4 ] 2 3 4 I 5 6
SATELLITE ORIENTATION 15.3°
f REFER SHEET SO NOTE 6

 

| PROPOSED SAN DB TO BE INSTALLED BY TELEPOWER.
/ BUILD CONTRACTOR TO TERMINATE POWER CONDUIT
APPROX. 1.5m UP BUILDING WALL. CONSIDERATIONS
SHALL BE GIVEN TO ALLOW POWER CABLE TO ENTER
BOTTOM CENTRE OF DB (WITH MINIMAL USE OF FLEXIBLE
CONDUIT IF REQUIRED) AND FIBRE CONDUIT TO RUN
UNIMPEDED TO BUILDING WALL PENETRATION LOCATION

 

EXISTING ASHPALT SURFACE NEED TO BE
B REMOVED FOR PROPOSED POWER EARTHING &
FIBRE TRENCHING. REFER TO G4 FOR DETAILS

FENCE RAILS ARE TO BE INSTALLED AT TOP AND
BOTTOM OF THE FENCE. STRAINER TO BE
INSTALLED THROUGH CENTRE OF EACH PANEL.
ENSURE ALL WIRE TWISTS ARE DIRECTED UP OR
OTHERWISE SAFELY (AWAY) FROM WORKERS

PROPOSED SATELLITE DISH
LATITUDE: -26.40640°
LONGITUDE: 153.04667°

EXISTING TELSTRA BUILDING

 

PROPOSED 1.8m SATELLITE DISH MOUNTED ON
PROPOSED 1.8m POLE. REFER TO SHEET T2 FOR DETAILS

SITE TO BE RE-INSTATED TO ORIGINAL STATUS

PROPOSED MOON FOOT PLATFORM.
REFER TO SHEET T2-1 FOR DETAILS

EXISTING TELECOM TOWER
D PROPOSED FENCE AROUND SAN
COMPOUND. REFER TO SHEET T8

FOR DETAILS EXISTING FENCE

 

 

YY

\
E SITE LAYOUT E

 

SCALE 1:250
CONDUIT SCHEDULE 5m 0 5m 10M SoALe 4:250
ITEM A REMARKS

TO BE READ IN CONJUNCTION WITH SHEETS S1, $1-2 & S3. FOR CON STRU CTION
POWER 27m IN 50mm HD uPVC ELECTRICAL CONDUIT

FIBRE mT INP50 CONDUIT ORDER | DRAWN} CHKD AMENDMENT EXAM | APPD | DATE _|ISS elstra —
m 57168 | NL | HH |FC-SP30096252WO094DECON-SATELLITE | RC | IT | 23.03.23} 1 €
EARTH 27m | 35mm? G/Y CABLE IN P32 CONDUIT

SATELLITE ACCESS NODE SITE 182703}

NOTES : NOOSAVILLE EXCHANGE & RT
F 1. FOR SITE SPECIFIC NOTES REFER TO SHEETS SO & S0-1 SITE LAYOUT

2. FOR EME SIGNS NOTED ASX) REFER TO 005486 DOCUMENTS FOR DETAILS. 88 GOODCHAP STREET, NOOSAVILLE, QLD 4566
3, ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE STATED.

DWG SHT =
4, MECHANICAL PROTECTION IS REQUIRED FOR CONDUIT RISERS ON BUILDING. ©elstra Corporation Limited ABN 33 054 775 556. All rights reserved No. Q7571 68 | NO, su

1 l 2 l 3 \Z 4 I 5 Cad file: 0757168.dwg A3

The copyright and cumership of tis drawing assigned io Telstra and must not be copied or saved elsewhere without writen permission from Tals,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
Log in to download the original file

fc Noosaville Exchange & rt.pdf · 6.1 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.