Form 15

 

Compliance certificate for
building design or specification

 

Queensland
Government

This form is to be used by an appointed competent person for the purposes of section 10 of the Building Act 1975 and sections 73
and 77 of the Building Regulation 2021 (Design-specification certificate) stating that an aspect of building work or specification
will, if installed or carried out as stated in this form, comply with the building assessment provisions.

Additional explanatory information is included in the Appendix at the end of this form.

 

 

1, Property description

This section need only be completed
if details of street address and
property description are applicable.

E.g. in the case of (standard/generic)
pool design/shell manufacture and/
or patio and carport systems this
section may not be applicable.

The description must identify all land
the subject of the application.

The lot and plan details (e.g. SP/RP)
are shown on title documents or a
rates notice.

If the plan is not registered by title,
provide previous lot and plan details.

 

 

Street address (include number, street, suburb/locality and postcode)
81 LAKE FLAT ROAD

Lot and plan details (attach list if necessary)
LOT 31 SP149578

Local government area the land is situated in
NOOSA SHIRE COUNCIL

 

 

2.Description of aspect/s certified

Clearly describe the extent of work
covered by this certificate, e.g. all
structural aspects of the steel roof
beams.

PROPOSED ALTERATIONS / RAISING OF EXITING RESIDENCE

 

 

 

3.Basis of certification

Detail the basis for giving the
certificate and the extent to which

tests, specifications, rules, standards,

codes of practice and other
publications were relied upon.

 

AS1170.0 STRUCTURAL DESIGN ACTIONS - GENERAL PRINCIPLES

AS1170.1 STRUCTURAL DESIGN ACTIONS - PERMANENT & IMPOSED ACTIONS
AS1170.2 STRUCTURAL DESIGN ACTIONS - WIND ACTIONS

AS4100. STEEL STRUCTURES

AS4055__ WIND LOADS FOR HOUSING DESIGN CRITERIA N3

AS1684.2 RESIDENTIAL TIMBER FRAME CONSTRUCTION HYNE IN DESIGN 7.5
AS2870 RESIDENTIAL SLABS & FOOTINGS

AS3660.1 TERMITE MANAGEMENT - NEW BUILDING WORK

AS1726 GEOTECHNICAL SITE INVESTIGATIONS

NCC — NATIONAL CONSTRUCTION CODE OF AUSTRALIA

DESIGN FLOOR LIVE LOADS (AS1170.1): DOMESTIC HABITABLE 1.5kPa/BALCONY
2.0kPa

DURABILITY: ALL STEELWORK TO BE OF A TYPE SUITABLE FOR THE ATMOSPHERIC
EXPOSURE

CONDITIONS TO BE ENCOUNTERED, REFER TABLE 3.4.4.2 OF NCC Vol 2 OR MANUF.
DETAILS

 

 

Building Regulation 2021 ¢ Section 73 and 77 © Form 15 © Version 1* September 2021

Page 1 of 3
Log in to download the original file

220221-Killeen-Signed F15&dwgs-24.11.22.pdf · 4.6 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

Full text of the other 11 pages

Page 2

 

4. Reference documentation

Clearly identify any relevant
documentation, e.g. numbered
structural engineering plans.

EBIS SITE CLASSIFICATION & FOOTING/SLAB DESIGN REPORT 220221-SI/FD
DRAWINGS BY EBIS NOS: A3-220221-FD1 TO FD4

DRAWINGS BY EBIS NOS; A3-220221-S1 TO $3

DRAWINGS BY EBIS NOS: A3-220221-1 TO 6

 

 

5. Building certifier reference
number and building development
application number

Building certifier reference number

 

Building development application number (if available)

 

 

 

 

6.Appointed competent person
details

Under Part 6 of the Building
Regulation a person must be
assessed as a competent for the type
of work (design-specification) by the
relevant building certifier.

Name (in full)
DONALD ROBERT STANFIELD

Company name (if applicable)
ENGINEERING & BUILDING INVESTIGATION SE

Contact person
DON STANF

 

 

Business phone number
(07) 5436 9199

Email address
[email protected]

Mobile number

 

Postal address
PO Box 973

BUDDINA

 

Licence class or registration type (if applicable)

Licence or registration number (if applicable)

RPEQ 4177

 

 

7. Signature of appointed competent
person

This certificate must be signed by the

individual assessed and appointed by
the building certifier as competent to

give design-specification help.

 

Signature Date

  

 

LOCAL GOVERNMENT USE ONLY

 

Date received

 

 

Reference number/s

 

 

 

Building Regulation 2021 © Section 73 and 77 © Form 15 ® Version 1* September 2021

 

Page 2 of 3

Page 3

Appendix — explanatory information

IMPORTANT NOTE: it is an offence fora competent person to give a building certifier a document, including this form, that the person
knows or reasonably suspects, is false or misleading.

Who can complete this certificate? (sections 10 of the Building Act 1975 (Building Act) and 73 of Building Regulation 2021 (BR 2021))

A building certifier can accept from a competent person (design — specifications) a certificate stating that the competent person has
assessed the building design or specification for the aspect of building work, and it will, if installed or carried out under the certificate,
comply with the building assessment provisions, including any relevant standards and codes.

Schedule 10 of the BR 2021 defines building design or specification as any material, system, method of building or other thing related to
the design of or specifications for building work.

For a competent person to meet the regulation requirements (section 77 of the BR 2021) they must substantially complete all sections
of this form, including information, such as the design of a particular material, system, method of building or that a building element
complies with the Building Code of Australia or a provision of the Queensland Development Code. It is also important that the details of
the relevant reference documents are included, for example, the applicable Australian Standards or other technical provisions that may
be applicable to the subject work.

What is the purpose of this form? (section 10 of the Building Act 1975)
The information in this form informs the building certifier’s decision making when they are assessing a building development
application and issuing the building development approval for the building work the subject of the certificate (form).

When is this form not required?
The assessment of some building applications will be entirely within the expertise of the relevant building certifier and therefore they
may not seek the help of a competent person. In these instances, this form is not required.

Is a manufacturer or supplier required under the BR 2021 to complete and sign this Form 15, if requested?

No. A manufacturer or supplier of building materials is not required to complete and give this form or any aspect and inspection
certificates if requested by a construction contractor, builder, appointed competent person, ora building certifier.

However, a manufacturer or supplier may give the construction contractor, builder, competent person or the building certifier evidence
of suitability such as a manufacturers statement for an aspect or material that itis compliant with the relevant reference documents in
the BCA.e. the applicable Australian Standard/s.

What if there is not enough space for all the supporting material/documents?

Items 2, 3 and 4 requires the competent person to clearly identify the extent of the assessment that was undertaken for aspect/s of work
identified in this form.

For instance, there is provision for material such as specifications, standards, codes or other relevant publications to be referenced in
the form. However, if the space in the form is not sufficient to accommodate all of this material, you can create and refer to additional
material in an addendum or attachment to the form.

The form is also available in a Microsoft Word version, that you can download and edit to include additional material in the relevant
parts of the form, Note that editing the form in the Microsoft Word version may cause the relevant boxes to expand and increase the
length of the document. This is acceptable and does not change the approved form, provided the section text (description on the left-
hand side of the page) is not altered.

Appointed competent person (design or specification) — (sections 34 and 36 of the BR 2021)

A building certifier must assess and decide to appoint an individual as a competent person before they can, as a competent person,
give design-specification help. The building certifier is required to keep detailed records about what was considered when appointing a
competent person.

A building certifier must be satisfied that an individual is competent to give the type of inspection help having regard to the individual’s

experience, qualifications and skills and if required by taw to hold a licence or registration, that the individual is appropriately registered
or licensed.

An individual is appointed as competent to give design-specification help on or from a particular day. The building certifier can also

decide an individual is a competent person (design-specification) and a competent person (inspection) at the same time or for the same
systems or components of the work,

For further information about assessment of someone as a competent person refer to the Guideline for the assessment of competent persons.

PRIVACY NOTICE

The Department of Energy and Pubtic Works is collecting personal information as required under the Building Act 1975. This information
may be stored by the Department, and will be used for administration, compliance, statistical research and evaluation of building laws.
Your personal information will be disclosed to other government agencies, local government authorities and third parties for purposes
relating to administering and monitoring compliance with the Building Act 1975. Personal information will otherwise only be disclosed to
third parties with your consent or unless authorised or required by law.

Building Regulation 2021 © Section 73 arid 77 ¢ Form 15 © Version 1¢ September 2021 Page 3 of 3

Page 4

 

 

NOTES

GENERAL

1,
2.

Wind Classification W41N/N3

All work to conform to the current Building Code of
Ausiralia- Class 1 & with AS1684.2 Residential Timber
Framed Construction-N3 as applicable fo the work.

The Builder shail check all dimensions, levels& details
before excavation, construction & ordering. Report
discrepancies to designer.

Do not scale. drawings.

The drawings and specifications shall be considered
complementary, and any work and/or materials absent
from one but present or implied in the other shall be
furnished as if they were present in both.

Drawings shall be read in conjunction with consuitants
drawings.

All work, materials & associated fixing methods shall
conform to respective manufacturer's specifications &
Australian Standards as applicable to the work.

Construction shall not proceed before approval in
writing has been received from both the Building
Certifier & Council as applicable.

It is the obligation of the contractor and / or plumbing
contractor to survey alll existing services prior to
construction.

No footing, or wall to encroach the title boundary.

. All proprietary waterproofing systems to be installed in

accordance with the manufacturers recommendations.

Plumbing to be caitied out by a licensed plumber and
in accordance with the requirement of local authorities.
the contractor shall be responsible for all permits and
approvals. all hot water lines shall be fully insulated.
Sanitary plumbing shall be connected to existing system
with materials approved by the focal authority.

Termite protection to be carried out in accordance with
AS3660.1Termite Management- New Building

Vehicle crossing / residential driveways to comply with
RS-49 & RS-50 (RS-56 for rural Driveways)

STORMWATER DRAINAGE

yr.

All stormwater runoff is to be directed to 90mm dia
PVC downpipes to connect to an approved ouilet in
accordance with AS3500.3 or to-water tanks as per
Council Guidelines

The control of stormwater pollution from the building
site shall be carried out in accordance with the
“Best Practice Guidelines”.

WIND CLASSIFICATION W41N/N3
GROUND FLOOR BRACING NOTES

s=—= M12 Bracing Sets

< REQUIRED 109.58 kN
PROVIDED 140.00 KN

A REQUIRED 158.07 KN
PROVIDED 180.0 kN

7 7
i 1 ' 1
po a e ok
20kN
|Z
R
5 °
i
| zg
R
°.
|Z
R
20kN
rr a oy °
i 1 !
[rs 4 [ne -l

 

 

ng goon oe

 

 

 

TOKN

T0kN

 

20kN

TOkN
i
lg
j=
ayaa Tt ° °
bd
NK
LEPTIN
i
i
|
|
4
20kN . °
z
g
z
8
HN °

 

 

NOTE

THE BUILDER SHALL CHECK ALL DIMENSIONS,
LEVELS & DETAILS BEFORE EXCAVATION,
CONSTRUCTION & ORDERING.

REPORT DISCREPANCIES TO EBIS.

IF IN DOUBT -ASK!

 

 

 

 

 

 

 

20KN

 

20kN
bw ene ee ee ee

20kN r

 

 

SUB FLOOR BRACING PLAN

   

 

90mm TIMBER WALL FRAME ON BLOCKWORK

LOAD BEARING WALL (MGP12)

Top plate
Bottom plate

90 x 35 not notched
90 x 35 not notched

Studs 90 x 35 at 450 cts
Nogging 90 x 35 1350 max cts
JOIST TO TOP PLATE

]-framing anchor. 4-2.8 dia nails each leg.

ORIGINAL ISSUE 24.41.2022

 

Engineering & Building Investigation Services

Unit 1/4 Textile Ave, Warana

Proposed Alterations / Raising of Existing Residence
0 Box 973 Buddina 4575 at Lot 31 (No. 81) Lake Flat Road Boreen Point
Phone 07 54369199 Fax 07 54369198 E: [email protected] Client: Robert Killeen

 

BRACING PLAN

Drawing No. A3-220221-S1

 

Scale: 1:100

 

NOVEMBER 2022

 

Drawn: HS

Checked: Edy

 

 

Page 5

 

 

180 80.
7

ra
lo}
1
lol
toy

 

2-M12 BOLTS
TO BEARER

6mm CFW BETWEEN
TOP & BASE PLATE

EXIST. SHS POST WITH
10mm TOP PLATE

ee

LS

NEW SHS EXTENSION

SHS POST WITH PROPOSED ROD
BRACING & EXISTING BEARER TO

BUTT JOINT

 

 

 

 

 

I 30y60601130 |
EXIS. 240X63 LVL gl fo | ot EXIS. 240X63 LVL
BEARER gf | | BEARER
- fo | of
2 1 1
1 |
NEW 75X75X4 SHS POST 2-M12 BOLTS TO NEW 75X75X4 SHS POST
WITH ADJUSTABLE TOP EACH BEARER WITH ADJUSTABLE TOP
LEVELMASTER OR SIMILAR + LEVELMASTER OR SIMILAR
NEW 75X75X4 SHS POST EXTENSION FIX EXISTING POST TO. NEW 75X75X4 SHS POST EXTENSION
10mm BASE PLATE TO MATCH NEW WITH 2-M12 BOLTS 10mm BASE PLATE TO MATCH
EXISTING (175X75X10) EXISTING (175X75X10)
6mm CFW TO NEW SHS 6mm CFW TO NEW SHS

EXIST. SHS POST WITH
10mm TOP PLATE

. es
OX “Nn X KO

VY

 

TO EXISTING NEW SHS EXTENSION TO EXISTING
WITHOUT ROD BRACING &
EXISTING BEARER TO NEW SHS

NEW SHS EXTENSION (END / EXTENSION (AT JOINT)
CONTINUOUS SPAN)

 

(175X75X10}

A 75 ‘
p
See 1Omm BASE PLATE
“r 75
he

BASE PLATE

(PLAN VIEW)

ORIGINAL ISSUE 24.11.2022

 

Engineering & Building Investigation Services

Unit 1/4 Textile Ave, Warana PO Box 973 Buddina 4575
Phone 07 54369199 Fax 07 54369198 E: [email protected]

Proposed Alterations / Raising of Existing Residence
at Lot 31 (No. 81) Lake Flat Road Boreen Point
U Client: Robert Killeen

 

FIXING DETAILS

Drawing No. A3-220221-S2

 

 

Scale: 1:20

NOVEMBER 2022

 

Drawn: HS Checked: -AA2S

 

 

 

Page 6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   
 
   

 

 

 

 

 

 

 

 

 

 

 

°
[-] | °
75 x 75 x 8 THICK
FULLY WELD TAGS FULLY WELDED
THREADED RODS. TO SHS. DRILL FOR yo) a
TO 150 x 50x8 1-M16 BOLT i
THICK TAGS, 9
DRILL FOR BOLT 2
&
&
oO
£
=
PROVIDE TURNBUCKLE
TO JOIN & TIGHTEN
BRACING RODS AS
REQUIRED
°
Lt 2g |__|
bk p
I (D} SPACING 1
SINGLE BRACING SET
ORIGINAL ISSUE 24.11,2022
Engineering & Building Investigation Services Proposed Alterations / Raising of Existing ResidendeSINGLE BRACING SET Drawing No. A3-220221-S3
Unit 1/4 Textile Ave, Warand PO Box 973 Buddina 4575 at Lot 31 (No. 81) Lake Flat Road Boreen Point
T: (07) 5436 9199 F: (07) 5436 9198 E: [email protected] Client: Robert Killeen Scale: nts NOVEMBER 2022 | Drawn: HS Checked: AG

 

 

 

 

 

Page 7

 

NOTES
GENERAL
1. Wind Classification N3

2. All work to conform to the current Building Code of
Australia- Class 1 & with AS1684.2 Residential Timber
Framed Construction-N4 as applicable to the work.

3. The Builder shall check all dimensions, levels& details
before excavation, construction & ordering. Report
discrepancies to designer.

4. Do not scale drawings.

5. The drawings and specifications shall be considered ee

complementary, and any work and/or materials absent aaa a
from one but present or implied in the other shall be | ——— .
furnished as if they were present in both. | ee

 

6. Drawings shall be read in conjunction with consultants
drawings.

7. All work, materials & associated fixing methods shall
conform to respective manufacturer's specifications &
Australian Standards as applicable to the work.

8. Construction shall not proceed before approval in writing
has been received from both the Building Certifier & Council
as applicable.

9. It is the obligation of the contractor and / or plumbing
contractor to survey all existing services prior to
construction.

10. No footing, or wall to encroach the title boundary.

11. All proprietary waterproofing systems to be installed in |
accordance with the manufacturers recommendations.

12. Plumbing to be carried out by a licensed plumber and in
accordance with the requirement of local authorities.

the contractor shall be responsible for all permits and
approvals. all hot water lines shall be fully insulated.
Sanitary plumbing shall be connected to existing system
with materials approved by the local authority.

13. Termite protection to be carried out in accordance with
AS3660.1Termite Management- New Building

STORMWATER DRAINAGE

1. All stormwater runoff is to be directed to 100mm dia
PVC downpipes to connect to an approved outlet in

accordance with AS3500.3 or to water tanks as per

Council Guidelines

 

2. The control of stormwater pollution from the building
site shall be carried out in accordance with the
"Best Practice Guidelines".

 

 

 

Site Plan
- ) 1: 1200 7

 

 

EXACT POSITION OF BUILDING ON THE SITE
TO BE CONFIRMED BY BUILDER IN
ACCORDANCE WITH SURVEY PLAN

 

PROPERTY DESCRIPTION
Lot 31 on SP149578
Area 6.1949 Ha

 

 

 

NORTH

 

 

Engineering & Building Investigation Services

Proposed Alterations / Raising of
Existing Residence
Client - Robert Killeen

 

SITE PLAN

 

 

 

 

 

 

‘ 3 7 Sheet No. ig
Unit 2/4 Textile Ave. Warana_ PO Box 973 Buddina 4575 at Lot 31 (No. 81) Lake Flat Road — 2 ane A3-220221- 1
Boreen Point Drawn b —
Phone 07 54369199 Fax 07 54369198 fawn by HS | _
Checked by “ra x | Scale 1: 1200

 

 

 

Page 8

 

IN RECOGNITION OF THE HAZARDOUS WORK ACTIVITY UNDERTAKEN DURING THE
DEMOLITION, CONSTRUCTION, OPERATION OR MAINTENANCE OF THIS BUILDING, 'THE
WORK HEALTH AND SAFETY ACT 2011' REQUIRES CONTROL MEASURES TO BE
UNDERTAKEN BY THOSE RESPONSIBLE TO PREVENT OR MINIMISE RISKS TO WORKERS
DURING THE DEMOLITION, CONSTRUCTION, OPERATION OR MAINTENANCE OF THIS
BUILDING & ENSURE THAT EACH HAZARD IS IDENTIFIED BEFORE A WORKER
UNDERTAKES THE WORK ACTIVITY.

(REFER TO WORK HEALTH & SAFETY REPORT)

SECTION 46 OF THE ACT REQUIRES "A PERSON WHO HAS A DUTY IN RELATION TO THE
SAME MATTER MUST, SO FAR AS IS REASONABLY PRACTICABLE, CONSULT, COOPERATE
& COORDINATE ACTIVITIES WITH ALL OTHER PERSONS WHO HAVE A DUTY IN RELATION
TO THE SAME MATTER".

SECTION 47 OF THE ACT REQUIRES "THE PERSON CONDUCTING A BUSINESS OR
UNDERTAKING MUST, SO FAR AS IS REASONABLY PRACTICABLE, CONSULT WITH
WORKERS WHO CARRY OUT WORK FOR THE BUSINESS OR UNDERTAKING WHO ARE, OR
ARE LIKELY TO BE, DIRECTLY AFFECTED BY A MATTER RELATING TO WORK HEALTH OR
SAFETY".

SECTION 17 OF THE ACT REQUIRES THE PERSON WHO HAS A DUTY, "TO ELIMINATE
RISKS TO HEALTH & SAFETY OR MINIMISE RISKS TO HEALTH & SAFETY, SO FAR AS IS
REASONABLY PRACTICABLE."

PROVIDE A HAZARD IDENTIFICATION & RISK CONTROL STATEMENT TO ELIMINATE RISKS
TO HEALTH & SAFETY OR MINIMISE RISKS TO HEALTH & SAFETY, SO FAR AS IS

REASONABLY PRACTICABLE, BEFORE WORK ACTIVITY COMMENCES.
(REFER TO WORK HEALTH & SAFETY REPORT)

 

a) As constructed Floor plan

RUMPUS

 
 
 
 
 
 
 
 
 
 
 
 
  
 
  

UP

FAMILY

LOUNGE

 
   

PANTRY

OFFICE

     

 
   
  

 

 

Engineering & Building Investigation Services | Prepcsed Alterations / Raising of

Unit 2/4 Textile Ave. Warana PO Box 973 Buddina 4575

Phone 07 54369199 Fax 07 54369198

Existing Residence

Client - Robert Killeen

at Lot 31 (No. 81) Lake Flat Road
Boreen Point

 

FLOOR PLAN

 

 

Sheet No. _1/6_
Date 24.11.2022
Drawn by

A3-220221- 2

 

 

HS
Checked by Cay DS

 

Scale

: 100

 

 

Page 9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NTH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Di

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

North Elevation

1 1: 100

6371
FROM GROUND LEVEL TO TOP OF ROOF

1900
FROM GROU!
LEVEL TO E

FFL.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1600
PROPOSED
RAISED HEIG

 

 

 

\s
| 6371
FROM GROUND LEVEL TO TOP OF ROOF

1900
FROM GROU

 

 

LEVEL TO EXISs.

pee
|
|

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i

 

iM

 

 

 

 

 

 

 

x

= —_

 

 

 

 

 

 

1600 ,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROPOSED
RAISED HEIG

 

 

 

 

South Elevation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

zZ 1: 100

STAIRS TO COMPLY WITH CURRENT NCC SECTION 3.9.1.2
AND 3.9.1.4

BALUSTRADES ARE SHOWN INDICATIVE ONLY
AND TO COMPLY WITH CURRENT NCC SECTION 3.9.2

FINAL NO. OF STAIRS TO BE DETERMINED BY
BUILDER ON SITE DURING CONSTRUCTION

WHERE WINDOWS TO BEDROOMS (WHERE FLOOR LEVEL IS
2.0m OR GREATER ABOVE THE SURFACE BELOW) ARE LESS
THAN 1.7m ABOVE THE FLOOR, THE OPENING SHALL BE
RESTRICTED TO 125mm MAXIMUM OR FITTED WITHA
SCREEN TO RESIST 250N OF HORIZONTAL OUTWARD FORCE

 

 

Engineering &
Unit 2/4 Textile Ave. Warana

Phone 07 54369199

Building Investigation Services

PO Box 973 Buddina 4575

Fax 07 54369198

 

Proposed Alterations / Raising of
Existing Residence

Client - Robert Killeen

at Lot 31 (No. 81) Lake Flat Road
Boreen Point

ELEVATIONS

 

 

 

Sheet No. —/
Date 24.11.2022 A3-220221- 3
Drawn by HS

 

 

Checked by (OHM | Scale 1: 100

 

 

 

Page 10

 

 

 

 

 

 

 

 

  

    
  

  
 

 

 

 

 

 

 

 

 

West Elevation

2 1: 100

f

 

 

 

 

 

 

 

6371
FROM GROUND LEVEL TO TOP OF ROOF

1900

 

  
  
 

 

   

f

     

[=P ET ET ETT SS) EET SEEN = E11

  

 

 

 

 

 

 

 

 

 

      

     

    

 

 

 

 

 

 

     

     

    

 

  
 
  

  
   

 

——~TFROM GROUN
LEVEL TO EXIS!

| | | FFL;

=|

|) 22) EET IEE} IEE) 11

East Elevation
53

i

 

HII

III

PIS 2 PIE) IS) ISI I IE IS Ee PE E21 PE) I=

2700

PROPOSED
RAISED HEIGH

   

AS CONSTRUCTED UPPER FLOOR

 

Engineering & Building Investigation Services

Unit 2/4 Textile Ave. Warana PO Box 973 Buddina 4575

Phone 07 54369199 Fax 07 54369198

 

Proposed Alterations / Raising of
Existing Residence

Client - Robert Killeen

at Lot 31 (No. 81) Lake Flat Road
Boreen Point

 

 

 

 

 

 

ELEVATIONS

Sheet No. —/—

Date 24.11.2022 A3-220221- 4

Drawn by ___HS

Checked by oud Scale 1: 100

 

 

Page 11

 

3D View 1

Va

View 2
om.

 

 

 

 

 

 

 

 

 

Engineering & Building Investigation Services

Unit 2/4 Textile Ave. Warana

Phone 07 54369199

PO Box 973 Buddina 4575

Fax 07 54369198

 

Proposed Alterations / Raising of
Existing Residence

Client - Robert Killeen

at Lot 31 (No. 81) Lake Flat Road
Boreen Point

3D VIEWS

 

Sheet No.

/

 

Date

24.11.2022

 

 

Drawn by
Checked by

HS

al

 

Scale

A3-220221-5

 

 

Page 12

 

 

+ 3D View 3

 

 

Engineering & Building Investigation Services | Prercsed Alterations / Raising of 3D VIEWS

Existing Residence

 

. Client - Robert Killeen Sheet No l
Unit 2/4 Textile Ave. Warana PO Box 973 Buddina 4575 at Lot 31 (No. 81) Lake Flat Road “94.112

Date 24.11.2022 A3-220221- 6
Boreen Point | peawiby He |
Phone 07 54369199 Fax 07 54369198 y a

 

 

 

 

 

Checked by Curd Skt | Scale

 

 