4 2 3 4 I 5
NOTES:
A 1. ALLLOW VOLTAGE AND ELECTRICAL INSTALLATION Nonoroeen wy ence A
SHALL BE IN ACCORDANCE WITH THESE SPECIFICATION, OXYERNAL WALL OF TELSTRA
TELSTRA CIVIL DESIGN MANUAL, TELSTRA EARTHING EXCHANGE BUILDING TOBE
MANUAL, ALL REFERENCED TELSTRA STANDARD INSTALLED BY TELEPOWER
DOCUMENTATION ALONG WITH ASINZS3000, AS/NZS3008, BY TELEPOWER
ASINZS3015, ASINZS3017, ASINZS1768, AS/ACIFSO08, =
RELEVANT STATE/TERRITORY SPECIFIC INSTALLATION PROPOSED 2C+E 10mm? MAINS, | |
RULES AND ALL OTHER RELEVANT AUSTRALIAN BY SAN TEAM APPROX CABLE RUN 27m
STANDARDS AS APPLICABLE TO PROPOSED WORKS.
2. ALLLOW VOLTAGE AC POWER WORKS SHALL BE
COMPLETED BYLICENSEDELECTRIIANIN, ISOLATOR INSIDE DISTRIBUTION SURGE PROTECTION DEVICE SIMILAR
ACCORDANCE WITH INSTALLATION RULES AND | 100A, 1PH, 240V, 12 POLE BOARD TO CLIPSAL 4AFRC225 IN AN EXTERNALLY
B RELEVANT SAFETY PRACTICES APPLICABLE TO SITE. | ON € B
DISTRIBUTION BOARD MOUNTED ENCLOSURE ON THE H-FRAME
3. ALLWORKS SHALL BE LIAISED AND COORDINATED WITH | 1p56 RATED. LOCKABLE. | ADJACENT TO DISTRIBUTION BOARD
RELEVANT PERSONNEL, SITE REPRESENTATIVES, | A00A,1PH |
LANDOWNER, SITE PROVIDER AND/OR POWER | ISOLATOR| posts sss 4
AUTHORITY AS APPLICABLE | |
4. ALLWORKS SHALL BE AS PER TELSTRA SPECIFICATIONS 32 |
AND APPROVED MOPS INCLUDING LABELLING. SPARE MCB.) —-SURGE PROTECTION DEVICE | | a
5. CONTRACTOR SHALL MAKE THEMSELVES AWARE OF ALL | [20a | 32a SPACES WITH FAIL INDICATION | |
SITE CONDITIONS AND SAFETY REQUIREMENTS PRIOR |, RCBO | RCBO | | |
TO COMMENCING ANY WORK ON SITE. | | | |
6. CONTRACTOR TO VALIDATE ALL APPROVALS AND | power jy POWER | | |
OUTAGES REQUIRED TO CONDUCT PROPOSED WORKS | outer Llouttet | \ \
c THIS INCLUDES BUT IS NOT LIMITED TO ANY DONOR poe TAL Jo poo --- 5 c
SITES AND/OR FAR END SITES WHICH MAY BE IMPACTED
DUE TO PROPOSED WORKS. POWER PLUG |
7. ALL CONTRACTORS WORKING ON TELSTRA FACILITIES (ausTraaNstanparg) =| i tsi‘ EL J
SHALL BE TELSTRA ACCREDITED AS PER TELSTRA | SATELLITE DISH
— PROTOCOLS J -—-— POWER CABLE ANTENNA
8. ALLLV CABLES SHALL BE INSTALLED IN CONDUITS. ANY | PDU/ (XCVR, HP BUC,
EXPOSED CONDUITS SHALL BE UV PROTECTED. | POWER SUPPLY LNB & FEED)
9. NO SEPARATE METERING IS REQUIRED FOR SAN MFR. AC POWER CABLE | LH | MER. DC MFR. DC
he UNLESS SPECIFIED AND DIRECTED BY i, BER | POWER CABLE POWER CABLE
10. NEUTRAL AND ELECTRICAL SAFETY EARTH FOR SAN IL __FQUIPMENT | MFR. DC
D INSTALLATION SHALL BE TAKEN FROM EXCHANGE | | MFR TU POWER CABLE |D
EXISTING MEN
CONDUIT W/ | | CABLES
FIBER | |
| | TTT TTT TT 7-77
mr | I | |
Lo _j | | 1
| | OAN CABINET | |
| | (CABLE MANAGEMENT HOODIAC UNIT | |
Lo NOT SHOWN FOR CLARITY) | |
bee EEE aa
FIBER INTERFACE —MFR. AC DATA CABLE ELECTRONICS
E (aT FRAME) ENCLOSURE E
AC POWER CONNECTION
NOT TO SCALE
FOR SITE SPECIFIC NOTES REFER TO SHEET SO FOR CONSTRUCTION
ORDER [DRAWN] CHKD AMENDMENT EXAM | APPO | DATE [ISS LH
57168| NL | HH |FC-SP30096252WOO94DECON-SATELLITE | RC | IT | 23.03.23] 4 €el stra
SATELLITE ACCESS NODE SITE 182703}
NOOSAVILLE EXCHANGE & RT
F AC POWER CONNECTION
88 GOODCHAP STREET, NOOSAVILLE, QLD 4566
DWG SHT
©felstra Corporation Limited ABN 33 051 775 556 Allrights reserved. NO, Q757 1 68 | NO. Ee
1 2 3 KZ 4 I 5 Cad file: Q757168.dwg A3

 

 

“The copyright and ownership ofthis crawing s assigned to Telstra and must nct be copiad or saved elsewhere without writen permission fam Testa
Log in to download the original file

fc Noosaville Exchange & rt.pdf · 6.1 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.