APPLICABLE. CLASS B
                                                                                                                                                                                                                                                                                                                                                             SL82 MESH
                     FORMWORK SHALL BE ADOPTED UNLESS NOTED OTHERWISE.                                                                                                                                                                                                                                                                                                                   10mm ABELFEX OR EQUIV.
                                                                                                                                                                                                                                                                                                                                                             50 COVER
         ·           ALL TEMPORARY FORMWORK, FALSEWORK, PROPPING, BRACING, TO BE DESIGNED AND CERTIFIED
                     BY A REGISTERED PROFESSIONAL ENGINEER (RPEQ) PRIOR TO ERECTION.
         ·           ALL REINFORCEMENT TO BE SUPPORTED OFF FORMS WITH PLASTIC OR PLASTIC TIPPED WIRE




                                                                                                                                                                                                                                                                                                                                           180
                     CHAIRS TO PROVIDE THE SPECIFIED COVER. ALL CONCRETE CAST AGAINST GROUND TO BE
                     UNDERLAIN BY WATERPROOF MEMBRANE.
                                                                                                                                                                                                                                                                                                                                                                                                                200mm CTB
             TRANSPORT :                                                                                                                                                                                                                                                                                                                                                300             300
                                                                                                                                                                                                                                                                                                                                                                                                   200 UM VISQUEEN
             ALL CONCRETE IS TO BE TRANSPORTED TO SITE IN AGITATOR TRUCKS.
             CONCRETE NOT PLACED WITHIN ONE HOUR AFTER BATCHING MAY BE REJECTED AT THE                                                                                                                                                                                                                                                                        DOWEL JOINT (DJ)
             ENGINEER'S DISCRETION.
                                                                                                                                                                                                                                                                                                                                                                              N.T.S

                     PLACEMENT, COMPACTION AND FINISHING :
         ·           CONCRETE TO BE PLACED IN FORMS BY HORIZONTAL 'CHUTING' NO MORE THAN 3M³, CONCRETE
                     PUMPING OR KIBBLING. UNDER NO CIRCUMSTANCES SHALL CONCRETE BE INDUCED TO FLOW
                     HORIZONTALLY BY USE OF VIBRATORS.
         ·           ALL CONCRETE SHALL BE PLACED CONTINUOUSLY BETWEEN CONSTRUCTION JOINTS AS DETAILED,
                     IN SUCH A MANNER AS TO AVOID 'COLD JOINTS'. CONSTRUCTION JOINTS SHALL BE LOCATED AS                                                                                                                                                                                                                                    CONCRETE ACCESS DRIVEWAYS
                     DETAILED ON DRAWINGS OR AS INSTRUCTED IN WRITING BY THE ENGINEER.
         ·           ALL CONCRETE IS TO BE COMPACTED UPON PLACEMENT USING 5OMM DIAMETER VIBRATORS.
         ·           SLABS AND BEAMS ARE TO HAVE A FILM OF APPROVED ALPHATIC ALCOHOL APPLIED TO THE SURFACE,
                     DIRECTLY AFTER SCREEDING, PRIOR TO FLOATING, REGARDLESS OF WEATHER CONDITIONS.
         ·           ADDITIONAL PROTECTIVE MEASURES SUCH AS CHILLED MIX WATER, SHADING PLACEMENT AREAS,
                     WIND BREAKS, ETC MAY BE REQUIRED BY THE ENGINEER IF PLACING CONCRETE DURING
                     UNUSUALLY HOT, DRY OR WINDY CONDITIONS.
         ·           ALL CONCRETE SLABS SHALL BE STEEL TROWEL FINISHED UNLESS NOTED OTHERWISE.
         ·           BROOM FINISHING, WHERE SPECIFIED, SHALL BE CARRIED OUT AFTER STEEL TROWEL FINISHING.
         ·           ALL CONCRETE TO BE ORDERED AND PLACED AT 8OMM SLUMP UNLESS NOTED OTHERWISE.
         ·           NO WATER TO BE ADDED ON SITE UNLESS APPROVED BY THE ENGINEER.




NOTE: ONLY DRAWINGS MARKED "FOR CONSTRUCTION" AND BEARING AN ORIGINAL SIGNATURE SHALL BE USED FOR CONSTRUCTION Design:
                                                                                                               PURPOSES.
                                                                                                                       SWT                                                                                                                                                   PROJECT:                                                                  DRAWING TITLE:
                                                                                                                                                                                                                                           ALTA PROJECTS
                                                                                                              Drawn: SWT
                                                                                                                                                                                                                                           A.B.N. 611355330                                                                                            ROADWORKS CONCRETE DETAILS
                                                                              FOR APPROVAL                     Date: July 2020                                                                                                             26 Memorial Avenue, Cotton Tree   PROPOSED SUBDIVISION ESTATE
                                                                                    NOT FOR CONSTRUCTION                                                                                                                                   PO Box 559, Cotton Tree, QLD, 4558                                                                                                                        Revision        Sheet
                                                                                                            Checked:. . . . . . . . . . .                                                                                                  Email: [email protected]
                                                                                                                                                                                                                                                                             at 108 BLACK MOUNTAIN RANGE ROAD, BLACK MOUNTAIN
                                                                                                                                                                                                                                           Tel (07) 5475 4125 Fax (07) 5479 1607                                          DRAWING No:
                                                                                                                                                                                                                                                                                                                                      A6578/20/P05                                                     A           5 of 6
                                                                                  STEPHEN ROBERTS
  A    26/02/2021   ISSUE FOR APPROVAL                          S.T.   S.R.
                                                                               .......................
                                                                                   DIRECTOR APPROVAL             Datum AHD
                                                                                                                                                                                                                                           Web: http://www.alta.net.au       for TOTAL CONCEPT HOMES
 REV    DATE                             DESCRIPTION            BY     CHKD        RPEQ - 7665                    A1 SHEET SIZE              FILENAME : A6539-P05 CONCRETE DETAILS.dwg - DATE : 4/3/21 - 4:35pm - XREF's: H-Approved-SR; H-Checked-SR                                                         Council Ref: ............
Log in to download the original file

A6578-20-P05 [A] ROADWORKS CONCRETE DETAILS.pdf · 245 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.