32. Noise emission from mechanical equipment shall comply with the following
requirements:
a. Air-conditioning and Refrigeration
i. 7am to 10pm: Maximum background + 5dB(A)
ii. 10pm to 7am: Maximum background + 3dB(A)
b. Pumps
i. 7am to 7pm: Maximum background + 5dB(A)
ii. 7pm to 10pm: Maximum background + 3dB(A)
iii. 10pm to 7am: No audible noise.
33. Air conditioning units and swimming pool filtration plant shall be located within the
undercover carpark.
34. Kitchen exhaust points for the development must be located and operated in accordance
with Australian Standard AS1668.2-2002 “The use of ventilation and air-conditioning in
buildings” (specifically Section 5.10 – Air Discharges).
35. Submission of written certification from a suitably qualified person confirming that the
noise levels from all mechanical equipment comply when measured at either the
residential boundary or outside the most exposed part of an affected building, whichever
is the closest to the equipment.
The assessment and certification is required immediately after installation of the
equipment and prior to any occupation of the building, and in a format approved by
Council. All equipment should be operating at the same time to test the overall noise
level created.
36. Speakers located in outdoor areas of the site must be selected to be low power, installed
as a distributed speaker system and controlled from a central volume control unit
accessible to staff only and fitted with an electronic noise limiter such that speakers do
not operate at noise levels which exceed 75 dB(C) at 3 metres from the source at any
time. Speakers must be located and oriented such that they are not be directed towards
off-site residential areas. There is to be no live entertainment on site.
Outdoor Lighting Devices
37. Lighting associated with the use must be designed, sited, installed and tested to comply
with Table 2.1 & 2.2 of Australian Standard AS4282-1997 “Control of the obtrusive
effects of outdoor lighting” using a control level of 1.
38. Certification must be submitted to Council from a qualified person which certifies that all
outdoor lighting devices comply with the requirements of this Decision Notice at the time
of commissioning.
For the purpose of certifying outdoor lighting devices for the development, a qualified
person is:
a. Registered Professional Engineer of Queensland;
b. an environmental or electrical design consultant with a minimum of 3 years current
experience in the field of outdoor lighting.
Page 6 of 15
Document Set ID: 22778276
Version: 6, Version Date: 24/01/2024
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
SUPERSEDED - Council Meeting Decision - Other Change - MCU18 0102 02 [As Published].pdfRelated documentApplication case desk ↗
DN - Other Change - MCU18 0102 02 [As Published].pdfRelated documentApplication case desk ↗
About this file
- File size
- 210 KB (small file)
- File type
No other editions are linked here.