 Attention: Sonja Heron                                                                                                       31 May 2022
 By Email                                                                                                  ARCOS PROJECT:220329
                                                                                                             Report 01 Revision Rev A
Report on Geotechnical Investigation
Proposed Residential Dwelling
36 Riverpark Drive, Ringtail Creek
Arcos Unit Group Pty Ltd (Arcos Group) has undertaken a geotechnical investigation for the above project and client.
SUMMARY OF INVESTIGATION

                     Results of Australian Geomechanic Society Landslide Risk Assessment
                                                            Low to Moderate*
Note:     The above is a summary of the detailed investigation results discussed within this report. The entire report must be read,
          understood and kept in entirety. * See Section 6 for details




Geotechnical Engineer                                                                             Principal Geotechnical Engineer




Cody Surawski B.Eng (Civ)(Hons), B.Env.Sc                                        Billy Blake B.Eng (Civ)(Hons), MIEAust, RPEQ,
                                                                                                                   CPEng, NER
[email protected]                                                                         [email protected]
For and On Behalf of Arcos Group                                                                For and on Behalf of Arcos Group




Sunshine Coast | Brisbane | Gold Coast
Log in to download the original file

Geotechnical Investigation.pdf · 1.8 MB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

Full text of the other 24 pages

Page 2

                                                                                                       ABN 51 640 311 842
                                                                                                       arcosgroup.com.au
                                                                                      Sunshine Coast | Brisbane | Gold Coast




1         INTRODUCTION
Arcos Unit Group Pty Ltd (Arcos Group) was commissioned to undertake a geotechnical investigation for the project
at the location described on the title page of this report.
This report outlines the results of the investigation, laboratory testing, analysis, and interpretive reporting on the
following items:
 Review of the existing slope stability hazards, their attributed risks and impacts of the proposed development in
  alignment with the practices set out within the Australian Geomechanics Society guidelines; and,
 Provide recommendations from a geotechnical context that will avoid or reduce any potential instability.
This report must be kept in entirety. The use of this document is exclusively undertaken in accordance with our terms
and conditions.

2         REGIONAL GEOLOGY
The site is located on the border between two geological units, as shown in Figure 1. The location of the proposed
dwelling is underlain by Quaternary aged Tiaro Coal Measures, which typically comprises “Clay, silt, sand and gravel;
flood-plain alluvium”, while the lower side of the batter is underlain by Quaternary aged deposits, typically comprising
“Mud, muddy sand, sand and minor peat; swamp and heath deposits in coastal areas”. The encountered material is
in general agreement with the predicted geological units.




FIGURE 1: REGIONAL GEOLOGY


Sunshine Coast | Brisbane | Gold Coast

Page 3

                                                                                                         ABN 51 640 311 842
                                                                                                         arcosgroup.com.au
                                                                                        Sunshine Coast | Brisbane | Gold Coast




3         EXISTING STABILITY RISK
Local authorities prepare mapping tools to aid in assessing potential slope stability requirements. The mapping tools
are a “high level” approach where the site specific investigations are specific to a particular site/allotment. It is
important to note that where a site specific investigation and slope stability assessment are undertaken, they take
precedence.
Reference to the available overlays for the area show the site has been initially mapped as “Moderate” in terms of
landslide hazard.

4         GEOTECHNICAL INVESTIGATION
A previous geotechnical investigation was undertaken by Global Testing Pty Ltd (Global) for the purposes of a site
classification. As part of this investigation, Global undertook the drilling of four boreholes around the proposed
location of the dwelling, on the high side of the batter. The encountered material consisted of clay fill overlying natural
stiff clays, increasing to very stiff clay at depth. No groundwater was noted in their borehole logs. Global’s previous
investigation is attached to this report, and has been used to form part of the analysis undertaken by Arcos. An
additional test pit was excavated at a later date, with the soil logged by a Geotechnical Engineer from Arcos. The
test pit log can be found attached, however in summary, the encountered soil profile was consistent with the findings
from Global. Additionally, the material at the base of the batter was assessed by Arcos, where silty sandy clay was
encountered, with a higher moisture content.

5         WALKOVER ASSESSMENT
Geotechnical comments are based on the factual findings of the investigation, best practice, local experience,
published correlations; however, are fundamentally founded in opinion and this should be considered.
A site walkover assessment was undertaken by a Geotechnical Engineer on 27 April 2022. The proposed dwelling
location is positioned towards the northern end of the property in a cleared pad. The house pad is relatively flat with
an approximately 9 m high batter on the northern side sloping down to meet with alluvial plains running alongside the
river. The slope angle of the batter varies from approximately 20° up to approximately 35°. No obvious signs of
disturbed ground, tension cracks or hummocks were noted in the vicinity of the proposed residence during the
walkover assessment. Some surficial soil creep was noted in the steeper parts of the slope where the water flow
paths were present. Based on the nearby river and dam, as well as overly moist soils at the base of the batter, it is
presumed that the standing water table is approximately 1 m below the existing ground level at the base of the batter.



6         AGS ASSESSMENT
Landslides are caused where a soil or rock mass has a decrease in strength, usually attributed to groundwater,
resulting in the material not being able to maintain its own self-weight resulting in a slope failure.
The Australian Geomechanics Society (AGS) developed a set of tools and procedures for assessing the stability of
a slope. The tools and procedures presented with the AGS documentation form the basis of the assessment
undertaken herein and their documentation is attached for reference.
The guidelines also identify that the regulator typically sets the standard for levels of tolerable risk. AGS defines
tolerable risk as “risks within a range that society can live with so as to secure certain benefits. It is a range of risk
regarded as non-negligible and needing to be kept under review and reduced further if practicable”.
The guides suggest that areas of moderate or greater risk should not be developed unless a rigorous remediation
plan be implemented to reduce the area to a level of Acceptable Risk. AGS defines acceptable risk as “risk which
everyone affected is prepared to accept. Action to further reduce such risk is usually not required unless reasonably
practicable measures are available at low cost in terms of money, time and effort.”.

Sunshine Coast | Brisbane | Gold Coast

Page 4

                                                                                                           ABN 51 640 311 842
                                                                                                           arcosgroup.com.au
                                                                                          Sunshine Coast | Brisbane | Gold Coast




AGS suggest that regulators generally accept risk levels of “low” or lower as a level of acceptable risk.
AGS prepared a semi-quantitative assessment tool for determining the level of risk for a site. The tool separates the
potential hazards for a site, from a stability context, and rates them with a level of risk frequency. The multiplication
of these individual risk frequency summates as the risk frequency rating which is then measured against the levels
of risk nominated by AGS.
The results of this analysis are shown in Table 1.
TABLE 1: AGS ASSESSMENT

                Hazard                         Likelihood               Consequence                      Risk Level
             Global Failure                      Possible                    Minor                         Moderate
         Creep in Shallow Soils                   Likely                  Insignificant                       Low
  Rotational or translational slide down         Possible                    Minor                         Moderate
                 the slope


Based on the results of the AGS assessment, the perceived risk based on the conditions encountered and information
available at the time of the assessment is “Moderate” for the current proposed construction. Where proposed
structures are set back a minimum of 1m from the edge of the slope batter the risk rating may be reduced to “Low”.

7         HILLSIDE CONSTRUCTION
The following works should be implemented in addition to other items highlighted within this document. These points
are considered to be typical good hillside construction practice as explained in attached documentation:
 All footings should be found in natural materials and should extend to a depth which will not adversely effect the
  existing battered slope.
 Fill should be limited to no more than 1 m and should be step keyed into the existing slope. The fill should be
  formed at no steeper than 3H:1V, unless retained by an engineered retention system. All fill should be placed in
  accordance with AS3798.
 Where slopes are not supported by an engineer designed support system, natural slopes within or near movement
  sensitive areas should be no steeper than 2.5H:1V.
 All stormwater and surface water is to be discharged by an approved stormwater drainage system. The use of
  subsurface drainage systems are not suitable unless greater than 50 m downslope from the envelope at this site.
 Ongoing maintenance of effluent wastewater areas are also considered mandatory. The location of the application
  area should be located below the proposed building.
 Plumbing and services must also not be allowed to leak and regular maintenance and inspections should be
  undertaken.
 Erosion protection of cut and fill batters will be required. Batters should incorporate crest and toe drainage.
  Batters should be vegetated appropriately to minimise erosion.
 Overland flow paths will need to be carefully directed to approved outlets to minimise erosion.

8         GEOTECHNICAL RECOMMENDATIONS
The following sections details specific geotechnical constraints or recommendations in addition to general hillside
construction notes.




Sunshine Coast | Brisbane | Gold Coast

Page 5

                                                                                                       ABN 51 640 311 842
                                                                                                       arcosgroup.com.au
                                                                                      Sunshine Coast | Brisbane | Gold Coast




8.1       FOOTINGS
In accordance with industry standards, a geotechnical engineer from Arcos should undertake the testing within the
footings to confirm that the encountered material is in alignment with the adopted parameters and assumptions
provided within this report. Where this does not occur, Arcos cannot be held liable for any of the information presented
within this report.
All footings will need to be designed to accommodate potential ground surface movement, settlement values and
any additional settlement values associated with the placement of new fill.
Settlement for suitably sized and designed high level footings should be in the order of 1-2% of the width of the
footing.
If footings are located adjacent to an underground service or other obstruction that is not homogenous with the
founding strata, the footing should be extended a minimum 0.3 m below an imaginary line projected at a 45 degree
angle from the lowest point of the service/obstruction. This is depicted graphically for reference:




The ultimate geotechnical end bearing and shaft adhesion parameters are presented in Table 2. The values given
will need to reduced by applying a suitable geotechnical strength reduction factor (Φg) for limit state or divided by a
suitable factor of safety for working stress methods. The Φg should be selected by the designer.
Based on the conditions encountered, high level footings or bored piles would be considered suitable


TABLE 2: DEEP LEVEL FOOTING – ULTIMATE GEOTECHNICAL PARAMETERS (LONG PILE)

                  Material                                     Bored                                Bored

                                                             Fb (kPa)                             Fs (kPa)
                   Stiff Clay                                    450                                  20
                Very Stiff Clay                                  900                                  45
 Notes: Fb = Base Bearing (Ultimate); Fs = Shaft Adhesion (Ultimate)


The upper 1 m of soil profile should be ignored in shaft calculations for bored piles to allow for shrinkage cracks. Due
to installation disturbance, shaft adhesion should be ignored for steel screw piles. The values presented in Table 3
assume that the material equal to four pile diameters below the base of any footings is as strong or stronger.



Sunshine Coast | Brisbane | Gold Coast

Page 6

                                                                                                       ABN 51 640 311 842
                                                                                                       arcosgroup.com.au
                                                                                      Sunshine Coast | Brisbane | Gold Coast




Settlement values are subjected to a variety of factors; however, a properly designed and constructed pile should
have a serviceability settlement between 1% and 2% of its’ diameter.


8.2       TEMPORARY BATTER SLOPES
It is understood that a basement is to be constructed as part of the proposed residential dwelling. Therefore, it is
likely that temporary batter slopes will be required, with personnel working at the base of the excavations.
Near vertical temporary excavations less than 1.5 m depth in dry clay soils are likely to be suitable for short term
footing construction, excavation and construction of a basement, or installations of underground services provided
there are no sensitive services or structures, or vehicular trafficked areas located close to the excavation crest.
All excavations greater than 1.5 m depth will need to be benched or battered for stability and prior to personnel
entering the excavation.
Suitable unsurcharged temporary and permanent dry batter slopes for excavations up to 3 m in height in in stiff or
stronger clay soils can be formed at a slope of 1H:1V (short term), however should be confirmed by a geotechnical
engineer at the time of excavation. Where groundwater seepage is encountered, batter slopes will need to be
considerably flatter.


8.3       ACID SULFATE SOILS
Acid sulfate soils (ASS) are coastal and near-coastal soils, sediments or other materials containing iron sulfides.
They are environmentally benign when left undisturbed in an aqueous, anoxic environment, but when exposed to
oxygen the iron sulfides break down, releasing sulfuric acid and soluble iron. Both substances have considerable
ability to degrade the natural and built environment, and the acid may additionally mobilise other pollutants (ie.
aluminium, lead, zinc) if present in the soil.
Previous experience and available guidelines indicate that ASS are normally restricted in extent to recent
(Holocene to Pleistocene age) soil horizons deposited in a saline environment below RL 5 m.
ASS includes actual acid sulfate soils (AASS) and potential acid sulfate soils (PASS). AASS and PASS are often
found within the same soil profile, with AASS generally overlying PASS. AASS are highly acidic resulting from the
oxidation of soil materials that contained sulfides. PASS are soils that contain iron sulfides or sulfidic materials,
which have not yet been oxidised.
Based on the QASSIT guidelines, the following criteria was adopted to determine the presence of acid sulfate soils:
•   pHf of less than 4 indicates oxidation of sulfides has probably occurred in the past, indicating the presence of
    actual acidity (AASS).
• pHf between 4 and 5.5 indicates the soils are acidic. This may be as a result of limited oxidation of sulfides, but
    may also be as a consequence of the presence of organic acids.
• pHf of greater than 5.5 indicates the soil has little or no actual acidity; however this can be common with PASS
    materials or marine-influenced samples.
The pHf test method does not detect acidity bound within sulfides; however the pHfox test gives an indication of any
potential acid release. Results of the pHfox are summarised as follows:
•   pHfox of less than 3, plus a pHfox reading at least one pH unit below pHf, plus a strong reaction with peroxide,
    strongly indicates the presence of PASS.
•   pHfox between 3 and 4 indicates the possibility of PASS material and a pHfox between 4 and 5 may indicate the
    presence of small amounts of sulfide or fine carbonates.
•   pHfox of greater than 5 indicates that PASS material is unlikely.

To provide confirmation of the above qualitative testing, quantitative analytical testing was carried out on selected
samples, generally with the greatest difference in pHf and pHfox readings and strongest reaction to peroxide using
the Chromium Suite method.




Sunshine Coast | Brisbane | Gold Coast

Page 7

                                                                                                       ABN 51 640 311 842
                                                                                                       arcosgroup.com.au
                                                                                      Sunshine Coast | Brisbane | Gold Coast




•   The chromium reducible sulfur values (SCR) where greater than 0.01 %S indicates a significant level of sulfide,
    and where greater than 0.03 %S then the soil has a potential acidity level exceeding the QASSIT guideline value.
• Where the total actual acidity (TAA) value exceeds 18 mol/t then the soil has an acidity level exceeding the
    QASSIT guideline value.
• Where the sulfur in KCl extract values (SKCl) is less than 0.01 %S, then the soil has little or no history of sulfide
    oxidation. A low SKCl combined with a low SCR indicates the soil is not an acid sulfate soil and further development
    of acid is likely to be low.
Generally, the action criterion from the chromium suite of tests, which triggers a requirement for ASS disturbance to
be managed, derived from the Soil Management Guidelines is as follows:
•   Net Acidity (TAA + SCR + SNAS) of greater than or equal to 0.03 %S for disturbances of greater than 1000 tonnes.

The action criterion was exceeded in no samples tested.
The complete treatment and neutralisation of the naturally occurring acidic soils is considered not necessary. The
acidity found naturally in non-ASS soils is not typically damaging to the environment and indeed the ecology. Some
environments are naturally acidic and support ecologies adapted to those acidic conditions.




ATTACHMENTS
About Your Geotechnical Report
Interpretation of the Subsurface Sheets
Client Supplied Information (Soil Report by others)
Test Pit Logs
Practice Note Guidelines for Landslide Risk Management




Sunshine Coast | Brisbane | Gold Coast

Page 8

                                                                                                    ABN 51 640 311 842
                                                                                                    arcosgroup.com.au
                                                                                   Sunshine Coast | Brisbane | Gold Coast




                                         ABOUT YOUR GEOTECH REPORT



                                                            Reporting
These notes have been provided to clarify and               The report has been prepared and reviewed by
enhance the reader’s understanding of the                   suitably qualified and experienced persons. The
terminology used throughout the report, and also to         persons draw on previous experience, local
identify where limitations exist. All investigations are    knowledge, published literature, and otherwise
undertaken based on budgetary constraints which             standard engineering approaches and principals. The
impart a level of uncertainty as a result of limiting the   context of which the report has been prepared for must
amount of investigation undertaken.                         be considered and if the context changes, due
                                                            consideration should be given to the possibility that the
                                                            report is no longer considered relevant and review by
Copyright                                                   Arcos Unit Group Pty Ltd must be undertaken.
This report remains the property of Arcos Unit Group        Arcos Unit Group Pty Ltd undertakes quality
Pty Ltd at all times unless ownership is transferred in     assurance checks in accordance with its’ quality
writing. It cannot be included in any documentation         system requirements; however, restrictions on the
without the express written permission of Arcos Unit        project outside of Arcos Unit Group Pty Ltd’s control
Group Pty Ltd                                               can result in unanticipated variations, changes in
                                                            policy or interpretation of said policies by the relevant
                                                            authority, or the actions of contractors subject to
Subsurface Report Sheets (Bores etc)                        commercial pressure.
The provided subsurface sheets are inherently an
interpretation undertaken by a suitably qualified and
experienced person; however, the reliability of the
                                                            Site Variations
provided information will rely on the method of             If site variations become evident at the time of
investigation. It is prudent to state that these sheets     construction or after the release of a report, Arcos Unit
only represent a very small percentage of the               Group Pty Ltd requests immediately notification. This
subsurface conditions across a particular project.          notification is proposed in order to assist in
                                                            remediation prior to any permanent structures or
It reasons that given the relatively small representation
                                                            design procedures are undertaken.
of the subsurface conditions for a project, spacial
variability between testing locations must be taken into
consideration including the orientation of strata           Collaboration
intersections.
                                                            Arcos Unit Group Pty Ltd strongly recommends open
The presence or lack of groundwater is usually stated       and collaborative communication about the use and
on the subsurface sheets; however, it must be noted         inherent interpretation of Arcos Unit Group Pty Ltd’s
that the measurements undertaken onsite are typically       report. Please contact the author of the report to
very inaccurate and if the presence or lack of              arrange for an obligation free discussion regarding the
groundwater will have any degree of affect on the           potential benefits of having geotechnical consultants.
project, additional groundwater monitoring techniques
should be employed such as groundwater monitoring
wells.




Sunshine Coast | Brisbane | Gold Coast

Page 9

                                                                                                           ABN 51 640 311 842
                                                                                                           arcosgroup.com.au
                                                                                        Sunshine Coast | Brisbane | Gold Coast




                                      Interpretation of the Subsurface Sheets


The terminology included on Arcos Unit Group Pty            the most important component. Typically, the strength
Ltd’s has been evolved from AS1726:2016. Typically          of rock is based on laboratory testing, tactile
a soil’s strength, colour, plasticity, grain size, other    assessment and other observations as relevant. The
inclusions, and moisture will be described. A rock’s        industry standard method for assessing the strength of
strength, weathering, colour, grain, and other              rock in the field is to use the point load strength index
inclusions are typically described.                         (AS4133.4.1). It is important to note that the point load
                                                            strength index does not take into consideration the
                                                            degree of fracturing of a rock mass which can both
Soil                                                        lower and increase the overall rock strength. The
Soil is typically described by the components that          strength of rock is broken down as follows:
make it up by percentage or whichever has a                 Very Low Strength (VLS)              < 2 MPa (UCS)
governing behaviour. The types and sizes reproduced         Low Strength (LS)                    2 to 6 MPa (UCS)
from AS1726 are:                                            Medium Strength (MS)                 6 to 20 MPa (UCS)
Boulder >200 mm                                             High Strength (HS)                   20 to 60 MPa (UCS)
Cobble 63 to 200 mm                                         Very High Strength (VHS)             60 to 200 MPa (UCS)
Gravel 2.36 to 63 mm                                        Extremely High Strength (EHS)        > 200 MPa (UCS)
Sand    0.075 to 2.36 mm                                    Very Low Strength (VLS)              < 0.1 Is(50)
Silty   0.002 to 0.075 mm                                   Low Strength (LS)                    0.1 to 0.3 Is(50)
Clay    < 0.002 mm                                          Medium Strength (MS)                 0.30 to 1.0 Is(50)
The strength of soil is usually assessed by suitably        High Strength (HS)                   1.0 to 3.0 Is(50)
experienced persons through the use of laboratory           Very High Strength (VHS)             3.0 to 10.0 Is(50)
test results, published literature, field assessments or    Extremely High Strength (EHS)        > 10.0 Is(50)
a combination of the above. The strength of soil is         The Is(50) values are based on a correlation between
characterised into either cohesive (clays and silts) or     the unconfined compressive strength (UCS) of 20.
cohesionless (sands and gravels) as shown below:            This value varies significantly and site specific testing
Cohessive Soil Strength Term                                must take precedence.

Very Soft            < 12.5 kPa                             Rock weathering is broken down as follows:
Soft                 12.5 to 25 kPa                         Extremely weathered (EW) Behaves as soil but rock structure
Firm                 25 to 50 kPa                                  evident
Stiff                50 to 100 kPa                          Highly weathered (HW) Colour and strength of original fresh rock
                                                                    is not recognisable. Decomposition of rock evident
Very Stiff           100 to 200 kPa
                                                            Moderately weathered (MW)    Defects are heavily stained with
Hard                 > 200 kPa
                                                                   rock mass showing signs of discolouration
Cohesionless Soils Strength Term (uncorrected Qc)           Slightly weathered (SW)     Some staining but minimal to no
Very Loose           <2 MPa                                          change in strength

Loose                2 to 5 MPa                             Fresh stained       (FS) Minor staining evident

Medium Dense         5 to 15 MPa                            Fresh rock        (FR) No change

Dense                15 to 25 MPa                           Rock fracturing is broken down as follows and can only
Very Dense           > 25 MPa                               be accurately described where undamaged
                                                            continuous sampling has been undertaken:
                                                            Fragmented (Fg)      Defect spacings < 20 mm
Rock
                                                            Highly Fractured (HF)    Defect spacings 20 to 50 mm
Rock is typically described by the components that          Fractured (Fr) Defect spacings 50 to 200 mm
make it up by percentage or whichever has a                 Slightly Fractured (SF) Defect spacings 200 to 1000 mm
governing behaviour. The strength of rock is typically      Unbroken (Ub) Defect spacings > 1000 mm




Sunshine Coast | Brisbane | Gold Coast

Page 10

                                                                                          PH: 07 54 740 900
                                                                        3/53 Gateway Drive, Noosaville 4566
                                                                             [email protected]
                                                                                           QBCC 15288478




 JOB NUMBER              21-1559 SITE CLASSIFICATION REPORT
 CLIENT                  SONJA GLINSTER
 SITE LOCATION           PROPOSED DWELLING
                         36 RIVER PARK DRIVE, RINGTAIL CREEK.
 REPORT DATE             21/03/2022


1. INTRODUCTION
The purpose of this report is to classify the subject allotment in accordance with Australian Standard
2870 - 2011 'Residential Slabs and Footings'. From this classification, a footing system can be recom-
mended for the structure so as to allow adequate performance of the footings under the soil conditions
determined at the site.
Trees: The classification herein excludes the effect of trees on the site.


2. SITE DESCRIPTION

 Type of Allotment                                                      Acreage
 Vegetation                                                             Grassed
 Slope                                                   5% to north-east (30% Slope Adjacent)
 Surface Water will Drain Towards                                      North-east
 Will Surface Water from adjoining                                         No
 allotments traverse this site?
 Surrounding Allotments
                                 Left                                  Acreage
                                Right                                  Acreage
                                Rear                                   Acreage
 Depth to Weathered Rock                                          BH1 (N/a), BH2 (N/a)
 Depth to Water Table                                             BH1 (N/a), BH2 (N/a)


3. SITE CLASSIFICATION AND TARGET STRATA
.Based on the findings of the site investigation, the classification of the site is considered to conform to:

         CLASS “P” – (Due to Uncontrolled Fill - See Target Stratum)
    PLEASE NOTE: If not for the above reasons, this site would have the characteristics of a Class H2 Site.

in accordance with Australian Standard 2870 - 2011, 'Residential Slabs and Footings, Construction'.
The Target Stratum for the design of the proposed structure at location BH1 is the SILTY
SANDY CLAY at a depth of 2200mm below existing ground surface. The Target Stratum for the
design of the proposed structure at location BH2 is the SANDY CLAY at a depth of 2900mm
below existing ground surface. The Target Stratum for the design of the proposed structure at
location BH3 is the SANDY CLAY at a depth of 3000mm below existing ground surface. The
Target Stratum for the design of the proposed structure at location BH4 is the SANDY CLAY at
a depth of 2700mm below existing ground surface.




       Page | 1 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                             21-1559

Page 11

                                                                                        PH: 07 54 740 900
                                                                      3/53 Gateway Drive, Noosaville 4566
                                                                           [email protected]
                                                                                         QBCC 15288478



PLEASE NOTE: This report does not address slope stability. If a slope stability analysis is
required, the services of a suitably qualified geotechnical engineer should be sought.
We can recommend one or organise this service on your behalf.
It is the designing engineer’s responsibility to address the potential influence of any trees present
on or around the proposed building site.

If any further fill is placed over the existing ground, the structure shall be piered through the fill
into the existing material. Further note that the placement of reactive material as fill, or cutting
of the site may change the site’s classification.


4. SOIL PROFILE
Refer to Soil Profile Report for borelog information.
Whilst every effort has been made to ensure that the borelogs carried out at the subject allotment are
indicative of the soil profile over the site any discrepancy between the profile detailed in the borelogs
and that observed during construction shall be referred to Global Testing for immediate attention.


5. MATERIALS LABORATORY TEST RESULTS
Soil Laboratory testing carried out on samples of the soil taken from the site gave the following results:

                    BOREHOLE                                                 BH1
                    DEPTH RANGE OF SAMPLE                                 400-700mm
                    LIQUID LIMIT (%)                                          N/a
                    PLASTIC LIMIT (%)                                         N/a
                    PLASTIC INDEX (%)                                         N/a
                    LINEAR SHRINKAGE (%)                                      N/a
                    INSTABILITY INDEX (%)                                     N/a
                    SHRINK SWELL INDEX, Iss (%)                               5.4
                    PREDICTED SURFACE MOVEMENT                                N/a


Please note that the Plasticity Index (PI) determined by the Atterberg Test may be correlated to an
Instability Index (Ips)with reference to the results of extensive testing carried out by others, notably, Dr
P Mitchell, ‘Footings for Small Scale Domestic Structures,’ March 1990.
 Yours Sincerely,




 (Michael Pinkney - Office Manager-)




       Page | 2 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                             21-1559

Page 12

                                                                                         PH: 07 54 740 900
                                                                       3/53 Gateway Drive, Noosaville 4566
                                                                            [email protected]
                                                                                          QBCC 15288478


                                               LIMITATIONS

Recommendations given in this report are based on the information supplied by the client regarding the
proposed building construction in conjunction with the findings of the investigation. Any change in
construction type, building location or omission in the client supplied information, may require addi-
tional testing and/or make the recommendations invalid.


The recommendations herein identify a target soil stratum into which the footings are to be founded.
The target stratum has been located by the depth in mm of the target stratum's upper horizon boundary
below the existing ground surface level at the time of the site investigation. Any cutting or filling works
and any surface erosion or deposits subsequent to the site investigation, will alter the measured location
of the stratum relative to the surface. Where required, the author should be notified in such cases to
confirm the location of the target stratum.


The description of the soil given in the Soil Profile section of this report is intended as a brief overview
of the soil's primary constituents. For a detailed classification of the soil, the reader should refer to the
Soil Profile Reports and/or Borehole Reports attached to this report.

Every reasonable effort has been made to locate the test sites so that the borehole profiles are repre-
sentative of the soil conditions within the area investigated. The client should be made aware however,
that exploration is limited by time available and economic restraints. In some cases, soil conditions can
change dramatically over short distances, therefore, even careful exploration programs may not locate
all the variations.

If soil conditions different from those shown in this report are encountered or are inferred from other
sources, then the author must be notified immediately.

This report may not be reproduced except in full. The information and drawings provided with this
report shall only be used and will only be applicable for the development shown on the client supplied
information provided for this site.

Any dimensions, contours, slope directions and magnitudes shown on the Test Locality Plan shall not
be used for any building construction or costing calculations. The purpose of the plan is to show ap-
proximate location of field tests only.

Any changes made to these recommendations by persons unauthorised by the author will legally be
interpreted as that person assuming the responsibility for the long-term performance of the footing sys-
tem.

The recommendations contained in this report have not taken into consideration the long-term effects
of any previous, current or potential subsurface work by mining companies or potential slope instability
problems. At the time of writing this report neither our client (nor his agent) nor the local authority had
made the author aware that these problems may be affecting this allotment. If a mining subsidence or
slope stability assessment is required for this allotment, the recommendations of a suitably qualified
geotechnical engineer should be sought.



       Page | 3 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                             21-1559

Page 13

                                                                                          PH: 07 54 740 900
                                                                        3/53 Gateway Drive, Noosaville 4566
                                                                             [email protected]
                                                                                           QBCC 15288478


SOIL PROFILE REPORT
CLIENT:      SONJA GLINSTER                            AUTHORISED              SONJA GLINSTER
                                                       BY:
PROJECT:     36 RIVER PARK DRIVE,                      DATE TESTED:            28/02/2022
             RINGTAIL CREEK.                           JOB NO:                 21-1559

                        Drilling Method: Jacro 105 100mm.                                      Borehole
                                                                                                  No.1
   Depth      Description                                                     PENET.          Est. Bearing
   (mm)                                                                      (blows per        Capacity
                                                                              100mm)              (kPa)

                                                                         1       2   3    4
     0        (FILL) SANDY CLAY (CI)-Medium              plasticity,
              grey-brown, fine to coarse sand, fine to coarse gravel,
              moist, firm.
    100                                                                  2                         50
    200       (FILL) SANDY CLAY (CI)-Medium              plasticity,     3                        100
              grey-brown, fine to coarse sand, fine to coarse gravel,
              moist, stiff.
    300                                                                  4
    400       SANDY CLAY (CH)-High plasticity, red/brown, pale           5
              grey, fine to coarse sand, moist, stiff.
    500                                                                 4                         125
    600                                                                 5
    700                                                                 6                        >200
    800                                                                 6
    900                                                                 5
   1000                                                                 6                        >200
   1100                                                                 5
   1200                                                                 6
   1300                                                                 5
   1400                                                                 5                         150
   1500                                                                 5
   1600                                                                 6                        >200
   1700                                                                 6
   1800                                                                 7
   1900                                                                 7
   2000                                                                 7
   2100                                                                 7
   2200       SILTY SAND CLAY (CH) High plasticity, brown,/             10
              pale grey, fine to coarse sand, moist, very stiff.
   2300                                                                  19
   2400                                                                 >20
   2500
   2600
   2700
   2800
   2900
   3000
   3100
   3200
   3300
   3400
   3500       Hole Terminated




    Page | 4 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                          21-1559

Page 14

                                                                                            PH: 07 54 740 900
                                                                          3/53 Gateway Drive, Noosaville 4566
                                                                               [email protected]
                                                                                             QBCC 15288478




SOIL PROFILE REPORT
CLIENT:      SONJA GLINSTER                          AUTHORISED                SONJA GLINSTER
                                                     BY:
PROJECT:     36 RIVER PARK DRIVE,                    DATE TESTED:              28/02/2022
             RINGTAIL CREEK.                         JOB NO:                   21-1559



                        Drilling Method: Jacro 105 100mm.                                       Borehole
                                                                                                   No.2
   Depth      Description                                                      PENET.          Est. Bearing
   (mm)                                                                       (blows per        Capacity
                                                                               100mm)              (kPa)

                                                                          1      2    3    4
     0        (FILL) SANDY CLAY (CI)-Medium plasticity, grey-
              brown, fine to coarse sand, fine to coarse gravel, moist,
              stiff.
    100                                                                          3                 100
    200                                                                          3
    300                                                                          3
    400       SANDY CLAY (CH)-High plasticity, red/brown, pale                   4                 125
              grey, fine to coarse sand, moist, stiff.
    500                                                                          3
    600                                                                          4
    700                                                                          4
    800                                                                          3                 100
    900                                                                          4
   1000                                                                          4
   1100                                                                          3
   1200                                                                          4                 125
   1300                                                                          5
   1400                                                                          5
   1500                                                                          6                >200
   1600                                                                          7
   1700                                                                          7
   1800                                                                          6
   1900                                                                          6
   2000                                                                          6                >200
   2100                                                                          6
   2200                                                                          7
   2300                                                                          7
   2400                                                                          8
   2500                                                                          9
   2600                                                                          9
   2700                                                                          8
   2800                                                                          9
   2900       SANDY CLAY (CH)-High plasticity, red/brown, pale                  10                >200
              grey, fine to coarse sand, moist, very stiff.
   3000                                                                        15
   3100                                                                        >20
   3200
   3300
   3400
   3500       Hole Terminated



    Page | 5 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                          21-1559

Page 15

                                                                                          PH: 07 54 740 900
                                                                        3/53 Gateway Drive, Noosaville 4566
                                                                             [email protected]
                                                                                           QBCC 15288478


SOIL PROFILE REPORT
CLIENT:      SONJA GLINSTER                          AUTHORISED              SONJA GLINSTER
                                                     BY:
PROJECT:     36 RIVER PARK DRIVE,                    DATE TESTED:            28/02/2022
             RINGTAIL CREEK.                         JOB NO:                 21-1559

                        Drilling Method: Jacro 105 100mm.                                        Borehole
                                                                                                    No.3
   Depth      Description                                                    PENET.          Est. Bearing Ca-
   (mm)                                                                     (blows per             pacity
                                                                             100mm)                (kPa)

                                                                        1   2     3      4
     0        (FILL) SANDY CLAY (CI)-Medium              plasticity,
              grey-brown, fine to coarse sand, fine to coarse gravel,
              moist, stiff.
    100                                                                           4                125
    200                                                                           3
    300                                                                           4
    400                                                                          >20
    500                                                                           -            Pre-Drilled
    600       SANDY CLAY (CH)-High plasticity, red/brown, pale                    -
              grey, fine to coarse sand, moist, stiff.
   700                                                                             -
   800                                                                             -
   900                                                                             -
   1000                                                                            -
   1100                                                                            -
   1200                                                                            -
   1300                                                                            -
   1400                                                                            -
   1500                                                                            -
   1600                                                                           5                150
   1700                                                                           7
   1800                                                                           7
   1900                                                                           7
   2000                                                                           7
   2100                                                                           7
   2200                                                                           6                200
   2300                                                                           7
   2400                                                                           7
   2500                                                                           7
   2600                                                                           7
   2700                                                                           7
   2800                                                                           9
   2900                                                                           9
   3000       SANDY CLAY (CH)-High plasticity, red/brown, pale                    10              >200
              grey, fine to coarse sand, moist, very stiff.
   3100                                                                           10
   3200                                                                           11
   3300                                                                           11
   3400                                                                           11
   3500       Hole Terminated                                                     11




    Page | 6 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                          21-1559

Page 16

                                                                                             PH: 07 54 740 900
                                                                           3/53 Gateway Drive, Noosaville 4566
                                                                                [email protected]
                                                                                              QBCC 15288478


SOIL PROFILE REPORT
CLIENT:      SONJA GLINSTER                         AUTHORISED                  SONJA GLINSTER
                                                    BY:
PROJECT:     36 RIVER PARK DRIVE,                   DATE TESTED:                28/02/2022
             RINGTAIL CREEK.                        JOB NO:                     21-1559



                       Drilling Method: Jacro 105 100mm.                                          Borehole
                                                                                                     No.4
  Depth      Description                                                    PENET.            Est. Bearing Ca-
  (mm)                                                                 (blows per 100mm)            pacity
                                                                                                    (kPa)
                                                                       1    2    3    4
    0        (FILL) SANDY CLAY (CI)-Medium              plasticity,
             grey-brown, fine to coarse sand, fine to coarse gravel,
             moist, firm.
   100                                                                                4            125
   200                                                                                6            >200
   300                                                                                8
   400                                                                                7
   500                                                                                6
   600       SANDY CLAY (CI)-Medium plasticity, red/brown,                            5             150
             pale grey, fine to coarse sand, moist, stiff.
   700                                                                                4
   800                                                                                3
   900                                                                                3             100
   1000                                                                               4
   1100                                                                               5
   1200                                                                               5
   1300                                                                               4
   1400                                                                               5             150
   1500                                                                               5
   1600                                                                               6            >200
   1700                                                                               7
   1800                                                                               7
   1900                                                                               8
   2000                                                                               7
   2100                                                                               6             200
   2200                                                                               6
   2300                                                                               9
   2400                                                                               9
   2500      SANDY CLAY (CH)-High plasticity, brown, fine to                          6
             coarse sand, moist, stiff.
   2600                                                                               7
   2700      SANDY CLAY (CH)-High plasticity, brown, fine to                          11           >200
             coarse sand, moist, very stiff.
   2800                                                                              >20
   2900
   3000      SILTY SAND CLAY (CH) High plasticity, brown,/
             pale grey, fine to coarse sand, moist, stiff.
   3100
   3200
   3300
   3400
   3500      Hole Terminated




    Page | 7 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                          21-1559

Page 17

                                                                           PH: 07 54 740 900
                                                         3/53 Gateway Drive, Noosaville 4566
                                                              [email protected]
                                                                            QBCC 15288478




       Site- 36 RIVER PARK DRIVE, RINGTAIL CREEK.




Page | 8 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                      21-1559

Page 18

                                                                                                                                                                                                                                                                                                                                                                                                   LEGEND

                                                                                                                                                                                                                                                                                                                                                                                                                 BHx = BOREHOLE LOCATION


                                                                                                                                                                                                                                                                                                                                                                                 TH
                                                                                                                                                                                                                                                                                                                                                                                R
                                                                                                                                                                                                                                                                                                                                                                               O                                 PNx = DYNAMIC CONE
                                                                                                                                                                                                                                                                                                                                                                           N                                     PENETROMETER LOCATION


                                                                                                                                                                                                                                                                                                                                                                                                                 PTx = PERCOLATION TEST



                                                                                                                                                                                                                                                                                                                                                                                                                 =TREES


                                                                                                                                                                                                            ADVANCED SECONDARY ASTP

                                                                                                                                                                                                            TO BE INSTALLED IN A SUITABLE LOCATION
                                                                                                                                                                                                            BY THE INSTALLING PLUMBER NOT ADJACENT
                                                                                                                                                                                                            TO LIVING ROOMS OR BEDROOMS
                                                                                    6.0                                                                                         LEVEL
                                                          5.0                             7.0                                                                                                                                                                                                                                                  RESERVE AREA

                                              4.0                                                                                                                  8.0
                         3.0                                                                                                     30% SLOPE                                                                                                                                                         8.0

                                                                                                                                                                                                                           30% SLOPE

                                                                                                                                                           PN 3
                                                                                                                                                           BH 3
                                                                                                                                                                                                                                                     PN 1                                                                                                                              K-RAIN VALVE (TO BE INSTALLED)
                                                                                                                                                                                                                                                                                                                                                                    BH7
                                                                                                                                                                                                                                                     BH 1
                                                                                                                                                                                                                                                                                              9.0 40000                                                             PT3
         3.0
                   4.0                                                                    PN 4                             PROPOSED RESIDENCE
                                                                                          BH 4
                                                                                                                                                                                                                                                                                                                                    BH6
                                5.0                                                                                                                                                                                                                                                                                                 PT2                                                PROPOSED FIXED SURFACE SPRINKLER IRRIGATION
                                                                                                                                                                                                                                                                                                                                                                                       AREA = 360M2
                                                                                                                                                                         PN 2                                                                                                                                                                                                          35 PLUMES REQUIRED
                                                                                                                                                                         BH 2                                                                                                                                                                                                          TO BE PLANTED OUT WITH A MINIMUM OF 35 PLANTS,
                                                                                                                                                                                                                                                                                                                                                                                       MULCHED, BORDER AND INSTALL




                                                                                                                                                                                                                                                                                                               24000
                                                                                                                                                                                                                                                                                        9.0
                                                                                                5% SLOPE
                                                    6.0




                                                                                                                                                                                                                                                                                                                        1800 3400
                                                                                                                                                                  LEVEL                                                                                                                                                             BH5
                                                                                                                                                                                                                                                                                                                                    PT1                                                FLUSH OUT VALVES
                                                                                                                                                                                                                                                                                                                                                                                       (TO BE INSTALLED)

                                                                                                                                                                                                                                                                                                                                          1500 3000

                                                                                                                                                                                                                                                                                                                                                       15000

                                                                7.0

                                                                                                                                                                                                                                                                                                                                                      5% SLOPE



                                                                            8.0




                                                                                                                                                                                                                                                         PPROX. EXTENT OF




                                                                                                                                                                                                   IVEWAY
                                                                                                                                                                                                                                                        PREDOMINANT TREE




                                                                                                                                                                                              NG DR
                                                                                           9.0                                                                                                                                                          LINE SHOWN SHADED




                                                                                                                                                                                        EXISTI
                                                                                                                                                                                                                                                            FIRE SOURCE


                                                                 PPROX. EXTENT OF
                                                                PREDOMINANT TREE
                                                                LINE SHOWN SHADED
                                                                    FIRE SOURCE




                                                                                                                                                                                                                                                                                                                                    HEAVY DROPLET (PLUMES E.G 10MM FEEDER LINES)



                                                                                                                                                                                                                                                                                                                                                                                                           TYP 150 HIGH MOUND SURROUND




                                                                                                                                                                                                                                                                                                                       PLUMES
                                                                                                                                                                                                                                                             1500                         3000




                                                                                                                                                                                                                                                                                                                         300
               SITE PLAN
               SCALE: 1 : 350



                                                                                                                                                                                                                                                                              25-32MM DIAMETER POLY LINES LAID BENEATH SURFACE.                                                       ULTILIZE EXISTING VEGETATION



                                                                                                                                                                                                                                                                                                    TYP FIXED SPRAY SURFACE IRRIGATION SYSTEM


                                                                                                           SITE CLASSIFICATION | EFFLUENT DESIGN  CLIENT DETAILS                    PROJECT DETAILS                                    SITE INFORMATION                      DRAWING TITLE                                                                                                             JOB No.            DRG No. REVISION
                                                                                                           SUNSHINE COAST | BRISBANE | GOLD COAST
                                                                                                                                                                                                                                       RPD:                              -
                                                                                                           [email protected]
                                                                                                                                                             SONJA GLINSTER         EFFLUENT DISPOSAL
                                                                                                                                                                                                                                                                             SITE PLAN
                                                                                                                                                                                                                                                                                                                                                                                                 21/1559 152                               1
                                                                                                                                                                                                                                       POSTCODE:                      4565
                                                                                                           COPYRIGHT © All rights reserved, this work is
                                                                                                           copyright and cannot be reproduced or copied
                                                                                                                                                                                    LOT 2, 36 RIVER PARK DR,                           SUBURB:              RINGTAIL CREEK
22/03/2022 FOR CONSTRUCTION                                      AA   1
  DATE                                DESCRIPTION                BY   REV
                                                                                                           in any form without prior consent
                                                                                                                                                                                    RINGTAIL CREEK, QLD                                AUTHORITY:     NOOSA SHIRE COUNCIL    DRAWN: AA            DESIGN: MP            CHECK: GB                DATE:     22/03/2022 SCALE: As indicated@A1

Page 19

                                                    CLIENT:       Sonja Heron                                       PROJECT #: 220329                        BORE
                                                    PROJECT: Proposed Residential Dwelling
                                                    ADDRESS: 36 River Park Drive, Ringtail Creek
                                                                                                                    LOGGED:          CS
                                                                                                                                                             1
                                                                                                                    EASTING:         498423 m
                                                    DRILL RIG: Excavator                                            NORTHING: 7089075 m                      TEST DATE: 27/04/2022

                                                                                                                                         Sampling & Testing
              Graphic Log




                                                                                                                                                                          DCP Results
                                                                         Material Description                                                    Results &
                                                                                                                                    Type                              (blows per 100 mm)
                                                                                                                                                 Comments
                            Water




 RL Depth
 (m) (m)                                                                                                                                                                5   10   15   20
                                    TOPSOIL Sandy CLAY CL: stiff, low plasticity, dark grey-brown, fine to medium grained sand,
                                    W<PL (fill)
                                                                                                                                                                  3




                                                                                                                                                                  3


                                                                                                                                           0.2
                             0.2 FILL Sandy CLAY CI: stiff, medium to high plasticity, orange-brown mottled red, fine to medium
                                    grained sand, w<PL (fill)
                                                                                                                                                                  4




                                                                                                                                     D                            3




                                                                                                                                                                  4


                                                                                                                                           0.5
                             0.5 Sandy CLAY CI: stiff to very stiff, medium to high plasticity, pale grey and orange-brown
                                    mottled red, fine to medium grained sand, with silt, w<PL
                                                                                                                                                                  5




                                                                                                                                                                  5




                                                                                                                                     D                            5




                                                                                                                                                                  5




                                                                                                                                                                  5

        1
                                                                                                                                           1
                                                                                                                                                                  6




                                                                                                                                                                  6




                                                                                                                                     D                            6




                                                                                                                                                                  7




                                                                                                                                                                  6


                                                                                                                                           1.5
                                                                                                                                                                  7




                                                                                                                                                                  7




                                                                                                                                     D                            7




                                                                                                                                                                  7




        2
                                                                                                                                           2
                                    medium plasticity




                                                                                                                                     D




                                                                                                                                           2.5




                                                                                                                                     D




                                                                                                                                           2.9
                             2.9 Bore Terminated at 2.9 m.
        3



DRILLING METHOD: Excavator                                                                                                                        CASING: Nil
GROUNDWATER: no groundwater seepage noted at the time of investigation
REMARKS:

                                                                                        LEGEND:
       D     - Disturbed Sample from Auger                                 SPT - Standard Penetration Test                        - Groundwater Seepage Level
       B     - Bulk Sample from Auger                                      Is50 - Point Load Result (MPa)                         - Standing Groundwater Level
       C     - Rock Core                                                   PP - Pocket Penetrometer (kPa)                         - Partial Groundwater Loss
       U50   - Undisturbed Sample (mm)                                                                                            - Perched Groundwater Level

Page 20

                                                   CLIENT:        Sonja Heron                                         PROJECT #: 220329                  BORE
                                                   PROJECT: Proposed Residential Dwelling
                                                   ADDRESS: 36 River Park Drive, Ringtail Creek
                                                                                                                      LOGGED:       CS
                                                                                                                                                         2
                                                                                                                      EASTING:      498495 m
                                                   DRILL RIG: Excavator                                               NORTHING: 7089141 m                TEST DATE: 27/04/2022

                                                                                                                                      Sampling & Testing
              Graphic Log




                                                                                                                                                                   DCP Results
                                                                         Material Description                                                Results &
                                                                                                                                   Type                        (blows per 100 mm)
                                                                                                                                             Comments
                            Water




 RL Depth
 (m) (m)                                                                                                                                                         5   10   15   20
                                    Silty Sandy CLAY CI: stiff, medium to high plasticity, brown and red-brown, fine to medium
                                    grained sand, w>PL




                             0.3 Bore Terminated at 0.3 m.




        1




        2




        3



DRILLING METHOD: Excavator                                                                                                                     CASING: Nil
GROUNDWATER: no groundwater seepage noted at the time of investigation
REMARKS:

                                                                                        LEGEND:
       D     - Disturbed Sample from Auger                                SPT - Standard Penetration Test                        - Groundwater Seepage Level
       B     - Bulk Sample from Auger                                     Is50 - Point Load Result (MPa)                         - Standing Groundwater Level
       C     - Rock Core                                                  PP - Pocket Penetrometer (kPa)                         - Partial Groundwater Loss
       U50   - Undisturbed Sample (mm)                                                                                           - Perched Groundwater Level

Page 21

                                                          ABN 51 640 311 842
                                                          arcosgroup.com.au
                                         Sunshine Coast | Brisbane | Gold Coast




Sunshine Coast | Brisbane | Gold Coast

Page 22

                                                          ABN 51 640 311 842
                                                          arcosgroup.com.au
                                         Sunshine Coast | Brisbane | Gold Coast




Sunshine Coast | Brisbane | Gold Coast

Page 23

                                                          ABN 51 640 311 842
                                                          arcosgroup.com.au
                                         Sunshine Coast | Brisbane | Gold Coast




Sunshine Coast | Brisbane | Gold Coast

Page 24

                                                          ABN 51 640 311 842
                                                          arcosgroup.com.au
                                         Sunshine Coast | Brisbane | Gold Coast




Sunshine Coast | Brisbane | Gold Coast

Page 25

                                                          ABN 51 640 311 842
                                                          arcosgroup.com.au
                                         Sunshine Coast | Brisbane | Gold Coast




   Contact Us

          07 5293 7648

          @arcosgroup

          [email protected]

          arcosgroup.com.au



Sunshine Coast | Brisbane | Gold Coast

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.