1577 06 (A) · OPW15/0208.01

Attached to the e-mail Minor Change to Operational Works Permit OPW15/0208.

of 1

Text shows just the words. Original shows the document exactly as it was published.

Check the original when the exact wording matters.

 

TERMINATE EXHAUST EXTERNAL TO THE
PUMP ROOM AND SO AS TO PROHIBIT
THE ENTRY OF RAINWATER

CONTROL PANEL
ON NEARBY WALL
(TO AS 2941-1995 CLAUSE 8.2.)

               

 

 

BUTTERFLY VALVE
PADLOCKED OPEN

STAINLESS STEEL
FLEXIBLE COUPLING

PRESSURE GAUGE &
GAUGE COCK

NRV

SIZE PRESSURE RELIEF VALVE &
DRAIN LINE TO PUMP MANUFACTURERS

AURAL ALARM
(TO AS 2941-1995 CLAUSE 9.3.9.2. & 9.4.8)

 

 

 

 

 

100 DIA

        
              

 

   
     

RECOMMENDATIONS VENT FAN TO 1008 MAIN
. < MANUFACTURERS
COMPOUND PRESSURE GAUGE \ ater REQUIREMENTS
& GAUGE COCK ‘.
SILENCE! DIESEL PRESSURE
STAINLESS STEEL STAINLESS STEEL 4 SWITCH
FLEXIBLE COUPLING LEXIBLE COUPLING
RESSURE SWITCH , JACKING PUMP PRESSURE
DRAIN. LINE x SWITCH

PUMP ISOLATING VALVE
COMPLYING WITH AS4118.1.6

    

         
                       

IGNITION 12V BATTERY R A
‘DRIVER ESSURE GAUGE

100 DIA 6@ PRESSURE LINE
MILD STEEL SUPPORT

RELIEF VALVE DRAIN. 15@ TEST LINE WITH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

~ 150 VALVE
(REFER FLOOR PLAN) { DISCHARGE TO
FLOOR DRAIN CATE VALVE penn
(REFER FLOOR PLAN) —= UNION
YDROPNEUMATIC ACCUMULATOR
GRADE SLAB TO POINT ty TEST VALVE DETAIL
ADJACENT TO FLOOR DRAIN NTS
STAINLESS STEEL
CONCRETE PLI FLEXIBLE COUPLING |
FLOOR LEVEL JACKING PUM
STAINLESS STEEL
VIBRATION RESISTANT RUBBER MOUNTING PIENIBLE COUPLING
NION
GATE VALVE
NTS
NOTES
1. PIPE DIAMETERS SHOWN ON DIAGRAMMATICS
PROVIDE A CENTRIFUGAL FIRE PUMP HAVING A COMPRESSION IGNITION >. PROVIDE MILD SIEEL SUPPORTS TO
DRIVER & CONTROLLERS COMPLYING WITH AS2941. 2 PROVIDE MILD. STEEL
Sysosomhd 3. ALL STUBS TO GAUGES MUST BRANCH FROM
m. CLEAN” PIPEWORK A MINIMUM OF TWO PIPE
DIAMETERS FROM ANY FITTING OR VALVE,
PROVIDE A PRESSURE MAINTENANCE PUMP COMPLYING WITH AS2941.
THE PUMP SHALL BE CAPABLE OF SUPPLYING A MINIMUM FLOW OF L
1.0L/S AT A HEAD REQUIRED BY THE HYDRANT PUMP SUPPLIER,
A {22.02.18 ISSUE FOR APPROVAL, JS [—
legals aya anes
7 | SPICE CONSULTING L

rot
4 CONSTRUCTION HYDRAULICS CONSULTANTS

Telephone 07 5445 3888
QBSA Facsimile 07 5445 3824 ry
1124616 Email — [email protected] AHSCA

 

 

CUENT SUNSHINE BEACH CONSTRUCTIONS P/L

 

ASSOCIATED CONSULTANT KIDD + CO

 

 

DRAWING = LEVEL: AHD
FIRE PUMP DETAIL SCALE:
Al- 1:

 

 

 

 

 

 

A3— 1:
PROJECT STATUS ISSUE >
PROPOSED UNITS at APPROVAL
39 DUKE ST, JOWG. No. A
SUNSHINE BEACH | tor 7-06
*06 oF 06

 

 

 

 

Used in these records

About this file

File size
105 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

1577 06 (A).pdf · 105 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.